ASTM C1298-1995(2013) Standard Guide for Design and Construction of Brick Liners for Industrial Chimneys《工厂烟囱砖砌内衬的设计和施工的标准指南》.pdf
《ASTM C1298-1995(2013) Standard Guide for Design and Construction of Brick Liners for Industrial Chimneys《工厂烟囱砖砌内衬的设计和施工的标准指南》.pdf》由会员分享,可在线阅读,更多相关《ASTM C1298-1995(2013) Standard Guide for Design and Construction of Brick Liners for Industrial Chimneys《工厂烟囱砖砌内衬的设计和施工的标准指南》.pdf(13页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: C1298 95 (Reapproved 2013)Standard Guide forDesign and Construction of Brick Liners for IndustrialChimneys1This standard is issued under the fixed designation C1298; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revision, the
2、year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope1.1 This guide covers procedures for the design,construction, and serviceability of brick liners for industrialchi
3、mneys. The structural design criteria are applicable tovertical masonry cantilever structures supported only at theirbase, either by a foundation, a concrete pedestal, or by somemeans from the outer concrete shell. Excluded from directconsideration are single-wythe, sectional brick linings that ares
4、upported on a series of corbels cast in the outer chimney shell.1.2 The values stated in inch-pound units are to be regardedas the standard. The values given in parentheses are forinformation only.1.3 This standard does not purport to address all of thesafety concerns, if any, associated with its us
5、e. It is theresponsibility of the user of this standard to establish appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use.2. Referenced Documents2.1 ASTM Standards:2C395 Specification for Chemical-Resistant Resin MortarsC466 Specification f
6、or Chemically Setting Silicate andSilica Chemical-Resistant MortarsC980 Specification for Industrial Chimney Lining BrickE447 Test Method for Compressive Strength of LaboratoryConstructed Masonry Prisms (Withdrawn 1997)3E111 Test Method for Youngs Modulus, Tangent Modulus,and Chord Modulus2.2 ACI St
7、andard:30788 Practice for the Design and Construction of Cast-In-Place Reinforced Concrete Chimneys42.3 ASCE Standard:ASCE 7-88 Minimum Design Loads for Buildings and OtherStructures (Formerly ANSI A58.1)52.4 Other Standard:1991 Uniform Building Code, International Conference ofBuilding Code Officia
8、ls, California63. Terminology3.1 Notations:a = brick dimension in radial direction (in.)b = brick dimension in tangential direction (in.)c = brick chamfer (in.)Ce= chimney deflection due to earthquake loads (in.)d = outside diameter of brick liner (in.)D = mean liner diameter at a given elevation (i
9、n.)Em= masonry modulus of elasticity as established by performing brick prismtest or by past experience, psifb= critical liner buckling stress, psifd= maximum vertical compressive stress due to dead load, psifde= maximum vertical compressive stress due to the combined effect ofearthquake and dead lo
10、ad, psifdw= maximum vertical compressive stress due to the combined effect ofwind and dead load, psifm= average ultimate masonry compressive strength established byperforming brick prism test or by past experience, psifv= maximum shear stress due to wind or earthquake, psiF.S. = factor of safetyh =
11、total liner height (ft)he= height of liner above elevation being checked for buckling (ft)Le= liner deflection due to earthquake loads (in.)P = constructional out-of-plumbness of liner with respect to shell (in.)r = average mean radius of liner (ft)S = shell deflection due to sun effect (in.)T = lin
12、er deflection due to differential temperature effects (in.)t = wall thickness (in.)v = coefficient of variation in brick prism testsW = shell deflection due to design wind loads (in.) = coefficient of thermal expansion for brick liner (use 3.5 106unlessotherwise established) (in./in./F)1This guide i
13、s under the jurisdiction of ASTM Committee C15 on ManufacturedMasonry Units and is the direct responsibility of Subcommittee C15.05 on MasonryAssemblies.Current edition approved June 1, 2013. Published June 2013. Originallyapproved in 1995. Last previous edition approved in 2007 as C1298 95 (2007).D
14、OI: 10.1520/C1298-95R13.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.3The last approved version of this hi
15、storical standard is referenced onwww.astm.org.4Available from American Concrete Institute (ACI), P.O. Box 9094, FarmingtonHills, MI 48333-9094, http:/www.aci-int.org.5Available from American Society of Civil Engineers (ASCE), 1801 AlexanderBell Dr., Reston, VA 20191, http:/www.asce.org.6Available f
16、rom International Code Council (ICC), 5203 Leesburg Pike, Suite600, Falls Church, VA 22041-3401, http:/www.intlcode.org.Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States14. Significance and Use4.1 History:4.1.1 For many years, brick lin
17、ers have been used with anexcellent record of performance. For the most part, however,the design and construction of brick liners has been based onpast industry practice due to the lack of available informationand knowledge of the physical properties of the brick andmortar, the thermal and seismic b
18、ehavior of brick liners, andmany related characteristics that were not properly or accu-rately defined.4.1.2 The use of scrubbers, which lower gas temperaturesand introduce highly corrosive condensates into the flue gassystem, requires many new design considerations. The effectthat scrubbers have on
19、 brick liners is an ongoing area of study,since a number of liners have experienced growth- anddeflection-related problems which may be attributable, at leastin part, to nonuniform temperature and moisture conditionswithin the liners.4.2 PurposeThe recommendations contained herein rep-resent current
20、 industry practices and serve to define thepertinent considerations that should be followed in the designand construction of brick chimney liners.5. Materials5.1 GeneralThe selection of suitable liner materials, thosecapable of resisting the environment to which they will beexposed, should be based
21、on an evaluation of the uniqueoperating conditions that exist in each application. Although itis not the intent to restrict the applicability of this guide, andwhile other materials may be appropriate in some applications,the chemical-resistant brick and mortar standards set forth in5.2 and 5.3 defi
22、ne the type of materials used in the majority ofbrick liners that are specified, designed, and erected today. Allportions of this guide reflect test data, design requirements, andother practices as they relate to these materials. The provisionsof this guide should be carefully reviewed for applicabi
23、lity ifother materials are specified or used. Due to a greater knowl-edge of overall plant operation, material capabilities, and theflue gas environment, the owners technical representativeshould be responsible for selecting all liner materials.5.2 Brick:5.2.1 Unless the specific application preclud
24、es their use,brick conforming to the requirements of Specification C980should be used. Specification C980 covers solid kiln-fired brickmade of clay, shale, or mixtures thereof.5.2.2 Three types of brick are defined in Specification C980:Types I, II, and III. By definition, the brick types vary,respe
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMC129819952013STANDARDGUIDEFORDESIGNANDCONSTRUCTIONOFBRICKLINERSFORINDUSTRIALCHIMNEYS 工厂 烟囱 内衬 设计

链接地址:http://www.mydoc123.com/p-464139.html