ASHRAE REFRIGERATION SI CH 8-2010 EQUIPMENT AND SYSTEM DEHYDRATING CHARGING AND TESTING《脱水设备及系统 充电和测试》.pdf
《ASHRAE REFRIGERATION SI CH 8-2010 EQUIPMENT AND SYSTEM DEHYDRATING CHARGING AND TESTING《脱水设备及系统 充电和测试》.pdf》由会员分享,可在线阅读,更多相关《ASHRAE REFRIGERATION SI CH 8-2010 EQUIPMENT AND SYSTEM DEHYDRATING CHARGING AND TESTING《脱水设备及系统 充电和测试》.pdf(8页珍藏版)》请在麦多课文档分享上搜索。
1、8.1CHAPTER 8EQUIPMENT AND SYSTEM DEHYDRATING,CHARGING, AND TESTINGDehydration (Moisture Removal) 8.1Moisture Measurement 8.3Charging 8.4Testing for Leaks. 8.5Performance Testing . 8.6ROPER dehydration, charging, and testing of packaged refrig-Peration systems and components (compressors, evaporators
2、,and condensing coils) help ensure proper performance and extendthe life of refrigeration systems. This chapter covers the methodsused to perform these functions. It does not address criteria such asallowable moisture content, refrigerant quantity, and performance,which are specific to each machine.
3、DEHYDRATION (MOISTURE REMOVAL)Factory dehydration may be feasible only for certain sizes ofequipment. On large equipment, which is open to the atmospherewhen connected in the field, factory treatment is usually limited topurge and backfill, with an inert holding charge of nitrogen. In mostinstances,
4、 this equipment is stored for short periods only, so thismethod suffices until total system evacuation and charging can bedone at the time of installation.Excess moisture in refrigeration systems may lead to freeze-upof the capillary tube or expansion valve. It also has a negative effecton thermal s
5、tability of certain refrigeration oils e.g., polyol ester(POE). (Chapter 7 has more information on moisture and othercontaminants in refrigerant systems).Except for freeze-up, these effects are not normally detected bya standard factory test.It is important to use a dehydration technique that yields
6、 a safemoisturelevelwithoutaddingforeignelementsorsolvents,becausecontaminantscancausevalvebreakage,motorburnout,andbearingand seal failure. In conjunction with dehydration, an accuratemethod of moisture measurement must be established. Many fac-tors, such as the size of the unit, its application, a
7、nd type of refriger-ant, determine acceptable moisture content. Table 1 shows moisturelimits recommended by various manufacturers for particular refrig-eration system components.Sources of MoistureMoisture in refrigerant systems can be (1) retained on the sur-faces of metals; (2) produced by combust
8、ion of a gas flame; (3) con-tained in liquid fluxes, oil, and refrigerant; (4) absorbed in thehermetic motor insulating materials; (5) derived from the factoryambient at the point of unit assembly; and (6) provided by freewater. Moisture contained in the refrigerant has no effect on dehy-dration of
9、the component or unit at the factory. However, becausethe refrigerant is added after dehydration, it must be considered indetermining the overall moisture content of the completed unit.Moisture in oil may or may not be removed during dehydration,depending on when the oil is added to the component or
10、 system.Bulk mineral oils, as received, have 20 to 30 mg/kg of moisture.Synthetic POE lubricants have 50 to 85 mg/kg; they are highlyhygroscopic, so they must be handled appropriately to preventmoisture contamination. Refrigerants have an accepted commercialtolerance of 10 to 15 mg/kg on bulk shipme
11、nts. Controls at the fac-tory are needed to ensure these moisture levels in the oils and refrig-erant are maintained.Newer insulating materials in hermetic motors retain much lessmoisture compared to the old rag paper and cotton-insulatedmotors. However, tests by several manufacturers have shown tha
12、tthe stator, with its insulation, is still the major source of moisture incompressors.Dehydration by Heat, Vacuum, or Dry AirHeat may be applied by placing components in an oven or byusing infrared heaters. Oven temperatures of 80 to 170C are usu-ally maintained. The oven temperature should be selec
