ASHRAE OR-16-C061-2016 Analysis of Supply Airflow Rate on the Performance of Radiant Cooling Systems.pdf
《ASHRAE OR-16-C061-2016 Analysis of Supply Airflow Rate on the Performance of Radiant Cooling Systems.pdf》由会员分享,可在线阅读,更多相关《ASHRAE OR-16-C061-2016 Analysis of Supply Airflow Rate on the Performance of Radiant Cooling Systems.pdf(8页珍藏版)》请在麦多课文档分享上搜索。
1、Kishor Khankari is the President at AnSight LLC in Ann Arbor, Michigan Analysis of Supply Airflow Rate on the Performance of Radiant Cooling Systems Kishor Khankari, PhD Fellow ASHRAE ABSTRACT Radiant cooling systems can potentially be more energy efficient than the traditional all air HVAC systems
2、partly due to their low supply air requirements. This paper with the help of Computational Fluid Dynamics (CFD) analysis compares the cooling performance of a traditional all air system with the radiant cooling systems for a typical perimeter office. The effect of supply airflow rate on the cooling
3、performance of both radiant floor and radiant ceiling systems is evaluated. The cooling performance is evaluated in terms of three-dimensional airflow patterns, temperature distribution, thermal comfort of occupants, and resulting cooling capacity of the radiant surfaces. These analyses indicate rad
4、iant cooling systems can provide comparable thermal comfort for occupants at much reduced airflow rates than the traditional all air system. However, the location of the radiant surface and associated supply airflow rates can significantly affect the thermal comfort and cooling capacity of the radia
5、nt systems. The radiant floor system may require higher airflow rate than the radiant ceiling system to provide comparable thermal comfort. However, increasing the airflow rate can significantly reduce the cooling capacity of the radiant floors than the radiant ceilings. Low airflow rates with radia
6、nt floor can create hot zones whereas high airflow rates with radiant ceiling can create cold zones for the occupants. Further the supply airflow rate can significantly affect the relative distribution between the convective and radiative heat transfer components of the radiant floors than the radia
7、nt ceilings. This study concludes that the radiant ceiling with low supply airflow rate can provide better thermal comfort and higher cooling capacity, and therefore, a better option for cooling perimeter offices than radiant floors. It is noted that CFD can be an effective tool in minimizing HVAC d
8、esign risks and gaining valuable insights which can help in optimizing the design of radiant cooling systems. INTRODUCTION Radiant systems primarily employ hydronic cooling and heating with reduced fan power due to reduced requirement of the supply air. Therefore such systems can be potentially more
9、 energy efficient than the traditional all air HVAC systems (Kwang and Olesen 2015, Sastri and Rumsey 2014, Thornton et al. 2009). Air is supplied to the occupied spaces with the radiant heating and cooling systems to maintain certain level of indoor air quality and humidity. Radiant heat transfer o
10、ccurs primarily between the surfaces such as walls, glazing, and radiant (hydronic) surfaces whereas the convective heat transfer occurs between the adjacent air and the radiant surfaces. Although in principle radiant heat transfer is supposed to provide more than 50 percent of the sensible heating
11、or cooling, adequate air movement adjacent to the radiant surfaces is essential for transferring the heat to and from the surfaces to the occupied spaces. In addition the temperature difference between the adjacent air and the radiant surfaces can also affect the cooling capacity of the radiant surf
12、aces. The distribution between the radiative and convective heat transfer to and from the radiant surfaces can depend on several factors including the location and type of sensible heat loads in the space, type and location of radiant system, type and location of supply air diffusers, supply air flo
13、w rate, and the temperature of the supply air. According to previous studies the radiant heat transfer in most cases can be limited to 0.97 Btu/hftF (5.5 W/mK) whereas the convective heat transfer can vary between 0.09 and 0.97 Btu/hftF (0.5 and 5.5 W/mK) which can depend on the surface type, surfac
14、e orientation, and on heating or cooling mode (Kwang and Olesen 2015). The main objective of this study is to compare the performance of a radiant cooling system with the all air overhead supply HVAC system for a small perimeter office using Computational Fluid Dynamics (CFD) simulations. Radiant fl
15、oor and radiant ceiling configurations are analyzed with two different supply airflow rates. The effect of supply airflow rates on the cooling capacity of radiant surfaces are analyzed along with the relative distribution of radiative and convective heat transfer components. The performance of these
16、 systems are compared by analyzing airflow patterns, temperature distribution, and the resulting thermal comfort of the occupants in a three dimensional office space. These analyses were performed systematically by varying a single parameter at a time. VIRTUAL OFFICE SET-UP A three-dimensional, stea
17、dy state, non-isothermal Computational Fluid Dynamics (CFD) model of a perimeter office is developed for this study. As shown in Figure 1 the virtual office has three occupants seated around a table with three computers, a window on one side of the room, a ceiling light, 4-way air supply diffuser, a
18、nd a return grill. The room has about 170 sq. ft. (15.8 m2) floor with 9 feet (2.74 m) ceiling height. The total sensible heat load in the room was assumed to be 19.7 Btu/h per sq. ft. (62 W/m2). The sensible heat load due to three occupants was assumed 4.5 Btu/h per sq. ft. (14 W/m2) whereas sensib
19、le heat load due to the computers and lighting was assumed to be 3.6 Btu/h per sq. ft. (11 W/m2) and 3.1 Btu/h per sq. ft. (10 W/m2), respectively. The room has South facing window with the solar heat gain of 8.6 Btu/h per sq. ft. (27 W/m2). These sensible cooling loads are part load design conditio
20、ns which are more prevalent than the peak design load conditions. The air is supplied through a 4-way diffuser at an angle of 15 degrees to the ceiling. This diffuser is placed close to the window such that one of the four supply air streams is directed towards the window for cooling the window glaz
21、ing. In the case of all air overhead system the total supply airflow rate and the supply air temperature were specified at 150 CFM (71 l/s, 6 ACH) and 55 F (13 C), respectively. In the case of floor and ceiling radiant systems the supply air flow rates were reduced to 25 percent and 50 percent of th
22、e supply airflow rate for the all air system and the supply air temperature was maintained at 55 F (13 C). It was ensured that as per ASHRAE Standard 62.1 the supply airflow rate is always maintained above the typical minimum ventilation airflow requirement of 0.15 cfm/ft2 (1.3 L/s.m2) for the offic
23、e spaces. According to ASHRAE Standard-55 occupants may feel uncomfortable due to contact with the cold floor, and therefore, for rooms with sedentary occupants the recommended minimum floor temperature for cooling is 66 F (19 C) (ASHRAE, 2013b). Accordingly in the case of radiant floor system the f
24、loor temperature was specified at 70 F (21 C) to ensure the surface temperature is not too close to the recommended minimum temperature. Whereas in the case of radiant ceiling system the ceiling temperature was specified at 65 F (18 C). This study assumes the room design set point temperature is 75
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASHRAEOR16C0612016ANALYSISOFSUPPLYAIRFLOWRATEONTHEPERFORMANCEOFRADIANTCOOLINGSYSTEMSPDF

链接地址:http://www.mydoc123.com/p-455784.html