ASHRAE LV-11-C006-2011 Proportional-Integral-Plus (PIP) Control System for Individual Thermal Zones in a Small Ventilated Space.pdf
《ASHRAE LV-11-C006-2011 Proportional-Integral-Plus (PIP) Control System for Individual Thermal Zones in a Small Ventilated Space.pdf》由会员分享,可在线阅读,更多相关《ASHRAE LV-11-C006-2011 Proportional-Integral-Plus (PIP) Control System for Individual Thermal Zones in a Small Ventilated Space.pdf(9页珍藏版)》请在麦多课文档分享上搜索。
1、Ali Youssef, Vasileios Exadaktylos, Sezin E. zcan, Daniel Berckmans M3-BIORES: Measure, Model 27.56”25.60”15.75”) were used. Step inputs in ventilation rate and inlet air temperature are applied and temperature responses at 30 sensor locations are recorded. First order transfer function data-based m
2、odels are identified for modeling the dynamic behavior of temperature in each of the 20 cells. A Proportional-Integral-Plus PIP control system is designed based on the identified models to control the temperature in each of the 20 cells individually. INTRODUCTION An imperfectly mixed fluid is charac
3、terized by spatio-temporal distributions in environmental variables (temperature, humidity, gas concentrations, dust concentrations, etc.) of which the values and the evolution are influenced by the flow pattern of the fluid and the interaction with the living organisms (Barber and Ogilvie, 1982; Be
4、rckmans, 1986). It is recognized that these spatio-temporal distributions in the micro-environmental variables are a serious limitation for improving both the quality of the life or the living organisms and the quality of the products and the energy efficiency of the production process (e.g. De Moor
5、 and Berckmans, 1993). On a macro-scale level, a lot of energy is lost in the inefficient control of the imperfectly mixed indoor environment. Barber and Ogilvie (1982) suggest that multiple flow regions, stagnant zones and short-circuiting of air to the exhaust outlet are the major causes of incomp
6、lete mixing. Therefore, the development of models for advanced control system design must account adequately for these imperfect mixing processes (Price et al., 1999). In applications where the ventilated process is supposed to be homogeneous, one strives to achieve a spatially homogeneous distribut
7、ion of heat and mass. On the other hand, if the ventilated process is supposed to be heterogeneous, a spatially heterogeneous distribution of heat and mass is desired. For example, in ventilated rooms which are not entirely LV-11-C00648 ASHRAE Transactions2011. American Society of Heating, Refrigera
8、ting and Air-Conditioning Engineers, Inc. (www.ashrae.org). Published in ASHRAE Transactions, Volume 117, Part 1. For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAES prior written permission.Figure 1. Schemati
9、c 3D diagram of the test installation Heater occupied, it is important to achieve good air conditions and thermal comfort in the occupied zone, without providing too large amounts of fresh air and heat in those parts of the room where it is not required (Sandberg, 1981; Van Brecht, 2004). In the pre
10、sent paper, the data-based modeling approach (e.g. Young, 1993; Young et al, 1998) is applied to the problem of modeling and controlling imperfect mixing in ventilated air space. Modeling is applied to data obtained from ventilation/heating experiment carried out on a small scale instrumented chambe
11、r. One advantage of the data-based model is its simplicity and ability to characterize the dominant model behavior of a dynamic system. This makes such a model an ideal basis for model-based control system design (Taylor et al, 1996; Price et al, 1999; Taylor et al, 2004). In this study, it is propo
12、sed that a data-based model for temperature in fixed spatial zones will be used in the design of Proportional-Integral-Plus (PIP) control system. TEST INSTALLATION AND EXPERIMENTS The research work presented in this paper is based on the analysis of data from planned experiments in a small scale tes
13、ted instrumented chamber in the Laboratory of Measure, Model and Manage Bioresponses (M3-BIORES) at the Katholieke Universiteit Leuven. The test chamber represented in the figure 1, has an inner dimension of length = 0.70 m (27.56”), width = 0.65 m (25.60”), and height = 0.4 m (15.75”) and is equipp
14、ed with an electrical heater with maximum capacity of 224 W. Two axial fans are installed, one in the inlet, which forced the incoming air over the heater before the air enters the chamber, while the second fan (exhaust fan) in the outlet to force out the air from the chamber. The chamber wall was c
15、onstructed with Plexiglas, wood with aluminum framing. The ceiling of the chamber was constructed with Plexiglas of 0.008 m (0.315”) thickness rested on aluminum framing. The inlet of the system composed of two series of ducting system first a circular ducting of 0.1055 m (4.15”) inner diameter, whe
16、re inlet fan was installed followed by a square ducting of outer dimension of 0.12 0.12 m (4.72” 4.72”) of made up of 0.018 m (0.71”) thick wooden wall, inside this section the heater was fixed. The temperature inside the test chamber could be changed by changing the inlet temperature which is regul
17、ated by the in/outlet fans and the heater voltages.A 2D grid of 30 calibrated temperature sensors (Semiconductors LM35) with and accuracy of 0.1 oC were arranged uniformly in 6 5 matrix of with a total dimension of length = 0.55 m and width = 0.44 m. The 2D grid of sensors were lowered 0.16 m downwa
18、rd from the ceiling to make a horizontal 2D grid of sensors suspending on the empty space of the chamber. The velocity of the exhaust air was measured by velocity sensor, which was installed inside the circular outlet ducting. A measurement and data collection unit with programmable measurement freq
19、uency was used for the data acquisition. All measurements were recorded every second and logged in the computer. 2011 ASHRAE 49During the course of the initial research reported in this paper, experiments have been carried out with step increases in both ventilation rate (over the range 9-40 m3.h-15
20、.30-23.5 cfm) and heating power (over the range 40-170 W; 136.5-580 Btu.h-1). A typical example of these step experiments is given in figure 2. The figure shows inlet temperature response (third graph) during and experiment with steps increase in inlet ventilation rate (top graph) from 9 to 27 and t
21、o 40 m3.h-1(5.30, 15.9, and 23.5 cfm), and with steps up in heating power from 40 to 100 and to 170 W (136.5, 341, and 580 Btu.h-1)and down in reveres sequence. The step experiments are designed in such way that all the steps up and down in heating power are repeated with each step in ventilation ra
22、te with time period of 20 minutes for each step in heating power. 2D TEMPERATURE DISTRIBUTION AND SPATIAL CLASSIFICATION In this study a grid system that involves 5265 cells (8165) is built based on two-dimensional interpolation between the 30 temperature measurements points (65 sensors grid). Figur
23、e 3a shows a typical example for the 2D temperature spatial distribution using the (8165) grid system at ventilation rate of 9 m3.h-1(5.3 cfm) and 100 W (341.21 Btu.h-1) heating power. In order to have spatially fixed zones for control purposes the horizontal area of the test chamber is divided into
24、 20 equal squared cells (54) and the average temperature of each cell is calculated at each time instance null. The cell Figure 2. Measured steps in ventilation rate (top graph), steps in heating power (second graph), and the inlet temperature (third graph) Step.(3) Step. (2) Step. (1) 50 ASHRAE Tra
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASHRAELV11C0062011PROPORTIONALINTEGRALPLUSPIPCONTROLSYSTEMFORINDIVIDUALTHERMALZONESINASMALLVENTILATEDSPACEPDF

链接地址:http://www.mydoc123.com/p-455409.html