ASHRAE OR-10-029-2010 An Experimental Evaluation of HVAC-Grade Carbon-Dioxide Sensors-Part 3 Humidity Temperature and Pressure Sensitivity Test Results《HVAC-级二氧化碳传感器的实验评估 第3部分 湿度、温.pdf
《ASHRAE OR-10-029-2010 An Experimental Evaluation of HVAC-Grade Carbon-Dioxide Sensors-Part 3 Humidity Temperature and Pressure Sensitivity Test Results《HVAC-级二氧化碳传感器的实验评估 第3部分 湿度、温.pdf》由会员分享,可在线阅读,更多相关《ASHRAE OR-10-029-2010 An Experimental Evaluation of HVAC-Grade Carbon-Dioxide Sensors-Part 3 Humidity Temperature and Pressure Sensitivity Test Results《HVAC-级二氧化碳传感器的实验评估 第3部分 湿度、温.pdf(13页珍藏版)》请在麦多课文档分享上搜索。
1、2010 ASHRAE 271ABSTRACTThis is the third paper in a four-part series reporting onthe test and evaluation of typical carbon-dioxide sensorsused in building HVAC applications. Fifteen models of NDIRHVAC-grade CO2sensors were tested and evaluated todetermine the humidity, temperature, and pressure sens
2、itivityof the sensors. This paper reports the performance of thesensors at various relative humidity, temperature, and pres-sure levels common to building HVAC applications andprovides a comparison with manufacturer specifications.Among the 15 models tested, eight models have a single-lamp, single-w
3、avelength configuration, four models have adual-lamp, single-wavelength configuration, and three modelshave a single-lamp, dual-wavelength configuration.The sensors were tested in a chamber specifically fabri-cated for this research. A description of the apparatus and themethod of test are described
4、 in Part 1 (Shrestha and Maxwell2009). The test result showed a wide variation in humidity,temperature, and pressure sensitivity of CO2sensors amongmanufacturers. In some cases, significant variations in sensorperformance exist between sensors of the same model. Eventhe natural variation in relative
5、 humidity could significantlyvary readings of some CO2sensor readings. The effects of tem-perature and pressure variation on NDIR CO2sensors are un-avoidable without an algorithm to compensate for the changes.For the range of temperature and pressure variation in an air-conditioned space, the effect
6、 of pressure variation is more sig-nificant compared to the effect of temperature variation.INTRODUCTIONThis is the third part of a four-part series of papers report-ing on the test and evaluation of typical wall-mounted CO2sensors used in building HVAC systems. In this study, fifteenmodels of NDIR
7、(non-dispersive infrared) HVAC-grade wall-mounted CO2sensors were tested and evaluated. In all, 45 sen-sors (three from each model) were tested in order to determinethe effects of humidity, temperature, and pressure on the CO2sensors readings. The sensitivity of the sensor reading to eachof these th
8、ree parameters was computed and compared to themanufacturers specifications. The experimental procedureused to test and evaluate the sensors is described in Part 1(Shrestha and Maxwell 2009) of this paper. Among the fifteenmodels tested, eight models have a single-lamp, single-wave-length configurat
9、ion, four models have a dual-lamp, single-wavelength configuration, and three models have a single-lamp, dual-wavelength configuration. All single-lamp, single-wavelength sensors and one single-lamp, dual-wavelengthsensor incorporate an “automatic baseline adjustment” algo-rithm in the sensors elect
10、ronics package. The working prin-ciples of NDIR CO2sensors are described in Part 1 (Shresthaand Maxwell 2009) of this paper.PREVIOUS STUDIESIn the past, limited studies have been done to investigatethe effects of humidity, temperature, and pressure variationson HVAC-grade CO2sensors. Fahlen et al. (
11、1992) evaluatedthe performance of two CO2sensors, one photo-acoustic typeand one infrared spectroscopy type, in lab tests and long termfield tests. The lab tests included performance and environ-mental tests. The authors found that the CO2sensors testedwere sensitive to humidity below a threshold va
