ASTM C1534-2012 Standard Specification for Flexible Polymeric Foam Sheet Insulation Used as a Thermal and Sound Absorbing Liner for Duct Systems《用作管道系统吸热吸声衬垫的软质聚合物泡沫薄片的标准规格》.pdf
《ASTM C1534-2012 Standard Specification for Flexible Polymeric Foam Sheet Insulation Used as a Thermal and Sound Absorbing Liner for Duct Systems《用作管道系统吸热吸声衬垫的软质聚合物泡沫薄片的标准规格》.pdf》由会员分享,可在线阅读,更多相关《ASTM C1534-2012 Standard Specification for Flexible Polymeric Foam Sheet Insulation Used as a Thermal and Sound Absorbing Liner for Duct Systems《用作管道系统吸热吸声衬垫的软质聚合物泡沫薄片的标准规格》.pdf(4页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: C1534 12Standard Specification forFlexible Polymeric Foam Sheet Insulation Used as aThermal and Sound Absorbing Liner for Duct Systems1This standard is issued under the fixed designation C1534; the number immediately following the designation indicates the year oforiginal adoption or, i
2、n the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope1.1 This specification covers the composition, dimensions,and physical properties of f
3、lexible unfaced foam sheet, used toinsulate interior surfaces of HVAC ducts, plenums and equip-ment used for the distribution of conditioned air with atemperature of up to 250F (121C).1.2 HVAC ducts, plenums and equipment systems typicallyoperate between a temperature range of 50F to 150F (10C to65C
4、) and are designed to meet building code requirements ofmaximum temperatures of 250F (121C).1.3 The values stated in inch-pound units are to be regardedas standard. The values given in parentheses are mathematicalconversions to SI units that are provided for information onlyand are not considered st
5、andard.1.4 This standard does not purport to address all of thesafety concerns, if any, associated with its use. It is theresponsibility of the user of this standard to establish appro-priate safety and health practices and determine the applica-bility of regulatory requirements prior to use.2. Refe
6、renced Documents2.1 ASTM Standards:2C168 Terminology Relating to Thermal InsulationC177 Test Method for Steady-State Heat Flux Measure-ments and Thermal Transmission Properties by Means ofthe Guarded-Hot-Plate ApparatusC209 Test Methods for Cellulosic Fiber Insulating BoardC390 Practice for Sampling
7、 and Acceptance of ThermalInsulation LotsC411 Test Method for Hot-Surface Performance of High-Temperature Thermal InsulationC423 Test Method for Sound Absorption and Sound Ab-sorption Coefficients by the Reverberation Room MethodC518 Test Method for Steady-State Thermal TransmissionProperties by Mea
8、ns of the Heat Flow Meter ApparatusC634 Terminology Relating to Building and EnvironmentalAcousticsC665 Specification for Mineral-Fiber Blanket Thermal In-sulation for Light Frame Construction and ManufacturedHousingC1045 Practice for Calculating Thermal Transmission Prop-erties Under Steady-State C
9、onditionsC1071 Specification for Fibrous Glass Duct Lining Insula-tion (Thermal and Sound Absorbing Material)C1104/C1104M Test Method for Determining the WaterVapor Sorption of Unfaced Mineral Fiber InsulationC1114 Test Method for Steady-State Thermal TransmissionProperties by Means of the Thin-Heat
10、er ApparatusC1304 Test Method for Assessing the Odor Emission ofThermal Insulation MaterialsC1338 Test Method for Determining Fungi Resistance ofInsulation Materials and FacingsE84 Test Method for Surface Burning Characteristics ofBuilding MaterialsE176 Terminology of Fire StandardsE795 Practices fo
11、r Mounting Test Specimens During SoundAbsorption TestsE2231 Practice for Specimen Preparation and Mounting ofPipe and Duct Insulation Materials to Assess SurfaceBurning CharacteristicsG21 Practice for Determining Resistance of Synthetic Poly-meric Materials to Fungi2.2 Other Standards:CAN/ULC-S102 S
