ARI 710-2004 Standard for Performance Rating of Liquid-Line Driers《液体干燥剂作业评定标准》.pdf
《ARI 710-2004 Standard for Performance Rating of Liquid-Line Driers《液体干燥剂作业评定标准》.pdf》由会员分享,可在线阅读,更多相关《ARI 710-2004 Standard for Performance Rating of Liquid-Line Driers《液体干燥剂作业评定标准》.pdf(11页珍藏版)》请在麦多课文档分享上搜索。
1、 2004 STANDARD for 4100 N. FAIRFAX DR., SUITE 200 ARLINGTON, VIRGINIA 22203 PERFORMANCE RATING OF LIQUID-LINE DRIERS Standard 710 Copyright Air-Conditioning and Refrigeration Institute Provided by IHS under license with ARINot for ResaleNo reproduction or networking permitted without license from IH
2、S-,-,-Price $12.50 (M) $25.00 (NM) Printed in U.S.A. Copyright 2004, by Air-Conditioning and Refrigeration Institute Registered United States Patent and Trademark Office IMPORTANT SAFETY DISCLAIMER ARI does not set safety standards and does not certify or guarantee the safety of any products, compon
3、ents or systems designed, tested, rated, installed or operated in accordance with this standard/guideline. It is strongly recommended that products be designed, constructed, assembled, installed and operated in accordance with nationally recognized safety standards and code requirements appropriate
4、for products covered by this standard/guideline. ARI uses its best efforts to develop standards/guidelines employing state-of-the-art and accepted industry practices. ARI does not certify or guarantee that any tests conducted under its standards/guidelines will be non-hazardous or free from risk. No
5、te: This standard supersedes ARI Standard 710-86. Copyright Air-Conditioning and Refrigeration Institute Provided by IHS under license with ARINot for ResaleNo reproduction or networking permitted without license from IHS-,-,-TABLE OF CONTENTS SECTION PAGE Section 1. Purpose1 Section 2. Scope.1 Sect
6、ion 3. Definitions 1 Section 4. Tubing Connections2 Section 5. Test Requirements 2 Section 6. Rating Requirements.2 Section 7. Minimum Data Requirements for Published Ratings .4 Section 8. Marking and Nameplate Data .4 Section 9. Conformance Conditions 4 TABLES Table 1. Applicable Refrigerant System
7、s .1 Table 2. Published Ratings .2 Table 3. Flow Rate per Ton of Refrigeration4 FIGURES Figure 1. Example of Water Capacity Rating Calculation for Refrigerant 134a at 75F 24C .5 APPENDICES Appendix A. References - Normative .6 Appendix B. References - Informative6 Appendix C. Guide for Selecting a L
8、iquid-line Drier - Informative.7 Copyright Air-Conditioning and Refrigeration Institute Provided by IHS under license with ARINot for ResaleNo reproduction or networking permitted without license from IHS-,-,-Copyright Air-Conditioning and Refrigeration Institute Provided by IHS under license with A
9、RINot for ResaleNo reproduction or networking permitted without license from IHS-,-,-ARI STANDARD 710-2004 1PERFORMANCE RATING OF LIQUID-LINE DRIERS Section 1. Purpose 1.1 Purpose. The purpose of this standard is to establish for Liquid-line Driers: definitions; tubing connections; test requirements
10、; rating requirements; minimum data requirements for Published Ratings; marking and nameplate data; and conformance conditions. 1.1.1 Intent. This standard is intended for the guidance of the industry, including manufacturers, engineers, installers, contractors and users. 1.1.2 Review and Amendment.
