AHRI 365 I-P-2009 Performance Rating of Commercial and Industrial Unitary Air-Conditioning Condensing Units.pdf
《AHRI 365 I-P-2009 Performance Rating of Commercial and Industrial Unitary Air-Conditioning Condensing Units.pdf》由会员分享,可在线阅读,更多相关《AHRI 365 I-P-2009 Performance Rating of Commercial and Industrial Unitary Air-Conditioning Condensing Units.pdf(18页珍藏版)》请在麦多课文档分享上搜索。
1、 2009 Standard for Performance Rating of Commercial and Industrial Unitary Air-Conditioning Condensing Units AHRI Standard 365 (I-P) Price $15.00 (M) $30.00 (NM) Copyright 2009, by Air-Conditioning, Printed in U.S.A. Heating, and Refrigeration Institute Registered United States Patent and Trademark
2、Office IMPORTANT SAFETY DISCLAIMER AHRI does not set safety standards and does not certify or guarantee the safety of any products, components or systems designed, tested, rated, installed or operated in accordance with this standard/guideline. It is strongly recommended that products be designed, c
3、onstructed, assembled, installed and operated in accordance with nationally recognized safety standards and code requirements appropriate for products covered by this standard/guideline. AHRI uses its best efforts to develop standards/guidelines employing state-of-the-art and accepted industry pract
4、ices. AHRI does not certify or guarantee that any tests conducted under the standards/guidelines will not be non-hazardous or free from risk. AHRI CERTIFICATION PROGRAM PROVISIONS Scope of the Certification Program The Certification Program includes Commercial and Industrial Unitary Air-Conditioning
5、 Condensing Units rated at or above 135,000 Btu/h but below 250,000 Btu/h at the AHRI Standard Rating Conditions (Cooling). Certified Ratings The following Certification Program ratings are verified by test: 1. Single Number Rating Cooling Capacity, Btu/h 2. Single Number Rating Energy Efficiency Ra
6、tio, EER, Btu/(Wh) 3. Integrated Energy Efficiency Ratio, IEER (effective January 1, 2010) or Integrated Part-Load Value, (IPLV) (effective through December 31, 2009) Conformance to the requirements of the Maximum Operating Conditions Tests (Section 8) is also verified by test. Note: This standard s
7、upersedes ARI Standard 365-2002. For SI ratings, see AHRI Standard 366 (SI)-2009. TABLE OF CONTENTS PAGE Section 1. Purpose . 1 Section 2. Scope 1 Section 3. Definitions 1 Section 4. Classifications . 2 Section 5. Test Requirements 2 Section 6. Rating Requirements 3 Section 7. Minimum Data Requireme
8、nts for Published Ratings . 7 Section 8. Operating Requirements . 8 Section 9. Marking and Nameplate Data . 9 Section 10. Conformance Conditions 9 TABLES Table 1. Classifications of Commercial and Industrial Air-Conditioning Condensing Units . 2 Table 2. Standard Rating Conditions 3 Table 3. IEER Pa
9、rt-Load Rating Conditions 5 APPENDICES Appendix A. References - Normative 10 Appendix B. References Informative . 10 Appendix C. Method and Example of Calculating Integrated Part-Load Values (IPLV) Normative . 11AHRI STANDARD 365 (I-P)-2009 1 PERFORMANCE RATING OF COMMERCIAL AND INDUSTRIAL UNITARY A
10、IR-CONDITIONING CONDENSING UNITS Section 1. Purpose 1.1 Purpose. The purpose of this standard is to establish for Commercial and Industrial Unitary Air-Conditioning Condensing Units: definitions; classifications; test requirements; rating requirements; minimum data requirements for Published Ratings
11、; operating requirements; marking and nameplate data; and conformance conditions. 1.1.1 Intent. This standard is intended for the guidance of the industry, including manufacturers, engineers, installers, contractors and users. 1.1.2 Review and Amendment. This standard is subject to review and amendm
12、ent as technology advances. Section 2. Scope 2.1 Scope. This standard applies to factory-made Commercial and Industrial Unitary Air-Conditioning Condensing Units greater than or equal to 135,000 Btu/h as defined in Section 3. 2.1.1 Energy Source. This standard applies only to electrically-driven, me
