《ASTM C1053-2000(2005) Standard Specification for Borosilicate Glass Pipe and Fittings for Drain Waste and Vent (DWV) Applications《排水沟、污水沟和排出口用的硼硅酸盐玻璃管和配件的标准规范》.pdf》由会员分享,可在线阅读,更多相关《ASTM C1053-2000(2005) Standard Specification for Borosilicate Glass Pipe and Fittings for Drain Waste and Vent (DWV) Applications《排水沟、污水沟和排出口用的硼硅酸盐玻璃管和配件的标准规范》.pdf(18页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: C 1053 00 (Reapproved 2005)Standard Specification forBorosilicate Glass Pipe and Fittings for Drain, Waste, andVent (DWV) Applications1This standard is issued under the fixed designation C 1053; the number immediately following the designation indicates the year oforiginal adoption or,
2、in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon (e) indicates an editorial change since the last revision or reapproval.This standard has been approved for use by agencies of the Department of Defense.1. Scope1.1
3、 This specification covers chemically resistant, low ex-pansion, Type I, borosilicate glass, Class A (see SpecificationE 438), used to manufacture corrosion-resistant pipe and fit-tings for drain, waste, and vent service.1.2 The pipe and fittings covered by the specification areintended for chemical
4、 resistant service above and below gradeunder gravity flow or vacuum conditions.1.3 The pipe and fittings shall have beaded or plain ends.2. Referenced Documents2.1 ASTM Standards:2C 600 Method of Thermal Shock Test on Glass PipeC 623 Test Method for Youngs Modulus, Shear Modulus,and Poissons Ratio
5、for Glass and Glass-Ceramics byResonanceC 693 Test Method for Density of Glass by BuoyancyE 438 Specification for Glasses in Laboratory Apparatus3. Ordering Information3.1 The minimum ordering information for material underthis specification shall include the following information:3.1.1 ASTM designa
6、tion and date of issue,3.1.2 Manufacturers catalog number or parts identification,3.1.3 Quantity ordered,3.1.4 Special test or certification requirements,3.1.5 Special packaging or marking, if required, and3.1.6 Accessory items such as couplings, drains, adapters,and cutters.4. Materials and Manufac
7、ture4.1 The glass components shall represent good workman-ship as consistent with standard glass process capabilities.5. Chemical Requirements Chemical Requirements5.1 The chemical requirements shall be as described inSpecification E 438.6. Physical Requirements6.1 The physical requirements shall be
8、 as described inSpecification E 438.6.2 Refer also to Annex A1 for additional physical require-ments.7. Operating Temperatures7.1 Minimum Operating TemperatureThe minimum ratedoperating temperature for all sizes shall be 40F (40C)provided the material being conveyed is fluid.7.2 Maximum Operating Te
9、mperatureThe maximumrated continuous operating temperature shall be 212F(100C).7.3 Thermal Shock ResistanceThe maximum allowabletemperature differential for installed systems shall be in accor-dance with Table 1 for the various pipe sizes. Maximumtemperature differential refers to an almost instanta
10、neoustemperature change, such as low-pressure steam followeddirectly by a flush of ice cold water, or the reverse. Maximumtemperature differential pertains to either inside or outside pipesurfaces.7.3.1 Thermal shock resistance is not ordinarily tested. Ifthermal shock resistance may be questioned,
11、it shall be testedin accordance with Method C 600. If all pieces tested pass theallowable temperature differential, the lot shall be accepted. Ifone or more failures occur, a retest shall be made using asample size twice that of the first test. If any failures occur onthe retest, the entire shipment
12、 shall be retested.8. Pressure Rating8.1 DWV piping systems are designed for gravity flow only.8.2 All pipe sizes are suitable for vacuum service.9. Dimensions and Permissible Variations9.1 Beaded Flanges:9.1.1 Flange Face FlatnessMaximum permissible devia-tion from a flat plane across the face of a
13、 flange on all sizesshall be116 in. (1.6 mm).1This specification is under the jurisdiction of ASTM Committee C14 on Glassand GlassProducts and is the direct responsibility of Subcommittee C14.05 on Glass Pipe.Current edition approved Sept. 1th, 2005. Published October 2005. Originallyapproved in 198
14、5. Last previous edition approved in 2000 as C 1053 00.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.1Copyr
15、ight ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.9.1.2 Flange Face SquarenessFlange faces of both pipeand fittings shall be square to the pipe centerline within thelimits prescribed in Table 2.9.1.2.1 Squareness of straight pipe lengths sha
16、ll be mea-sured by placing the pipe on rollers, located approximately 2in. (51 mm) from each end, and butting one end against a flatplate perpendicular to the axis of the rollers. The pipe shall berotated and length variation read with a suitable mechanism,such as a dial indicator. The maximum readi
17、ng shall not exceedthat shown in Table 2 for the respective pipe size.9.1.2.2 Pipe fittings shall be measured for flange squarenessby a gage having flat plates constructed at the angle required bythat fitting. One flange shall be firmly placed on one plate, andany difference between the remaining fl
18、ange face and the othersurface plate shall be measured with Feller gages. Differencesshall not exceed the amount shown in Table 2 for the respectivefitting size.9.1.3 Flange Dimensions and SpecificationsBeadedflange dimensions shall be as required by the manufacturer forthe system.9.2 Bow:9.2.1 Bow
19、for All Pipe DiametersBow shall be measuredby supporting the pipe in “V” blocks approximately 2 in. fromeach end with a dial gage at midlength, rotating the pipe full360. The total dial deflection divided by two is the measure ofbow, which shall not exceed 0.25 % of the pipe length.9.3 Dimensions of
20、 All Pipe and Fittings:9.3.1 Dimensional specifications for pipe and common fit-tings shall be as shown in the manufacturers literature. Typicalconfigurations are as illustrated in Figs. 1-45.10. Inspection10.1 Inspection of the material shall be made at the point ofdelivery unless otherwise agreed
21、upon by the purchaser and theseller.11. Packaging11.1 Pipe, fittings, and hardware shall be so packaged as toprevent damage during transportation and handling. Thoseitems packed in containers conforming to all constructionrequirements of consolidated freight classification as to burst-ing tests, siz
22、e limit, and gross mass shall be considered as beingproperly packed.11.2 All hardware items shall be packed in such a way as toprevent contact with glass components. Some typical hardwareitems are shown in Appendix X1.12. Keywords12.1 borosilicate; components; fittings; glass; pipeTABLE 1 Maximum Te
23、mperature Differential for Thermal ShockPipe Size, in. (mm)Sudden TemperatureDifference, Max F (C)112 3 (3876) 200 (93)4 (102) 175 (78)6 (152) 160 (71)TABLE 2 Flange Face SquarenessNominal Pipe Size, in.SquarenessMeasurement,Max, in.112 to 2132336441166564Size, in.A (OD) B (OD)Wall Thick-ness,in.Len
24、gth, ftADiameter, in. Diameter, in.112 2.06 1.84 0.17 5 and 102 2.58 2.34 0.17 5 and 103 3.69 3.41 0.20 5 and 104 4.84 4.53 0.27 5 and 106 7.12 6.66 0.33 5 and 10ALength includes coupling allowance.Nominal OD Over EPSA112 in. 213162in. 35163in. 54in. 6146in. 8916APipe with EPS (expanded polystyrene)
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMC105320002005STANDARDSPECIFICATIONFORBOROSILICATEGLASSPIPEANDFITTINGSFORDRAINWASTEANDVENTDWVAPPLICATIONS

链接地址:http://www.mydoc123.com/p-463158.html