11、 This standard is subject to review and amendment as technology advances. Section 2. Scope 2.1 Scope. This standard applies to Liquid-line Driers utilizing solid Desiccants designed for use in the liquid line of all types of refrigeration and air-conditioning systems. 2.2 Applicability. This standar
12、d applies to Liquid-line Driers for use in refrigerant systems employing the halocarbon refrigerants listed in Table 1, as described in ANSI/ASHRAE Standard 34: Table 1. Applicable Refrigerant Systems Refrigerant Number Chemical Name Chemical Formula R-12 dichlorodifluoromethane CC12F2R-22 monochlor
13、odifluoromethane CHC1F2R-134a 1,1,1,2-tetrafluoroethane CH2FCF3R-245fa 1,1,1,3,3-pentafluoropropane CHF2CH2CF3R-404A Refrigerants 125/143a/134a 44.0/52.0/4.0 wt. CHF2CF3/ CH3CF3/ CH2FCF3R-407C Refrigerants 32/125/134a 23.0/25.0/52.0 wt. CH2F2/ CHF2CF3/ CH2FCF3R-410A Refrigerants 32/125 50.0/50.0 wt.
14、 CH2F2/ CHF2CF3R-502 Refrigerants 22/115 48.8/51.2 wt. CHC1F2/ CC1F2CF3R-507A Refrigerants 125/143a 50.0/50.0 wt. CHF2CF3/ CH3CF32.3 Exclusions. This standard does not apply to liquid anti-freeze solution Desiccants or driers used in the suction line or low side of refrigeration and air-conditioning
15、 systems. 2.4 Limitations. This standard provides a means of determining Water Capacity and Refrigerant Flow Capacity of a Liquid-line Drier at specified conditions. This standard does not attempt to reflect the performance of a Liquid-line Drier over the entire range of possible applications, There
16、fore, acid and particulate removal are not considered here. 2.4.1 Acid Removal. It is known that acid in a refrigeration system causes harmful corrosion. Many Liquid-line Driers will remove acids. However, there is no knowledge at the present time as to what concentration of various acids is allowab
17、le, nor how to test a Liquid-line Driers ability to remove these acids. Therefore, while noting its importance, no consideration of acid removal is given in this standard at this time. 2.4.2 Particulate Removal. Although many commercial Liquid-line Driers have filtering media, the subject of filtrat
18、ion is separate and distinct from the considerations of this standard. Therefore, the rating of a Liquid-line Drier is on the premise of a clean Liquid-line Drier and clean refrigerant. Section 3. Definitions All terms in this document shall follow the standard industry definitions in the current ed
19、ition of ASHRAE Terminology of Heating, Ventilation, Air Conditioning and Refrigeration unless otherwise defined in this section. 3.1 “As Received” Condition. This specifies the Liquid-line Drier as removed from the manufacturers packaging, without further reactivation or preparation. (Note: If info
20、rmation is desired with respect to the reactivation of a Liquid-line Drier, the user should consult the manufacturer for recommended reactivation procedure.) 3.2 Desiccant. A material that will collect and hold water. 3.3 Equilibrium Point Dryness (EPD). The lowest possible water content of liquid r
21、efrigerant attainable by a specific Liquid-line Drier. This is achieved at a specific temperature after it has collected a specific quantity of water when the two have been in contact until an equilibrium between the water in the refrigerant and the water in the Liquid-line Drier has been reached. E
22、PD is expressed in parts per million (ppm) by weight. 3.4 Liquid-line Drier. A manufactured device for use in the liquid line of refrigeration and air-conditioning systems. The primary purpose is to collect and hold, at its location, water Copyright Air-Conditioning and Refrigeration Institute Provi
23、ded by IHS under license with ARINot for ResaleNo reproduction or networking permitted without license from IHS-,-,-ARI STANDARD 710-2004 2 which is in excess of the amount which can be tolerated in the system. 3.5 Pressure Drop. The pressure difference between the inlet and the outlet of a Liquid-l
24、ine Drier, including its connections. 3.6 Published Rating. A statement of the assigned values of those performance characteristics, under stated Rating Conditions, by which a Liquid-line Drier may be chosen to fit its application. These values apply to all Liquid-line Driers of like nominal size an
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ARI7102004STANDARDFORPERFORMANCERATINGOFLIQUIDLINEDRIERS 液体 干燥剂 作业 评定 标准 PDF

链接地址:http://www.mydoc123.com/p-429457.html