ARMY UFGS-21 13 24 00 10-2007 AQUEOUS FILM-FORMING FOAM (AFFF) FIRE PROTECTION SYSTEM《水成膜泡沫消防系统》.pdf
《ARMY UFGS-21 13 24 00 10-2007 AQUEOUS FILM-FORMING FOAM (AFFF) FIRE PROTECTION SYSTEM《水成膜泡沫消防系统》.pdf》由会员分享,可在线阅读,更多相关《ARMY UFGS-21 13 24 00 10-2007 AQUEOUS FILM-FORMING FOAM (AFFF) FIRE PROTECTION SYSTEM《水成膜泡沫消防系统》.pdf(36页珍藏版)》请在麦多课文档分享上搜索。
1、*USACE / NAVFAC / AFCESA / NASA UFGS-21 13 24.00 10 (October 2007)-Preparing Activity: USACE SupersedingUFGS-21 13 24.00 10 (April 2006)UNIFIED FACILITIES GUIDE SPECIFICATIONSReferences are in agreement with UMRL dated October 2007Latest change indicated by CHG tags*SECTION TABLE OF CONTENTSDIVISION
2、 21 - FIRE SUPPRESSIONSECTION 21 13 24.00 10AQUEOUS FILM-FORMING FOAM (AFFF) FIRE PROTECTION SYSTEM10/07PART 1 GENERAL1.1 REFERENCES1.2 SUBMITTALS1.3 AFFF SYSTEM1.4 SYSTEM OPERATIONAL FEATURES1.5 SUBMITTAL PREPARERS QUALIFICATIONS1.6 INSTALLERS QUALIFICATIONS1.7 REGULATORY REQUIREMENTS1.8 SPARE PART
3、SPART 2 PRODUCTS2.1 STANDARD PRODUCTS2.2 REQUIREMENTS FOR FIRE PROTECTION SERVICE2.3 PRESSURE RATINGS2.4 NAMEPLATES2.5 UNDERGROUND PIPING SYSTEMS2.6 ABOVEGROUND PIPING SYSTEMS FOR WATER OR AFFF SOLUTION2.6.1 Pipe2.6.2 Grooved Fittings and Couplings2.6.3 Non-Grooved Fittings2.6.4 Flanges and Gaskets2
4、.6.4.1 Bolts2.6.4.2 Nuts2.6.4.3 Washers2.6.5 Pipe Hangers2.6.6 Control Valve2.6.7 Check Valve2.7 ABOVEGROUND PIPING SYSTEMS FOR AFFF CONCENTRATE2.7.1 Pipe2.7.2 Fittings2.7.3 Pipe Hangers2.7.4 Control ValvesSECTION 21 13 24.00 10 Page 1Provided by IHSNot for ResaleNo reproduction or networking permit
5、ted without license from IHS-,-,-2.8 ALARM CHECK VALVE ASSEMBLY2.9 AUTOMATIC WATER CONTROL VALVE ASSEMBLY (DELUGE VALVE)2.10 MECHANICAL ALARM DEVICE2.11 FIRE DEPARTMENT CONNECTION2.12 BASKET STRAINER2.13 REDUCED PRESSURE BACKFLOW PREVENTION ASSEMBLY2.14 DISCHARGE DEVICES2.14.1 Sprinkler2.14.2 Fixed
6、Nozzle2.14.3 Oscillating Monitor Nozzle Assembly2.15 AFFF LIQUID CONCENTRATE2.16 DIAPHRAGM TANK BALANCED PRESSURE PROPORTIONING SYSTEM2.17 PUMPED BALANCED PRESSURE PROPORTIONING SYSTEM2.17.1 AFFF Concentrate Storage Tank2.17.2 AFFF Concentrate Pump2.17.3 AFFF Pump Controller2.17.4 Power Supply2.17.5
7、 AFFF Pressure Maintenance Pump2.17.6 Pressure Balancing Valve2.17.7 Pressure Sustaining Valve2.18 BALANCED PRESSURE PROPORTIONER (RATIO CONTROLLER)2.19 AFFF CONCENTRATE CONTROL VALVE ASSEMBLY2.20 FOAM SYSTEM CONTROLS2.20.1 Zone Annunciator2.20.2 System Zoning2.20.2 Primary Power Supply2.20.3 Emerge
8、ncy Power Supply2.20.3.1 Storage Batteries2.20.3.2 Battery Charger2.21 ALARM INITIATING DEVICES2.21.1 Waterflow Pressure Alarm Switch2.21.2 Vane-type Waterflow Switch2.21.3 Heat Detector-Spot Type2.21.4 Continuous Linear Thermal Detector2.21.5 Combination Ultraviolet-Infrared Flame Detector2.21.6 No
9、zzle System Actuation Station2.21.6.1 Enclosure2.21.6.2 Horn2.22 VALVE SUPERVISORY (TAMPER) SWITCH2.23 NOTIFICATION APPLIANCES2.24.1 Electronic Signaling Device2.24.2 Alarm HornPART 3 EXECUTION3.1 INSTALLATION3.1.1 Aboveground Piping3.1.1.1 Joints3.1.1.2 Reducers3.1.1.3 Sprinkler Riser Nipples (Spri
10、gs)3.1.1.4 Sprinkler Deflectors3.1.1.5 Pipe Supports and Hangers3.1.1.6 Pipe Penetrations3.1.1.7 Piping Pitch3.1.1.8 Escutcheons3.1.1.9 Drains3.1.1.10 Identification Signs3.1.2 Underground Piping3.2 EXCAVATION, TRENCHING AND BACKFILLINGSECTION 21 13 24.00 10 Page 2Provided by IHSNot for ResaleNo rep
11、roduction or networking permitted without license from IHS-,-,-3.3 ELECTRICAL WORK3.3.1 Overcurrent and Surge Protection3.3.2 Grounding3.3.3 Wiring3.3.4 Control Panel3.3.5 Detectors3.3.6 Manual Actuation Stations3.3.7 Notification Appliances3.4 PIPE PAINTING AND LABELING3.4.1 Painting3.4.2 Pipe Iden
