ARI 450-2007 Performance Rating of Water-Cooled Refrigerant Condensers Remote Type.pdf
《ARI 450-2007 Performance Rating of Water-Cooled Refrigerant Condensers Remote Type.pdf》由会员分享,可在线阅读,更多相关《ARI 450-2007 Performance Rating of Water-Cooled Refrigerant Condensers Remote Type.pdf(11页珍藏版)》请在麦多课文档分享上搜索。
1、 4100 N. FAIRFAX DR., SUITE 200 ARLINGTON, VIRGINIA 22203 2007 STANDARD for PERFORMANCE RATING OF WATER-COOLED REFRIGERANT CONDENSERS, REMOTE TYPE Standard 450 Copyright Air-Conditioning and Refrigeration Institute Provided by IHS under license with ARI Not for ResaleNo reproduction or networking pe
2、rmitted without license from IHS-,-,-Price $10.00 (Members) $20.00 (Non-Members) Copyright 2007, by Air-Conditioning and Refrigeration Institute Printed in U.S.A. Registered United States Patent and Trademark Office IMPORTANT SAFETY DISCLAIMER ARI does not set safety standards and does not certify o
3、r guarantee the safety of any products, components or systems designed, tested, rated, installed or operated in accordance with this standard/guideline. It is strongly recommended that products be designed, constructed, assembled, installed and operated in accordance with nationally recognized safet
4、y standards and code requirements appropriate for products covered by this standard/guideline. ARI uses its best efforts to develop standards/guidelines employing state-of-the-art and accepted industry practices. ARI does not certify or guarantee that any tests conducted under its standards/guidelin
5、es will be non-hazardous or free from risk. Note: This standard supersedes ARI Standard 450-99. Copyright Air-Conditioning and Refrigeration Institute Provided by IHS under license with ARI Not for ResaleNo reproduction or networking permitted without license from IHS-,-,-TABLE OF CONTENTS SECTION P
6、AGE Section 1. Purpose . 1 Section 2. Scope .1 Section 3. Definitions .1 Section 4. Test Requirements.2 Section 5. Rating Requirements .2 Section 6. Minimum Data Requirements for Published Ratings5 Section 7. Marking and Nameplate Data6 Section 8. Conformance Conditions.6 TABLES Table 1. Standard Ra
7、ting Conditions.3 APPENDICES Appendix A. References Normative 7 Appendix B. References Informative 7 Copyright Air-Conditioning and Refrigeration Institute Provided by IHS under license with ARI Not for ResaleNo reproduction or networking permitted without license from IHS-,-,-Copyright Air-Conditio
8、ning and Refrigeration Institute Provided by IHS under license with ARI Not for ResaleNo reproduction or networking permitted without license from IHS-,-,-ARI STANDARD 450-2007 1 PERFORMANCE RATING OF WATER-COOLED REFRIGERANT CONDENSERS, REMOTE TYPE Section 1. Purpose 1.1 Purpose. The purpose of thi
9、s standard is to establish for remote type, Water-Cooled Refrigerant Condensers: definitions; test requirements; rating requirements; minimum data requirements for Published Ratings; marking and nameplate data; and conformance conditions. 1.1.1 Intent. This standard is intended for the guidance of t
10、he industry, including manufacturers, engineers, installers, contractors and users. 1.1.2 Review and Amendment. This standard is subject to review and amendment as technology advances. Section 2. Scope 2.1 Scope. This standard applies to water-cooled refrigerant condensers. 2.2 Exclusions. This stan
11、dard does not apply to condensers supplied as components of factory-assembled refrigeration and air-conditioning units. Section 3. Definitions All terms in this document follow the standard industry definitions in the current edition of ASHRAE Terminology of Heating, Ventilation, Air Conditioning an
12、d Refrigeration, unless otherwise defined in this section. 3.1 Bubble Point. Refrigerant liquid saturation temperature at a specified pressure. 3.2 Clean Tube Capacity. The Total Heat Rejection Effect of the condenser with clean tubes at Standard Rating Conditions expressed in Btu/h W. 3.3 Dew Point
13、. Refrigerant vapor saturation temperature at a specified pressure. 3.4 Field Fouling Allowance. Provision for the anticipated Fouling Factor during use. 3.4.1 Fouling Factor. The thermal resistance due to fouling accumulated on the heat transfer surface. 3.5 Liquid Refrigerant Storage Capacity. The
14、 maximum liquid refrigerant storage capacity of a condenser shall be computed as being 80 percent of the available volume for the refrigerant and shall be expressed in ft3L or in lb kg of a specified refrigerant, assuming saturated liquid refrigerant density at 90.0F 32.2C. 3.6 Nominal Refrigerating
15、 System Capacity. The cooling effect determined by the product of the mass flow rate of refrigerant and the difference in enthalpy between the refrigerant entering the evaporator and the refrigerant leaving the evaporator. 3.7 Published Rating. A statement of the assigned values of those performance
16、 characteristics, under stated Rating Conditions, by which a unit may be chosen to fit its application. These values apply to all Water-Cooled Refrigerant Condensers of like nominal size and type produced by the same manufacturer. As used herein, the term Published Rating includes the rating of all
17、performance characteristics shown on the unit or published in specifications, advertising or other literature controlled by the manufacturer, at stated Rating Conditions. Copyright Air-Conditioning and Refrigeration Institute Provided by IHS under license with ARI Not for ResaleNo reproduction or ne
18、tworking permitted without license from IHS-,-,-ARI STANDARD 450-2007 2 3.7.1 Application Rating. A rating based on tests performed at application Rating Conditions (other than Standard Rating Conditions). 3.7.2 Standard Rating. A rating based on tests performed at Standard Rating Conditions. 3.8 Ra
19、ting Conditions. Any set of operating conditions under which a single level of performance results and which causes only that level of performance to occur. 3.8.1 Standard Rating Conditions. Rating Conditions used as the basis of comparison for performance characteristics. 3.9 Saturated Condensing T
20、emperature. For single component and azeotrope refrigerants, it is the saturated temperature corresponding to the refrigerant pressure at the condenser entrance. For zeotropic refrigerants, it is the arithmetic average of the dew point and bubble point temperatures corresponding to the refrigerant p
21、ressure at the condenser entrance. 3.10 “Shall“ or “Should.“ “Shall“ or “should“ shall be interpreted as follows: 3.10.1 Shall. Where “shall“ or “shall not“ is used for a provision specified, that provision is mandatory if compliance with the standard is claimed. 3.10.2 Should. “Should“ is used to i
22、ndicate provisions which are not mandatory but which are desirable as good practice. 3.11 Total Heat Rejection Effect. The total amount of heat removed from the refrigerant. This value is the product of the mass flow rate of refrigerant and the difference in enthalpy between the entering refrigerant
23、 vapor and the leaving refrigerant liquid, expressed in Btu/h W. (The total heat rejection, for all practical purposes, is the total heat transfer in the evaporator of the system plus the heat added to the refrigerant by the refrigeration compressor.) 3.12 Water-Cooled Refrigerant Condenser. A facto
24、ry-made assembly in which heat is transferred from the refrigerant vapor to the water such that the refrigerant vapor is condensed into a liquid. Section 4. Test Requirements 4.1 Test Requirements. All Standard Ratings shall be verified by tests conducted in accordance with ASHRAE Standard 22. Secti
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ARI4502007PERFORMANCERATINGOFWATERCOOLEDREFRIGERANTCONDENSERSREMOTETYPEPDF

链接地址:http://www.mydoc123.com/p-429443.html