ASTM C1668-2009 Standard Specification for Externally Applied Reflective Insulation Systems on Rigid Duct in Heating Ventilation and Air Conditioning (HVAC) Systems.pdf
《ASTM C1668-2009 Standard Specification for Externally Applied Reflective Insulation Systems on Rigid Duct in Heating Ventilation and Air Conditioning (HVAC) Systems.pdf》由会员分享,可在线阅读,更多相关《ASTM C1668-2009 Standard Specification for Externally Applied Reflective Insulation Systems on Rigid Duct in Heating Ventilation and Air Conditioning (HVAC) Systems.pdf(4页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: C 1668 09Standard Specification forExternally Applied Reflective Insulation Systems on RigidDuct in Heating, Ventilation, and Air Conditioning (HVAC)Systems1This standard is issued under the fixed designation C 1668; the number immediately following the designation indicates the year of
2、original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope1.1 This specification covers the requirements and physicalprop
3、erties of reflective insulation systems applied externally toRigid Heating, Ventilation, and Air Conditioning (HVAC) ductsystems operating at or below 250F (121.1 C). Theseinsulation systems consist of one or more low-emittancesurfaces, such as metallic foil or metallic deposits, mounted onsubstrate
4、s to produce reflective air spaces. Reflective insulationsystems derive their thermal performance from surfaces withan emittance of no greater than 0.1 facing enclosed air spaces.1.2 The values stated in inch-pound units are to be regardedas standard. The values given in parentheses are mathematical
5、conversions to SI units that are provided for information onlyand are not considered standard.1.3 This standard does not purport to address all of thesafety concerns, if any, associated with its use. It is theresponsibility of the user of this standard to establish appro-priate safety and health pra
6、ctices and determine the applica-bility of regulatory limitations prior to use.2. Referenced Documents2.1 ASTM Standards:2C 168 Terminology Relating to Thermal InsulationC 335 Test Method for Steady-State Heat Transfer Proper-ties of Pipe InsulationC 390 Practice for Sampling and Acceptance of Therm
7、alInsulation LotsC411 Test Method for Hot-Surface Performance of High-Temperature Thermal InsulationC 1045 Practice for Calculating Thermal TransmissionProperties Under Steady-State ConditionsC 1258 Test Method for Elevated Temperature and Humid-ity Resistance of Vapor Retarders for InsulationC 1338
8、 Test Method for Determining Fungi Resistance ofInsulation Materials and FacingsC 1371 Test Method for Determination of Emittance ofMaterials Near Room Temperature Using Portable Emis-sometersE84 Test Method for Surface Burning Characteristics ofBuilding MaterialsE 96/E 96M Test Methods for Water Va
9、por Transmission ofMaterialsE 2231 Practice for Specimen Preparation and Mounting ofPipe and Duct Insulation Materials to Assess SurfaceBurning Characteristics2.2 Other Test Method:TAPPI Standard T-512 sp-02 Creasing of Flexible Packag-ing Material Paper Specimens for Testing33. Terminology3.1 Defin
10、itions:3.1.1 Unless otherwise noted, the terms used in this speci-fication conform to Terminology C 168.3.2 Definitions of Terms Specific to This Standard:3.2.1 HVAC ductsas pertaining to this standard, ductshaving rigid rectangular or circular cross-section used totransfer air from the air handling
11、 equipment to the conditionedspace and return.3.2.2 insulation spacersmaterial used to form enclosedair spaces that are interior to the reflective insulation system.3.2.3 reflective insulationthermal insulation consisting ofone or more low emittance surfaces, bounding one or moreenclosed air space(s
12、). C 1684. Classification4.1 Products covered by this specification are classifiedaccording to the substrate material and have the physicalproperties as listed in Table 1.4.1.1 Type AProduct with polyethylene foam substrate.4.1.2 Type BProduct with polyethylene bubble pack sub-strate.4.1.3 Type CPro
13、duct with fiberglass substrate.4.1.4 Type DProduct with polyester fiber substrate.1This specification is under the jurisdiction of ASTM Committee C16 onThermal Insulation and is the direct responsibility of Subcommittee C16.21 onReflective Insulation.Current edition approved May 15, 2009. Published
14、June 2009.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.3Available from Technical Association of the Pulp a
15、nd Paper Industry (TAPPI),15 Technology Parkway South, Norcross, GA 30092, http:/www.tappi.org.1Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.4.1.5 Type EProduct with kraft paper substrate.5. Ordering Information5.1 Specify the requ
16、ired thermal resistance.5.2 Specify the number of layers of insulation, width,thickness of the insulation system and the configuration of theduct(s) to be insulated.5.3 Special markings, if required, shall be specified.5.4 Special performance requirements, if any.6. Materials and Manufacture6.1 Refl
17、ective insulation shall consist of low-emittancesurface(s) with substrates and adhesives required to meet thespecified thermal performance and physical properties. Airspaces shall be maintained by use of insulation spacers.6.2 Multiple layer reflective insulation shall be designed toattain the inten
18、ded separation of layers. The design separationshall be maintained by the use of proper size, location andmethod of securing the insulation spacers to the duct system.6.3 DimensionsInsulation and properly sized insulationspacers shall be furnished in dimensions specifically agreedupon between the pr
19、oducer and the buyer.7. Physical Properties7.1 EmittanceLow-emittance surfaces used for this insu-lation shall have a surface emittance of 0.1 or less, asdetermined in accordance with 10.1.7.2 Water Vapor PermeanceThe water vapor permeanceshall be determined in accordance with 10.2 and shall meet th
20、erequirements of Table 1.7.3 Surface Burning CharacteristicsSurface BurningCharacteristics shall be determined in accordance with 10.3.The maximum flame spread index shall not exceed 25 and themaximum smoke developed index shall not exceed 50.7.4 Aging ResistanceThe laminates of the reflective insu-
21、lation shall be tested for aging resistance in accordance with10.4. Three specimens shall be tested. The test specimens shallbe shielded from condensate that drips from the ceiling of thehumidity chamber during the test.7.4.1 After exposure the specimens shall be evaluated forvisible corrosion and d
22、elamination. For purposes of corrosionevaluation, disregard the outer 0.25 in. (6 mm) perimeter. Notested specimen shall exhibit visible corrosion or unaideddelamination of layers.7.4.2 After exposure re-measure the emittance of thesamples. No test specimen shall have greater than 0.02deviation from
23、 the original emittance measurement.7.5 Adhesive PerformanceAdhesives when used shallshow no sign of bleeding when tested in accordance with thetest procedure in 10.5. Disregard bleeding at cut edges.Bleeding or delamination, shall be cause for rejection.7.6 PliabilitySpecimens tested in accordance
24、with theprocedure in 10.6 shall not show cracking or delamination.7.7 Fungi ResistanceSpecimens shall not have growthgreater than the comparative item (southern yellow pine) whentested in accordance with 10.7. Use interpretation of results in7.2 of Test Method C 1338.7.8 Thermal ResistanceDetermine
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMC16682009STANDARDSPECIFICATIONFOREXTERNALLYAPPLIEDREFLECTIVEINSULATIONSYSTEMSONRIGIDDUCTINHEATINGVENTILATIONANDAIRCONDITIONINGHVACSYSTEMSPDF

链接地址:http://www.mydoc123.com/p-465447.html