ASHRAE 4699-2004 Dehumidification Characteristics of Commercial Building Applications《商业建筑申请RP-1121的除湿特色》.pdf
《ASHRAE 4699-2004 Dehumidification Characteristics of Commercial Building Applications《商业建筑申请RP-1121的除湿特色》.pdf》由会员分享,可在线阅读,更多相关《ASHRAE 4699-2004 Dehumidification Characteristics of Commercial Building Applications《商业建筑申请RP-1121的除湿特色》.pdf(12页珍藏版)》请在麦多课文档分享上搜索。
1、4699 (RP-1121) Dehumidification Characteristics of Com me rcia I Bu i Id i n g Ap p I i cat i on s Michael J. Brandemuehl, Ph.D., P.E. Member ASHRAE ABSTRACT ASHRAE Research Project 11 21 -Rp: Evaluating the Abil- ity of Unitary Equipment to Maintain Adequate Space Humid- ity Levels: Phase 1, was es
2、tablished to develop aplan to guide the evaluation of humidity control by unitary HVAC equip- ment. Fart of the development of the plan involved the evalu- ation of dehumidjcation requirements in different building applications and different climates. This paper describes the analysis of building lo
3、ad characteristics to identi internal gains always exceed envelope heat loss, even in winter. Figure 5 shows an analogous plot of hourly zone latent load when the indoor conditions are maintained at 50% relative humidity. Unlike the sensible load, there is relatively little influence of outdoor cond
4、itions on latent load since there is assumed to be no diffusion of moisture through the envelope and the building is assumed to be sufficiently pressurized that infiltration is limited to 0.1 cfm/ft2 (0.5 L/s m2). Figures 4 and 5 also show the impact of the ventilation on HVAC system loads for a ven
5、tilation rate of 0.3 cfm/ft2 (1.5 L/s m2), which corresponds to the minimum requirement of the ventilation rate procedure of ANSI/ ASHRAE Standard 62-2001. Ventilation increases the sensible loads when the outside air temperature is warmer than the zone temperature and decreases the sensible loads w
6、hen it is lower. The figure shows that, with ventilation, heating is required when the outdoor air temperature is below about 58F. Under cooling design conditions, the HVAC system loads are almost doubled due to ventilation. The results of Figure 5 dramatically illustrate the role of ventilation on
7、latent loads when outside air humidity level is higher than the room humidity setpoint. The slope of the data line in the figure is directly proportional to the ventilation airflow rate. Figures 4 and 5 clearly show the impact of ventilation on the sensible and latent loads on an HVAC system. Howeve
8、r, ASHRAE Transactions: Research 71 Outdoor Temperature, G -17 -7 3 13 23 33 - 10 O 10 20 30 40 50 60 ?O 80 90 I00 Outdoor Temperature, F Figure 4 Sensible cooling loads, large retail store, Atlanta. 0.3 cfm/f? (1 5 Us mz) - U- ri 8 / -40 4 30 20 10 -I 10 5 O O -0.m O 0.002 0.004 0.006 0.008 0.01 0.
