AIR FORCE A-A-59878-2010 LOAD BANK ELECTRICAL 250 kilowatts 400 Hertz《250kW 400 HZ电气负荷组》.pdf
《AIR FORCE A-A-59878-2010 LOAD BANK ELECTRICAL 250 kilowatts 400 Hertz《250kW 400 HZ电气负荷组》.pdf》由会员分享,可在线阅读,更多相关《AIR FORCE A-A-59878-2010 LOAD BANK ELECTRICAL 250 kilowatts 400 Hertz《250kW 400 HZ电气负荷组》.pdf(7页珍藏版)》请在麦多课文档分享上搜索。
1、Beneficial comments, recommendations, additions, deletions, clarifications, etc. and any data that may improve this document should be sent to: WR-ALC/GRVEA, Robins AFB GA 31098-1813. Since contact information can change, you may want to verify the currency of this address information using the ASSI
2、ST Online database at https:/assist.daps.dla.mil/online . FSC 6625 INCH-POUNDA-A-59878 27 OCT 2010 COMMERCIAL ITEM DESCRIPTION LOAD BANK, ELECTRICAL 250 kilowatts, 400 Hertz The General Services Administration has authorized the use of this commercial item description for all federal agencies. 1. SC
3、OPE. This Commercial Item Description (CID) describes a 400 Hertz (Hz), 250 kilowatt (kW), portable type, resistive load bank and accessories. The commercially available, portable, enclosed, forced air cooled, industrial load bank is used for electrical performance testing of ground power supplies i
4、ncluding diesel engine and electrical motor driven generators designed to supply 400 Hz power for aircraft ground power applications. 2. SALIENT CHARACTERISTICS 2.1 Safety and environmental. The equipment shall meet all safety and environmental requirements as specified in National Fire Protection A
5、ssociation (NFPA) 70 National Electrical Code (NEC), ANSI/IEEE C2 National Electrical Safety Code and the latest applicable National Electrical Manufacturers Association (NEMA) standards except as stated herein. All resistive load element buses shall be over-current protected. Air flow failure shall
6、 cause the load bank to automatically drop all connected load before an over-temperature condition occurs. 2.2 Electrical power sources. The load bank shall be completely self-contained and require no power source to operate other than the generator under test. The operating power for internal circu
7、its, instruments, or (and) fan(s) shall be derived only from the power source under test. 2.3 Operating temperature. The equipment shall meet its performance and accuracy requirements in an operating environment of 0 degrees F to +120 degrees F. 2.4 Non-operating temperature. The equipment shall mee
8、t its performance and accuracy requirements after being in a non-operating environment (storage temperature) of 0 degrees F to +160 degrees F. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-A-A-59878 2 2.5 Calibration and maintenance adjustments. Th
9、e design of the system shall provide for readily accessible calibration adjustments and maintenance adjustments. The calibration adjustments, wherever possible, shall be accessible without removal of the instrument case or modules. These adjustments shall be provided by variable value components, wh
10、ich are adjustable, by the use of simple means. The calibration by substitution of selected components or parts is unacceptable unless specifically approved. The calibration interval shall be a period of one year or greater based on an operating time of 2,000 hours. 2.6 Accessories. Accessories to b
11、e supplied by the manufacturer with each deliverable load bank unit shall include standard and optional accessories as provided by the manufacturer and listed in the manufacturers catalog or data sheet. A written users manual, a written programmer reference manual (if applicable), and a traceable ca
12、libration certificate shall also be provided with each load bank unit. The user manual(s) shall include complete details for the operation, troubleshooting and maintenance of the load bank and shall include interconnect drawings and electrical schematics for all power and control circuits and device
13、s. A complete parts listing including original manufacturers name, part numbers, ratings and identifications shall be included with each load bank unit. 2.7 Environmental requirements. The load bank shall be designed for indoor or sheltered use and indoor storage. The load bank shall be clearly mark
14、ed “NOT FOR USE IN HAZARDOUS LOCATIONS”. 2.8 Performance characteristics. The load bank shall be capable of continuous, resistive load testing of aircraft ground power generator sets producing up to 250 kW at 115/200 volts alternating current (VAC) (nominal), 3 phase, 4 wire, 400 Hz power. The load
15、bank shall have a single, local control panel to contain all the meters, indicators, switches, and controls necessary to operate the unit. 2.8.1 Meters. The control panel of the load bank shall be equipped with meters for monitoring voltage (0-250 VAC), frequency (360-440 Hz), and current (0-300 AC
16、amps) and total power (0-300 kW). Meter accuracy shall be not less than 1.5%, full scale. 2.8.2 Phase selector switch. The load bank shall have a phase selector switch on the control panel for measuring the current of each phase of incoming power (A,B,C). Voltage measurements shall be selectable for
17、 both line-to-neutral and line-to-line for each phase on incoming power. 2.8.3 Phase rotation indicator. The load bank shall have a phase rotation indicator to indicate phase orientation and to indicate the presence of voltage on each phase (ABC, CBA). 2.8.4 E-F circuit. The load bank shall be equip
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- AIRFORCEAA598782010LOADBANKELECTRICAL250KILOWATTS400HERTZ250KW400HZ 电气 负荷 PDF

链接地址:http://www.mydoc123.com/p-427193.html