ASTM A927 A927M-2004 Standard Test Method for Alternating-Current Magnetic Properties of Toroidal Core Specimens Using the Voltmeter-Ammeter-Wattmeter Method《使用伏特计-电流计-瓦特计方法测试环形铁芯试.pdf
《ASTM A927 A927M-2004 Standard Test Method for Alternating-Current Magnetic Properties of Toroidal Core Specimens Using the Voltmeter-Ammeter-Wattmeter Method《使用伏特计-电流计-瓦特计方法测试环形铁芯试.pdf》由会员分享,可在线阅读,更多相关《ASTM A927 A927M-2004 Standard Test Method for Alternating-Current Magnetic Properties of Toroidal Core Specimens Using the Voltmeter-Ammeter-Wattmeter Method《使用伏特计-电流计-瓦特计方法测试环形铁芯试.pdf(5页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: A 927/A 927M 04Standard Test Method forAlternating-Current Magnetic Properties of Toroidal CoreSpecimens Using the Voltmeter-Ammeter-WattmeterMethod1This standard is issued under the fixed designation A 927/A 927M; the number immediately following the designation indicates the yearof or
2、iginal adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval.A superscript epsilon (e) indicates an editorial change since the last revision or reapproval.1. Scope1.1 This test method covers the determination of several acmagne
3、tic properties of either laminated ring or toroidal tapewound cores made from flat rolled product.1.2 This test method covers test equipment and proceduresfor determination of specific core loss, specific exciting power,and peak permeability for power and audio frequencies (50 to20 000 Hz) under sin
4、usoidal flux conditions.1.3 This test method, because of the use of a feedback-controlled power amplifier, is well suited for determination ofac magnetic properties at magnetic flux densities above theknee of the magnetization curve and is particularly useful fortesting of high-saturation iron-cobal
5、t alloys (for example,alloys listed in Specification A 801), although use of this testmethod is not restricted to a particular type of material.1.4 This test method shall be used in conjunction withPractice A 34/A 34M and Terminology A 340.1.5 The values and equations stated in customary (cgs-emuand
6、 inch-pound) or SI units are to be regarded separately asstandard. Within this standard, SI units are shown in bracketsexcept for the sections concerning calculations where there areseparate sections for the respective unit systems. The valuesstated in each system may not be exact equivalents; there
7、fore,each system shall be used independently of the other. Combin-ing values from the two systems may result in nonconformancewith this standard.1.6 This standard does not purport to address all of thesafety concerns, if any, associated with its use. It is theresponsibility of the user of this stand
8、ard to establish appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use.2. Referenced Documents2.1 ASTM Standards:2A 34/A 34M Practice for Sampling and Procurement Test-ing of Magnetic MaterialsA 340 Terminology of Symbols and Definitions Rel
9、ating toMagnetic TestingA 697/A 697M Test Method for Alternating Current Mag-netic Properties of Laminated Core Specimen Using theVoltmeter-Ammeter-Wattmeter MethodsA 801 Specification for Iron-Cobalt High-Magnetic Satura-tion Alloys (UNS R30005 and K92650)3. Significance and Use3.1 This test method
10、 is a derivative of Test Method A 697/A 697M specifically designed for testing of toroidal coreswhich are not covered in Test Method A 697/A 697M and fortesting at magnetic flux densities above the knee of themagnetization curve.3.2 Specimen size typically ranges from 1 to 1.25 in. 25.4to 31.8 mm in
11、 inside diameter to 1.5 in. 38.1 mm in outsidediameter with weights ranging from 30 to 60 g. Provided thetest equipment is suitably chosen, there is no obvious limit tothe overall size of core that can be tested. If basic materialproperties are desired, then the requirements of 5.1 must beobserved.3
12、.3 The reproducibility and repeatability of this test methodare such that this test method is suitable for design, specifica-tion acceptance, service evaluation, and research and develop-ment.3.4 When testing under sinusoidal flux conditions at mag-netic flux densities approaching saturation, highly
13、 peaked1This test method is under the jurisdiction of ASTM Committee A06 onMagnetic Properties and is the direct responsibility of Subcommittee A06.01 on TestMethods.Current edition approved Oct. 1, 2004. Published October 2004. Originallyapproved in 1994. Last previous edition approved in 1999 as A
14、 927/A 927M 99.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.1Copyright ASTM International, 100 Barr Harbor
15、 Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.magnetizing waveforms will be present, and the test instru-ments used must have crest factor capabilities of at least 3;otherwise erroneous results will be obtained.4. Apparatus4.1 The apparatus for testing under this test method s
16、hallconsist of as many of the components, described below andschematically illustrated in Fig. 1, as required to perform themeasurements.4.2 Signal GeneratorFor testing at other than line fre-quency (50 or 60 Hz), a low distortion sine wave signalgenerator is required. The frequency accuracy of the
17、signalgenerator should be within 60.1 %. To prevent dc biasing ofthe magnetizing current waveform, a blocking capacitor orisolation transformer should be installed between the signalgenerator and power amplifier.4.3 Power AmplifierA linear power amplifier should beused.3The signal from the secondary
18、 winding of the testspecimen is used for negative feedback control of the magne-tizing waveform. Depending on the power amplifier used, itmay be necessary to install feedback signal conditioningequipment such as an attenuator or amplifier; however, thesignal conditioning equipment must not distort t
19、he feedbackwaveform nor load the secondary winding. Fig. 1 also showsan audio choke connecting the output and feedback terminalsof the amplifier. This choke is intended to prevent dc bias beingintroduced into the magnetizing waveform by providing dcfeedback to the power amplifier. Without such a cho
20、ke, the dcoffset current present in certain power amplifiers will result inlarge dc output currents. This choke may not be neededdepending on the make and model of power supply. Furtherreduction or elimination of bias can be achieved by installingan isolation transformer to transformer couple the pr
21、imarycircuit.4.4 WattmeterAn electronic wattmeter with appropriatevoltage, current and wattage ranges, and bandwidth must beused. The full-scale accuracy of the wattmeter must be betterthan 60.5 %. The wattmeter must have a crest factor capabilityof at least 3 and be capable of accurate measurements
22、 atlow-power factors. The wattmeter must be able to measure rmscurrent and rms voltage to an accuracy of 60.5 % or better;otherwise, separate instruments meeting this accuracy require-ment must be used.4.5 Flux VoltmeterThe flux voltmeter must be a trueaverage responding, high-impedance voltmeter ca
23、librated toread=2 p/4 times the full wave rectified average voltage sothat its indications will be identical to those of a true rmsvoltmeter when reading a pure sinusoidal voltage. The ratedfull-scale accuracy must be 60.5 % or better.4.6 Current-Sensing Resistor (Optional)When peak per-meability is
24、 to be measured, a noninductive, high-precision,low-thermal coefficient of resistance current-sensing resistorshall be used. The resistor must be rated to carry the maximumcurrent used in the test.4.7 Peak Voltmeter (Optional)When peak permeability isto be determined, a high-impedance peak-reading v
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMA927A927M2004STANDARDTESTMETHODFORALTERNATINGCURRENTMAGNETICPROPERTIESOFTOROIDALCORESPECIMENSUSINGTHEVOLTMETERAMMETERWATTMETERMETHOD

链接地址:http://www.mydoc123.com/p-459996.html