9、012 Difference Between Outdoor end Indoor Humidity Ratio Figure 5 Latent cooling loads, large retail store, Atlanta. the individual loads are not necessarily the most important indicator of the ability of HVAC equipment to maintain adequate indoor humidity. The relative comparison between the sensib
10、le and latent loads is a more valuabIe indicator of the dehumidification performance of HVAC equipment. Figure 6 illustrates this comparison by showing the frequency of occurrence of the HVAC load sensible heat ratio, defined as the ratio of the sensible load to the total load. (In the figures, an S
11、HRof-1 indicates neither sensible nor latent loads during the hour.) 72 Figure 6 gives SHR histograms for three different ventilation scenarios. The first graph represents the case where there is no ventilation. The sensible load dominates the latent load, and the SHR of the loads occurs mostly with
12、in the range of 9.9 to 1 .O. When adding ventilation at a rate of O. 1 cfm/ft2 (0.5 L/s m2), latent loads are increased and the occurrence profile is shifted down to SHRs in the range of0.7 to 0.9. When the ventilation rate is increased to 0.3 cfm/ft2 (1.5 L/s m2), many hours are shifted down to SHR
13、s of 0.4 to 0.7, which typically cannot be met by conventional packaged HVAC ASHRAE Transactions: Research systems. A similar trend was also found in all other applications and cities. The building load characteristics presented above indi- cate a strong dependence on outdoor conditions, especially
14、in the presence of ventilation loads. As shown in Figures 4 and 5, sensible loads are a relatively strong function of outdoor temperature, and latent loads are dnven by outdoor humidity. Other building types exhibit similar load dependencies. Figure 7 shows the sensible load characteristics for the
15、four building types. The dashed lines represent the zone loads (without ventilation) and the solid lines represent the system loads, including ventilation. The amount of ventilation varies “-7 , W+ht%75F.SG%RH Figure 6 SHR distribution, large retail store, Atlanta. with each building type according
16、to the requirements of Standard 62, with values ranging from 0.15 to 1.0 cfm/ft2 (0.75 to 5.0 L/s m2). Note that eachpair of lines crosses at the zone setpoint of 75“F, since ventilation air at the zone temper- ature does not increase the sensible load. Similar sets of curve can be generated for the
17、 latent loads in the building. In virtually all cases, the zone loads without ventilation are very small compared to the loads associated with the ventilation air, as illustrated in Figure 5. That is, the slope of the latent load line, analogous to sensible load lines in Figure 7, is simply proporti
18、onal to the ventilation rate. The ability of unitary HVAC equipment to maintain adequate control of indoor humidity levels is most signifi- cantly affected by the sensible heat ratio of the loads. That is, the magnitudes of the sensible or latent loads are less impor- tant than their coincidence. Th
19、e different curves in Figure 7 indicate that different buildings have different occurrences of sensible and latent load levels. The SHR frequency distributions ofFigure 6 captured this coincidence for the retail building in Atlanta. Similar SHR distributions can be generated for the different buildi
20、ng types. Figure 8 shows these distributions for the four building types in Atlanta. The figure shows the hours of occurrence of SHR for the case of no ventilation (the zone loads) and with an outdoor ventilation airflow that depends on the building type. As noted above, the retail store SHR values
21、fall between 0.5 and 0.8 with the recommended ventilation rate, which is often below that available from conventional unitary HVAC equipment. If the SHR of the HVAC equipment is greater than that required by the loads, indoor humidity levels will rise above the setpoint of 50% RH. Outdoor Temperatur
22、e, C -1 7 -7 3 13 23 33 30 25 20 s f 8 15 u- L J 6 s 10 5 O 90 80 70 6o N 50 $ u- 40 4 30 20 10 O m O 10 20 30 40 50 60 70 80 90 100 Outdoor Temperature, F Figure 7 Sensible load characteristics for four prototypical applications. ASHRAE Transactions: Research 73 Resiaurani lmm Room No Venhlahon Sen
23、sibie Heat Ratio -i Figure 8 SHR distributions, various applications, Atlanta. With lower internal gains, the office has fewer hours during the year with cooling loads. However, ventilation reduces the SHR of the system loads to the 0.7-0.9 range, which can generally be met by conventional unitary e
24、quip- ment. There are many hours when the addition of ventilation air eliminates all loads, suggesting that economizer cooling However, the net sensible heat ratio of the annual cooling loads is reducedin eveiy location. As expected, Houston and Atlanta show the most dramatic impact of ventilation o
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASHRAE46992004DEHUMIDIFICATIONCHARACTERISTICSOFCOMMERCIALBUILDINGAPPLICATIONS 商业 建筑 申请 RP1121 除湿 特色 PDF

链接地址:http://www.mydoc123.com/p-454282.html