ASHRAE LV-11-C044-2011 Absorption Refrigeration Cycle Based On Capillary Force.pdf
《ASHRAE LV-11-C044-2011 Absorption Refrigeration Cycle Based On Capillary Force.pdf》由会员分享,可在线阅读,更多相关《ASHRAE LV-11-C044-2011 Absorption Refrigeration Cycle Based On Capillary Force.pdf(9页珍藏版)》请在麦多课文档分享上搜索。
1、Atsushi Tsujimor is a professor at the Department of Mechanical Engineering, Kanto-gakuin University, Yokohama, Japan. Masakazu Ohnuki is an assistant professor at the Department of Mechanical Engineering, Kanto-gakuin University, Yokohama, Japan. g3Absorption Refrigeration Cycle Based On Capillary
2、Force Atsushi Tsujimori Dr.Eng Masakazu Ohnuki M.Sc. Member JSRAE ABSTRACT This paper presents an absorption refrigeration cycle which is driven by capillary pumping. Conventional absorption refrigeration cycles require solution pumps to transfer the solution from a low-pressure absorber to a high-p
3、ressure generator. In contrast, the cycle proposed in the present study involves a low-pressure generator and a low-pressure absorber. The low-pressure generator consists of a heat transfer tube with rectangular grooves, which provide a path for the refrigerant vapor, and a cylindrical capillary wic
4、k inserted into the heat transfer tube. The inside part of the wick and the cooling tubes constitute the absorber. The working solution in the absorber penetrates the wick, after which the refrigerant evaporates due to the heat load transmitted to the heat transfer tube. This evaporation creates a p
5、ressure difference between the evaporated refrigerant vapor and the solution at the liquid-vapor interface, and the high-pressure refrigerant vapor condenses into liquid phase as it cools inside the condenser. In this situation, the high-pressure liquid refrigerant expands via the expansion valve an
6、d evaporates into the evaporator, which results in a decrease in temperature. The low-pressure refrigerant vapor which evaporates into the evaporator is absorbed into the solution inside the absorber. In this cycle, only the refrigerant vapor generated in the generator and the liquid refrigerant in
7、the condenser are kept at high pressure. Therefore, there is no need to use a solution pump to transport the solution. For the purposes of this study, experimental equipment was manufactured in order to verify the effectiveness of the proposed cycle. The experimental equipment consisted of a condens
8、er, an evaporator, a low pressure generator and an absorber, where the generator and the absorber were separated by a porous wick. Furthermore, in order to simplify the experiment, the refrigeration test was performed by using a single-component refrigerant as the working fluid. The resulting decrea
9、se in pressure due to capillary pumping was between 3.3 and 4.7 kPa, and a decrease in temperature of 8.0 to 13.2 K was achieved. INTRODUCTION The increase of concentrated heat fluxes in electronic devices has determined the need for advanced cooling methods. However, the size of electronic componen
10、ts is constantly decreasing, which obstructs the mounting of cooling devices adjacent to the heat source. Heat transport loops that utilize latent heat 12345 have been proposed as a solution to this problem. In addition, we have developed a cooling method based on loop heat pipes 678. However, these
11、 cooling techniques are not as efficient when the ambient temperature is greater than the temperature of the target electronic components. In order to meet the cooling requirements, several types of refrigeration systems, such as vapor compression systems, absorption refrigerators 910, adsorption re
12、frigerators 11 and Stirling coolers 12 have been applied in electronic cooling. In contrast to heat pipes, such cooling devices require mechanical driving parts. Even absorption refrigerators, which are driven mainly by heat, require pumps in order to circulate the solution, which decreases their re
13、liability and applicability as general-purpose cooling devices. In this study, an absorption refrigeration cycle without solution pumps is proposed. In order to maintain the pressure difference between the condenser and the evaporator for the purpose of refrigeration, the generator and the absorber
14、are separated by a capillary wick, and only the generated refrigerant vapor is maintained at high pressure. LV-11-C044364 ASHRAE Transactions2011. American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Published in ASHRAE Transactions, Volume 117, Part 1. F
15、or personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAES prior written permission.PROPOSED CYCLE The Duhring diagram of a conventional absorption cycle is shown in Fig. 1. The absorption cycle includes two pressuriz
16、ation stages, one of which corresponds to the evaporation and absorption range and the other corresponds to the generation and condensation range. A solution pump raises the solution pressure from the absorption range to the generation range and transfers the solution from an absorber into a generat
17、or. However, only a pair composed of a high pressure condenser and a low pressure evaporator is needed in order to achieve refrigeration. Therefore, the high-pressure solution inside the generator is needed only for the purpose of generating high-pressure refrigerant vapor. The cycle proposed in thi
18、s study is shown in Fig. 2. In contrast to a conventional absorption cycle, the absorber and the generator operate in the same pressure range. Figure 1 Duhring diagram of conventional absorption cycle Figure 2 Absorption refrigeration cycle proposed in this study Temperature PressurePLPHTe Tc T gPre
19、ssurePLPHTemperatur TeTcTg 2011 ASHRAE 365In other words, a solution pump which transfers the low-pressure solution to the high pressure region becomes unnecessary. In order to realize such a cycle, the maximum pressure difference Pmaxof the liquid phase and the gas phase shown in Eq. 1 is maintaine
20、d by using a porous material (wick) in the generator which separates the vapor channels and the solution reservoir inside the absorber. The working solution in the absorber penetrates the wick, after which the refrigerant evaporates due to the heat load transmitted to the heat transfer tube. This ev
21、aporation creates a pressure difference between the evaporated refrigerant vapor and the solution at the liquid-vapor interface. The high-pressure refrigerant vapor condenses into liquid phase as it cools inside the condenser. Next, the high-pressure liquid refrigerant expands via the expansion valv
22、e and evaporates into the evaporator, which produces a decrease in temperature. Finally, the low-pressure refrigerant vapor, which evaporates into the evaporator, is absorbed into the solution in the absorber after it is cooled. In this cycle, only the refrigerant vapor generated in the generator an
23、d the liquid refrigerant in the condenser are maintained at high pressure. Therefore, there is no need to use a solution pump to transport the solution from the absorber to the generator. Here, the pressure difference Pmaxconsists of the pressure difference P between the condenser and the evaporator
24、 in the expansion stage and the decrease in pressure caused by the flow of the refrigerant and the solution during the cycle. Because the decrease in pressure caused by the flow of the refrigerant and the solution depends on the system configuration, only the pressure difference Pwin the wick is con
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASHRAELV11C0442011ABSORPTIONREFRIGERATIONCYCLEBASEDONCAPILLARYFORCEPDF

链接地址:http://www.mydoc123.com/p-455447.html