12、lue, howeverthe threshold humidity level was not determined and the effectof humidity on the sensors readings was not evaluated.During the low-temperature test at 5C (which was within theAn Experimental Evaluation of HVAC-Grade Carbon-Dioxide Sensors Part 3: Humidity, Temperature, and Pressure Sensi
13、tivity Test ResultsSom S. Shrestha, PhD Gregory M. Maxwell, PhDStudent Member ASHRAE Member ASHRAESom S. Shrestha is a R however, the absolutehumidity remained constant.Established procedures, including guidelines for steady-state conditions, described in Part 1 (Shrestha and Maxwell2009) of this pa
14、per were used to perform the testing.HUMIDITY SENSITIVITY TEST RESULTSThe effect of humidity on a CO2sensors output is deter-mined by comparing the sensor readings at 20% and 60% RHto the sensor reading at 40% RH. The humidity sensitivity testresults are presented graphically in terms of the deviati
15、on ofthe sensor readings at 20% and 60% from the readings at40% RH (i.e., deviation from reading at 40% RH = measuredCO2concentration at a particular RH measured CO2 concen-tration at 40% RH). Figures 1, 2, and 3 illustrate the humiditysensitivity test results for the single-lamp single-wavelength,d
16、ual-lamp single-wavelength, and single-lamp dual-wave-length configurations, respectively. 2010, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Published in ASHRAE Transactions 2010, Vol. 116, Part 1. For personal use only. Additional reproduction,
17、distribution, or transmission in either print or digital form is not permitted without ASHRAEs prior written permission. ASHRAE Transactions 273The humidity sensitivity of each CO2sensor was calcu-lated using a linear regression of the test results. The slope ofthe regression line represents the sen
18、sitivity of the sensor interms of deviation in ppm reading per % change in relativehumidity. The numerical results of the sensor readings at eachof the test conditions along with the calculated sensitivity arealso tabulated. Tables 2, 3, and 4 provide the values forthe three sensor configurations. P
19、ositive values of humiditysensitivity indicate an increase in sensor reading as RH in-creases, and vice versa.The majority of the sensors show little to no sensitivity tohumidity. However, three sensor models were particularlysensitive to humidity. Specifically, all of the sensors frommodels S4 and
20、S7 exhibit positive relative humidity sensi-tivity. Sensitivity values for these sensor range from 1.4 to2.9 ppm/% RH. One sensor from model S14 (sensor A) has asensitivity of 3 ppm/% RH.Table 1. Manufacturer-Specified Temperature Sensitivity, Pressure Sensitivity, and Operating Range for Their Sens
21、orsSensor ModelConfiguration Temperature Sensitivity Pressure SensitivityTemperature and humidity Operating RangeS1 Single-lamp, single-wavelength 5 ppm/1.8F (1C) NA32 to 122F (0 to 50C)0 to 95% RHS2 Single-lamp, single-wavelength NAAdd 6.7% of reading per psi (6.89 kPa) decrease from 14.70 psia (10
22、1.35 kPa)*60 to 90F (15 to 32C)0 to 95% RHS3 Single-lamp, single-wavelength 3 ppm/1.8F (C)*6.7% of reading per psi (6.89 kPa) from 14.70 psia (101.35 kPa)*59 to 90F (15 to 32C)0 to 95% RHS4 Single-lamp, single-wavelength NA NA32 to 122F (0 to 50C)5 to95% RHS5 Single-lamp, single-wavelength 4 ppm/1.8
23、F (C)*6.7% of reading per psi (6.89 kPa)*32 to 122 (0 to 50C)0 to 95% RHS6 Single-lamp, single-wavelength NA9.6% of reading per psi(6.89 kPa) deviation from14.5 psia (100 kPa)*32 to 122F (0 to 50C)0 to 95% RHS7 Single-lamp, single-wavelength NAAdd 7.2% of reading per psi (6.89 kPa) decrease from 14.
24、70 psia (101.35 kPa)*32 to 122F (0 to 50C)0 to 90% RHS8 Single-lamp, single-wavelength NA NA32 to 122F (0 to 50C)0 to 95% RH S9 Dual-lamp, single-wavelength 5 ppm/1.8F (C)9.8% of reading per psi(6.89 kPa)*32 to 122F (0 to 50C)5 to95% RHS10 Dual-lamp, single-wavelength 2 ppm/1.8F (C ) NA23 to 113F (5
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASHRAEOR100292010ANEXPERIMENTALEVALUATIONOFHVACGRADECARBONDIOXIDESENSORSPART3HUMIDITYTEMPERATUREANDPRESSURESENSITIVITYTESTRESULTSHVAC

链接地址:http://www.mydoc123.com/p-455691.html