ASHRAE 4703-2004 A Study on the Control Methods for Radiant Floor Heating and Cooling System in Residential Building《一份研究报告 在住宅建筑中地板辐射采暖和制冷系统的控制方法》.pdf
《ASHRAE 4703-2004 A Study on the Control Methods for Radiant Floor Heating and Cooling System in Residential Building《一份研究报告 在住宅建筑中地板辐射采暖和制冷系统的控制方法》.pdf》由会员分享,可在线阅读,更多相关《ASHRAE 4703-2004 A Study on the Control Methods for Radiant Floor Heating and Cooling System in Residential Building《一份研究报告 在住宅建筑中地板辐射采暖和制冷系统的控制方法》.pdf(11页珍藏版)》请在麦多课文档分享上搜索。
1、4703 A Study on the Control Methods for Radiant Floor Heating and Cooling System in Residential Building Seong-Ryong Ryu Myoung-Souk Yeo, Ph.D. ABSTRACT when applying the radiant floor cooling system using Ondol-the Korean traditional radiantfloor heating system- it is important to select a precise
2、control method to maintain a stable roam temperature andfloor surface temperature and prevent surface condensation. Therefore, it is necessary to systematize various control methods and to conduct a compar- ative study of the respective control methods so as to be able to control the radiant floor h
3、eating and cooling system e ciently. As well as evaluating the level ofstabili of room tenzper- ature and floor surface temperature, we performed this study to search for a control method to minimize condensation during the cooling period without a dehumidijcation system. Based on the results of thi
4、s study, we are going to develop a radiant-floor cooling system integrated with a dehumid$ca- tion system. We aim to deal with indoor comfort in company with concern for condensation. In this study, computer simulations and model experi- ments wereperformed for this comparative analysis on control m
5、ethods usedfor the radiantfloor heatingandcooling system. And, on the basis of the results of our analysis on the control performances of respective control methods, we evaluated the applicability of control methods for the radiant floor heating and cooling system. INTRODUCTION In Korea, installatio
6、n of cooling systems in residential buildings was not taken into account due to factors such as technical problems, efficiency, and past living standard. However, today, with the growth of the industry and increase in the GNP, residents have begun to emphasize convenience Jae-Han Lim Kwang-Woo Kim,
7、Arch.D. and comforts of living. Therefore, the demand for cooling systems and installations of packaged air conditioners (PAC) has been increasing. Unfortunately, the use of PAC for cooling in residential buildings has been found to have negative effects on the environment and, apparently, causes th
8、e problem of sudden peak of electric power demand in summer. Moreover, some of the problems of a conventional cooling system with PAC include draft, local discomfort, and room temperature fluctuation. So it has become necessary to develop a cooling system that can reduce the problems caused by the u
9、se of PAC. Korean residential buildings, in general-particularly apart- ment buildings-are finished with Ondol, the Korean tradi- tional radiant floor heating system. The radiant floor heating system has been widely used as a heating method by flowing hot water into tubes embedded in the floor. And
10、so, in devel- oping a cooling system, it would be more advantageous to utilize the existing floor heating system rather than to adapt a separate system, in which case one would have to consider effective heatingkooling transformation of the floor area, conservation of resources, and the environment.
11、 Thus, the radiant floor cooling system using Ondol has been proposed as an alternative (RIESSNU 2003). In order to apply a radiant floor heating system for cooling during a hot and humid summer in Korea, there is a need to examine various factors such as surface condensation, floor surface temperat
12、ure, vertical room air temperature difference, etc. Developing accurate control is especially crucial in main- taining the stability of room temperature and floor surface temperature and preventing surface condensation. Therefore, it is important to identify the problems that may arise in the heatin
13、g and cooling panel system and to develop an appropi- ate control method that can quickly respond to such a problem and restore temperature stability. Also, it is necessary to eval- uate respective control performances through the performance Seong-Ryong Ryu and Jae-Han Lim are doctoral students, My
14、oung-Souk Ye0 is an assistant professor, and Kwang-Woo Kim is a professor in the Department of Architecture, Seoul National University, Seoul, Korea. 106 02004 ASHRAE. of a comparative analysis of control methods for the radiant floor heating and cooling system. In this study, we classified the vari
15、ous existing control methods that have been proposed or those that have been applied by control parameters until now. With water temper- ature control methods and water flow rate control methods, we performed computer simulations and experiments in the labo- ratory for the comparative analysis. In a
16、ddition, we conducted analysis of the control performances of each control method to evaluate the applicability of control methods for the radiant floor heating and cooling system. CONTROL METHODS FOR RADIANT FLOOR HEATING AND COOLING SYSTEM In the past, various control methods for the radiant floor
17、 heating system have been suggested and applied by research- ers. To control the radiant floor heating and cooling system efficiently on the basis ofthese control methods, it is necessary to systematize various control methods and to do a compara- tive study of each control method through computer s
18、imula- tions and experiments in the laboratory. First, we classified existing control methods that have been suggested or applied until now by control parameters. Control Parameters Control parameters for the radiant floor heating and cool- ing system can be classified into input variables, controll
19、ed variables, and manipulated variables, as shown in Table 1. It may be much simpler and systematic to classi Algren 1953). In order to control the flow rate of supply water, there are two types of control methods that can be used-the continuous flow rate control and the intermittent flow rate contr
20、ol. Vari- able flow control has a continuous flow rate, and onoff bang- bang control and odoff pulse-width modulation (PWM) control have a intermittent flow rate (Tekmar 1996). The on/ off bang-bang control (called the onoff control) is installed in almost every apartment building in Korea. The appl
21、ication of variable flow control is rare because it is difficult to control the flow rate precisely in the range of low flow rate due to nonlin- ear correlation between flow rate and heat output (Bourne 1989). Classification of Control Parameters Table 1. ASHRAE Transactions: Research 107 Table 2. C
22、ontrol Methods for the Radiant Floor Heating and Cooling System I I l Control Parameters Continuous flow Constant flow Flow rate L Heat Flux Constant Temperature Variable Temperature - Outdoor reset control Flux modulation I Supply Water Temperature intermittent flow - Variable flow Variable flow co
23、ntrol - Outdoor reset + - Bang-bang control Ordoff bang-bang control bang-bang control Pulse-width modula- Ordoff PWM control Outdoor reset + - tion(PWM) onioffPWM control Outdoor reset with indoor temperature feedback control The water temperature plus flow rate control methods are control methods
24、for multiple zones, where the supply water temperature is controlled by sensing the outdoor temperature, according to which the water flow rate is intermittently controlled using an odoff valve. The water temperature plus flow control method can be classified into outdoor reset plus odoff bang-bang
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASHRAE47032004ASTUDYONTHECONTROLMETHODSFORRADIANTFLOORHEATINGANDCOOLINGSYSTEMINRESIDENTIALBUILDING 一份

链接地址:http://www.mydoc123.com/p-454286.html