12、tandard Method of Test for SurfaceBurning Characteristics of Building Materials and Assem-blies3. Terminology3.1 The definitions of terms used in this specification shallbe in accordance with Terminologies C168, C634, and E176.Incase of any conflicts, Terminology C168 shall be the authority.3.2 Defi
13、nitions of Terms Specific to This Standard:1This specification is under the jurisdiction of ASTM Committee C16 onThermal Insulation and is the direct responsibility of Subcommittee C16.22 onOrganic and Nonhomogeneous Inorganic Thermal Insulations.Current edition approved Feb. 1, 2012. Published Marc
14、h 2012. Originallyapproved in 2002. Last previous edition approved in 2007 as C1534071. DOI:10.1520/C1534-12.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the sta
15、ndards Document Summary page onthe ASTM website.1Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.3.2.1 closed cell foama foam comprised of predominatelyindividual non interconnecting cells.3.2.2 flexible cellulara cellular material th
16、at will notrupture within 60 s when a specimen 1 3 1 3 8 in. in length(25 3 25 3 200 mm) is bent around a 1 in. (25 mm) diametermandrel at a uniform rate of one lap in5sintheform of a helixat a temperature between 65 and 85F (18 and 29C).3.2.3 open cell foama foam made porous by interconnect-ing cel
17、ls.4. Classification4.1 The flexible polymeric insulations of this specificationare classified into Types I and II. Type I is a closed flexiblefoam. Type II is an open cell flexible foam.NOTE 1The primary difference between Type I and Type II materialsare: Type I materials exhibit lower water absorp
18、tion properties and TypeII materials have greater acoustical properties as noted in Tables 1 and 2.5. Materials5.1 These products shall be made of a homogeneous blendof natural or synthetic polymeric materials. Modifications withvarious thermoplastic or thermosetting resins, plasticizers,modifiers,
19、antioxidants, curatives, blowing agents and otheradditives are allowed. These products do not melt whenexposed to heat and are considered to be thermoset materials.5.2 Flexible, polymeric cellular thermal insulations shall beof uniform core density. These insulation materials are avail-able with a s
20、mooth skin surface or coating on one or both sides,and they are to be considered homogeneous for the purposes ofdetermining thermal performance.6. Ordering Information6.1 Specific installation, insulation type, thickness, length,and width suited for the intended use shall be agreed upon bythe purcha
21、ser and supplier.7. Physical PropertiesSee Tables 1 and 2 for Summaryof Requirements7.1 Apparent Thermal ConductivityThe material shall betested for apparent thermal conductivity at 75F (24C) meantemperature in accordance with 12.1. The thermal conductivityfor the average of any four randomly select
22、ed samples, shallnot be more than 0.30 Btu-in./h-sq ftF (0.043 W/m-K) whentested in accordance with 12.1. See Table 1.NOTE 2Consult the local or state building codes for the minimuminstalled thermal resistance, R-value, required to be installed.7.2 Surface Burning CharacteristicsShall be in accor-da
23、nce with 12.2. See Table 1 for requirements.7.3 Hot Surface PerformanceThe insulation shall have noevidence of flaming, glowing, smoldering, visible smoke,delamination, cracking, warpage, melting, dripping or reduc-tion in thickness when tested in accordance with 12.3 at thetemperature specified in
24、Table 1.NOTE 3Hot Surface Performance Characteristics for Type 1MaterialWhen this type of material is used on hot applications, thematerials characteristics will change and should be considered whenselecting the material for an application. Heat will cause the elastomericinsulation to harden. As the
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMC15342012STANDARDSPECIFICATIONFORFLEXIBLEPOLYMERICFOAMSHEETINSULATIONUSEDASATHERMALANDSOUNDABSORBINGLINERFORDUCTSYSTEMS

链接地址:http://www.mydoc123.com/p-465039.html