13、chanical compression-type condensing units. 2.2 Exclusions. This standard does not apply to the testing and rating of condensing units for refrigeration purposes, as defined in AHRI Standard 520. Section 3. Definitions All terms in this document shall follow the standard industry definitions in the
14、current edition of ASHRAE Terminology of Heating, Ventilation, Air-Conditioning and Refrigeration unless otherwise defined in this section. 3.1 Bubble Point. Refrigerant liquid saturation temperature at a specified pressure. 3.2 Commercial and Industrial Unitary Air-Conditioning Condensing Unit. A f
15、actory-made assembly of refrigeration components designed to compress and liquefy a specific refrigerant. It consists of one or more refrigerant compressors, refrigerant condensers (air-cooled, evaporatively cooled, and/or water-cooled), condenser fans and motors (where used) and factory-supplied ac
16、cessories. 3.3 Cooling Capacity. The capacity in Btu/h obtained at specific conditions. It is equal to the increase in total enthalpy between the liquid refrigerant entering the expansion valve and superheated return gas multiplied by the mass flow rate of the refrigerant. 3.4 Dew Point. Refrigerant
17、 vapor saturation temperature at a specified pressure. 3.5 Energy Efficiency Ratio (EER). A ratio of the Cooling Capacity in Btu/h to the power input values in watts at any given set of Rating Conditions expressed in Btu/(Wh). 3.6 Integrated Energy Efficiency Rating (IEER). A single number part-load
18、 efficiency figure of merit calculated per the method described in this standard. 3.7 Integrated Part-Load Value (IPLV). A single number cooling part-load figure of merit calculated per the method described in Appendix C. AHRI STANDARD 365 (I-P)-2009 2 3.8 Published Rating. A statement of the assign
19、ed values of those performance characteristics, under stated Rating Conditions, by which a unit may be chosen to fit its application. These values apply to all units of like nominal size and type (identification) produced by the same manufacturer. As used herein, the term Published Rating includes t
20、he rating of all performance characteristics shown on the unit or published in specifications, advertising, or other literature controlled by the manufacturer, at stated Rating Conditions. 3.8.1 Application Rating. A rating based on tests performed at application Rating Conditions (other than Standa
21、rd Rating Conditions). 3.8.2 Standard Rating. A rating based on tests performed at Standard Rating Conditions. 3.9 Rating Conditions. Any set of operating conditions under which a single level of performance results and which causes only that level of performance to occur. 3.9.1 Standard Rating Cond
22、itions. Rating Conditions used as the basis of comparison for performance characteristics. 3.10 “Shall“ or “Should.“ “Shall“ or “should“ shall be interpreted as follows: 3.10.1 Shall. Where “shall“ or “shall not“ is used for a provision specified, that provision is mandatory if compliance with the s
23、tandard is claimed. 3.10.2 Should. “Should“ is used to indicate provisions which are not mandatory but which are desirable as good practice. 3.11 Single Number Rating. The Cooling Capacity and EER determined by the results of the tests at Rating Condition No. 1 for air-cooled and evaporatively-coole
24、d condensing units and at Rating Condition No. 3 for water-cooled condensing units (Section 6). Section 4. Classifications Equipment covered within the scope of this standard shall be classified as shown in Table 1: Table 1. Classifications of Commercial and Industrial Air-Conditioning Condensing Un
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- AHRI365IP2009PERFORMANCERATINGOFCOMMERCIALANDINDUSTRIALUNITARYAIRCONDITIONINGCONDENSINGUNITSPDF

链接地址:http://www.mydoc123.com/p-422525.html