12、tification3.5 PRELIMINARY TESTS3.5.1 Flushing3.5.2 Hydrostatic Tests3.5.3 Alarm Check and Automatic Water Control Valves3.5.4 Nozzles3.5.5 AFFF Concentrate System3.5.6 Control System Tests3.6 FINAL TEST3.6.1 Requirements3.6.1.1 Pretest Requirements3.6.1.2 Videotaping3.6.1.3 Manufacturers Services3.6
13、.1.4 Materials and Equipment3.6.1.5 Facility and Environmental Protection3.6.2 Control System Tests3.6.3 AFFF Proportioning System Tests3.6.4 Post-discharge Test Requirements3.7 POSTED INSTRUCTIONS3.8 TRAINING- End of Section Table of Contents -SECTION 21 13 24.00 10 Page 3Provided by IHSNot for Res
14、aleNo reproduction or networking permitted without license from IHS-,-,-*USACE / NAVFAC / AFCESA / NASA UFGS-21 13 24.00 10 (October 2007)-Preparing Activity: USACE SupersedingUFGS-21 13 24.00 10 (April 2006)UNIFIED FACILITIES GUIDE SPECIFICATIONSReferences are in agreement with UMRL dated October 2
15、007Latest change indicated by CHG tags*SECTION 21 13 24.00 10AQUEOUS FILM-FORMING FOAM (AFFF) FIRE PROTECTION SYSTEM10/07*NOTE: This guide specification covers requirements for foam-water AFFF fire protection sprinkler and nozzle systems.Edit this guide specification for project specific requirement
16、s by adding, deleting, or revising text. For bracketed items, choose applicable items(s) or insert appropriate information.Remove information and requirements not required in respective project, whether or not brackets are present.Comments and suggestions on this guide specification are welcome and
17、should be directed to the technical proponent of the specification. A listing of technical proponents, including their organization designation and telephone number, is on the Internet.Recommended changes to a UFGS should be submitted as a Criteria Change Request (CCR).*PART 1 GENERAL*NOTE: The comp
18、lete design of the AFFF system must be shown on the project drawings. There are no provisions in this UFGS for the Contractor to perform hydraulic calculations or to lay out the system. (For aircraft hangar applications, refer to ETL 1110-3-484.) Use sprinkler hydraulics software for hydraulic calcu
19、lation of the fire protection system. Assure that the design analysis clearly describes the design approach and includes hydraulic calculations. The drawings SHOULD include complete pipe and equipment layout WITH SPACE ENVELOPE REQUIRED FOR INSTALLATION AND OPERATION OF EACH SECTION 21 13 24.00 10 P
20、age 4Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-SYSTEM COMPONENT SHOWN. THE DRAWINGS SHOULD ALSO INCLUDE sprinkler and nozzle locations, elevation views of the piping showing vertical location of sprinklers and piping with respect to the ceiling
21、 and floor heat detectors, control panels, AFFF control panel zoning, wiring, foam storage tank, pumps, and other associated equipment. Consider pipe hanger requirements when laying out the system to ensure that the Contractor can provide hangers per NFPA 13.*1.1 REFERENCES*NOTE: This paragraph is u
22、sed to list the publications cited in the text of the guide specification. The publications are referred to in the text by basic designation only and listed in this paragraph by organization, designation, date, and title.Use the Reference Wizards Check Reference feature when you add a RID outside of
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ARMYUFGS21132400102007AQUEOUSFILMFORMINGFOAMAFFFFIREPROTECTIONSYSTEM 水成膜 泡沫 消防系统 PDF

链接地址:http://www.mydoc123.com/p-449637.html