13、ted carefullyto prevent damage to the synthetics used and to avoid breakdown ofany residual run-in oil that may be present in compressors. Air in theoven must be maintained at low humidity. When dehydrating byheat alone, the time and escape area are critical; therefore, the sizeof parts that can be
14、economically dehydrated by this method isrestricted.The vacuum method reduces the boiling point of water belowthe ambient temperature. The moisture then changes to vapor,which is pumped out by the vacuum pump. Table 3 in Chapter 1 ofthe 2009 ASHRAE HandbookFundamentals shows the relation-ship of tem
15、perature and pressure for water at saturation.Vacuum is classified according to the following absolute pres-sure ranges:Low Vacuum 101.325 to 3.5 kPaMedium Vacuum 3500 to 0.130 PaHigh Vacuum 130 to 0.13 mPaVery High Vacuum 130 to 0.13 PaUltrahigh Vacuum 0.13 Pa and belowThe degree of vacuum achieved
16、 and the time required to obtainthe specified moisture level are a function of the (1) type and size ofvacuum pump used, (2) internal volume of the component or sys-tem, (3) size and composition of water-holding materials in the sys-tem, (4) initial amount of moisture in the volume, (5) piping andfi
17、tting sizes, (6) shape of the gas passages, and (7) external temper-atures maintained. The pumping rate of the vacuum pump is criticalonly if the unit is not evacuated through a conductance-limiting ori-fice such as a purge valve. Excessive moisture content, such as apocket of puddled water, takes a
18、 long time to remove because of thevolume expansion to vapor.Vacuummeasurementsshouldbetakendirectlyattheequipment(or as close to it as possible) rather than at the vacuum pump. Smalltubing diameters or long tubing runs between the pump and theThe preparation of this chapter is assigned to TC 8.1, P
19、ositive Displace-ment Compressors.8.2 2010 ASHRAE HandbookRefrigeration (SI)equipment should be avoided because line/orifice pressure dropsreduce the actual evacuation level at the equipment.If dry air or nitrogen is drawn or blown through the equipmentfor dehydration, it removes moisture by becomin
20、g totally or par-tially saturated. In systems with several passages or blind passages,flow may not be sufficient to dehydrate. The flow rate should obtainoptimum moisture removal, and its success depends on the overallsystem design and temperature.Combination MethodsEachofthefollowingmethodscanbeeff
21、ectiveifcontrolledcare-fully, but a combination of methods is preferred because of theshorter drying time and more uniform dryness of the treated system.HeatandVacuumMethod.Heat drives deeply sorbed moistureto the surfaces of materials and removes it from walls; the vacuumlowers the boiling point, m
22、aking the pumping rate more effective.The heat source can be an oven, infrared lamps, or an ac or dc cur-rent circulating through the internal motor windings of semiher-metic and hermetic compressors. Combinations of vacuum, heat,and then vacuum again can also be used.Heat and Dry-Air Method. Heat d
23、rives moisture from thematerials. The dry air picks up this moisture and removes it from thesystem or component. The dry air used should have a dew pointbetween 40 and 73C. Heat sources are the same as those men-tioned previously. Heat can be combined with a vacuum to acceler-ate the process. The he
24、at and dry-air method is effective with open,hermetic, and semihermetic compressors. The heating temperatureshould be selected carefully to prevent damage to compressor partsor breakdown of any residual oil that may be present.Advantages and limitations of the various methods dependgreatly on the sy
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASHRAEREFRIGERATIONSICH82010EQUIPMENTANDSYSTEMDEHYDRATINGCHARGINGANDTESTING 脱水 设备 系统 充电 测试 PDF

链接地址:http://www.mydoc123.com/p-455980.html