1、 4100 N. FAIRFAX DR., SUITE 200 ARLINGTON, VIRGINIA 22203 2007 STANDARD for PERFORMANCE RATING OF THERMOSTATIC REFRIGERANT EXPANSION VALVES Standard 750 Copyright Air-Conditioning and Refrigeration Institute Provided by IHS under license with ARI Not for ResaleNo reproduction or networking permitted
2、 without license from IHS-,-,-IMPORTANT SAFETY DISCLAIMER ARI does not set safety standards and does not certify or guarantee the safety of any products, components or systems designed, tested, rated, installed or operated in accordance with this standard/guideline. It is strongly recommended that p
3、roducts be designed, constructed, assembled, installed and operated in accordance with nationally recognized safety standards and code requirements appropriate for products covered by this standard/guideline. ARI uses its best efforts to develop standards/guidelines employing state-of-the-art and ac
4、cepted industry practices. ARI does not certify or guarantee that any tests conducted under its standards/guidelines will be non-hazardous or free from risk. Note: This standard supersedes ARI Standard 750-2001. Price $10.00 (M) $20.00 (NM) Copyright 2007, by Air-Conditioning and Refrigeration Insti
5、tute Printed in U.S.A. Registered United States Patent and Trademark Office Copyright Air-Conditioning and Refrigeration Institute Provided by IHS under license with ARI Not for ResaleNo reproduction or networking permitted without license from IHS-,-,-TABLE OF CONTENTS SECTION PAGE Section 1. Purpo
6、se1 Section 2. Scope.1 Section 3. Definitions 1 Section 4. Test Requirements 2 Section 5. Rating Requirements.2 Section 6. Minimum Data Requirements for Published Ratings 3 Section 7. Marking and Nameplate Data 3 Section 8. Conformance Conditions .3 TABLES Table 1. Standard Rating Conditions 3 APPEN
7、DICES Appendix A. References - Normative 4 Appendix B. References - Informative.4 Appendix C. Recommended Maximum Operating Pressures for Pressure-Limiting Type Thermostatic Refrigerant Expansion Valves - Informative5 Appendix D. Recommended Color Coding for Valve Identification by Refrigerant - Inf
8、ormative 6 Appendix E. Recommended Standard Connection Sizes - Informative 7 TABLES FOR APPENDICES Table C1. Recommended Maximum Operating Pressures for Pressure-Limiting Type Thermostatic Refrigerant Expansion Valves 5 Table D1. Recommended Color Coding for Valve Identification by Refrigerant.6 Cop
9、yright Air-Conditioning and Refrigeration Institute Provided by IHS under license with ARI Not for ResaleNo reproduction or networking permitted without license from IHS-,-,-Table E1a. Recommended Standard Connection Sizes - IP Nominal.7 Table E1b. Recommended Standard Connection Sizes - SI Nominal.
10、7 Copyright Air-Conditioning and Refrigeration Institute Provided by IHS under license with ARI Not for ResaleNo reproduction or networking permitted without license from IHS-,-,-ARI STANDARD 750-2007 1 PERFORMANCE RATING OF THERMOSTATIC REFRIGERANT EXPANSION VALVES Section 1. Purpose 1.1 Purpose. T
11、he purpose of this standard is to establish for Thermostatic Refrigerant Expansion Valves: definitions; test requirements; rating requirements; minimum data requirements for Published Ratings; marking and nameplate data; and conformance conditions. 1.1.1 Intent. This standard is intended for the gui
12、dance of the industry, including manufacturers, engineers, installers, contractors and users. 1.1.2 Review and Amendment. This standard is subject to review and amendment as technology advances. Section 2. Scope 2.1 Scope. This standard applies to Thermostatic Refrigerant Expansion Valves for use wi
13、th refrigerants listed in 2.1.1 at evaporator temperatures between 50F 10C and -40F -40C. 2.1.1 Refrigerants. The refrigerants included in this standard are: R-12, R-22, R-134a, R-404A, R-407C, R-410A, R-502 and R-507A. Section 3. Definitions All terms in this document follow the standard industry d
14、efinitions in the current edition of ASHRAE Terminology of Heating, Ventilation, Air Conditioning and Refrigeration unless otherwise defined in this section. 3.1 Capacity of Thermostatic Refrigerant Expansion Valves. The refrigerating effect produced by the evaporation of refrigerant which will pass
15、 through the valve under the following specified conditions: a. Liquid refrigerant temperature at the valve inlet b. Saturated evaporator temperature c. Pressure difference across the valve d. Static superheat set point e. Superheat change from the set point 3.2 Maximum Operating Pressure (MOP). The
16、 maximum equalizer (internal or external) pressure permitted by a pressure-limiting type Thermostatic Refrigerant Expansion Valve (See Appendix C). 3.3 Published Rating. A statement of the assigned values of those performance characteristics, under stated Rating Conditions, by which a unit may be ch
17、osen to fit its application. These values apply to all units of like nominal size and type (identification) produced by the same manufacturer. The term Published Rating includes the rating of all performance characteristics shown on the unit or published in specifications, advertising or other liter
18、ature controlled by the manufacturer, at stated Rating Conditions. 3.3.1 Application Rating. A rating based on tests performed at application Rating Conditions (other than Standard Rating Conditions). 3.3.2 Standard Rating. A rating based on tests performed at Standard Rating Conditions. 3.4 Rating
19、Conditions. Any set of operating conditions under which a single level of performance results and which causes only that level of performance to occur. 3.4.1 Standard Rating Conditions. Rating conditions used as the basis of comparison for performance characteristics. Copyright Air-Conditioning and
20、Refrigeration Institute Provided by IHS under license with ARI Not for ResaleNo reproduction or networking permitted without license from IHS-,-,-ARI STANDARD 750-2007 2 3.5 “Shall“ or “Should“. “Shall“ or “should“ shall be interpreted as follows: 3.5.1 Shall. Where “shall“ or “shall not“ is used fo
21、r a provision specified, that provision is mandatory if compliance with the standard is claimed. 3.5.2 Should. “Should“ is used to indicate provisions which are not mandatory but which are desirable as good practice. 3.6 Thermostatic Refrigerant Expansion Valve. A controlling device which regulates
22、the flow of volatile refrigerant into an evaporator of a refrigeration system and which is actuated by changes in evaporator pressure and superheat of the refrigerant gas leaving the evaporator. 3.7 Thermostatic Refrigerant Expansion Valve Pressure Drop. The pressure drop across the valve, which is
23、the net pressure difference between the valve inlet and outlet. 3.8 Thermostatic Refrigerant Expansion Valve Superheat. The difference between the temperature of the thermal bulb and the dew point temperature corresponding to the refrigerant pressure at the valve outlet, or at the equalizer connecti
24、on, when provided. 3.8.1 Static Superheat. The superheat at which the manufacturer calibrates or “sets“ the thermostatic expansion valve. 3.9 Vapor-Free (Subcooled) Liquid Refrigerant. Refrigerant which has been cooled below the bubble point temperature for a given pressure. Section 4. Test Requirem
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ARI7502007PERFORMANCERATINGOFTHERMOSTATICREFRIGERANTEXPANSIONVALVESPDF

链接地址:http://www.mydoc123.com/p-429462.html