ASTM E2750-17 Standard Guide for Extension of Data from Penetration Firestop System Tests Conducted in Accordance with ASTM E814.pdf
《ASTM E2750-17 Standard Guide for Extension of Data from Penetration Firestop System Tests Conducted in Accordance with ASTM E814.pdf》由会员分享,可在线阅读,更多相关《ASTM E2750-17 Standard Guide for Extension of Data from Penetration Firestop System Tests Conducted in Accordance with ASTM E814.pdf(7页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: E2750 17 An American National StandardStandard Guide forExtension of Data from Penetration Firestop System TestsConducted in Accordance with ASTM E8141This standard is issued under the fixed designation E2750; the number immediately following the designation indicates the year oforigina
2、l adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope1.1 This guide covers the extension of results obtained fromfire tests
3、 performed in accordance with Test Method E814 toapplications that have not been tested. Test Method E814evaluates the duration for which test specimens will contain afire, retain their integrity, or both during a predetermined firetest exposure. Firestops are intended for use in fire-resistivewalls
4、 and floors that are evaluated in conformance with TestMethod E119.NOTE 1Data obtained from firestops tested in accordance with TestMethods E119 with positive pressure can also be used.1.2 This guide is based on principles involving the exten-sion of test data using simple considerations. The accept
5、ance ofthese principles and their application is based substantially onan analogous worst-case proposition.1.3 These principles are only applicable to temperatureconditions represented by the standard time-temperature curvedescribed in Test Method E814, for systems falling within thescope of Test Me
6、thod E814. This test method is a fire-test-response standard.1.4 The types of building constructions which are part ofthis guide are as follows: floors, walls, partitions, floor/ceilingand roof/ceiling assemblies.1.5 This guide applies to:1.5.1 a single penetrating item, or1.5.2 multiple penetrating
7、 items.1.6 This guide does not apply to joints systems tested toE119, E1966 and E2307.1.7 Penetrating items can be one of the following: metallicpipe, non-metallic pipe, metallic tubing, non-metallic tubing,metallic conduit, non-metallic conduit, flexible metal conduit,cables, cable trays, bus ducts
8、, insulated pipes, insulated tubing,insulated conduit, insulated and non-insulated ducts, and struc-tural members.Metallic pipe, tubing or conduit 6.7Insulated pipe, tubing or conduit 6.8Non-metallic pipe, tubing or conduit 6.9 and 6.10Flexible metal conduit 6.11.1.4 and 6.11.1.5Cables 6.11Cable tra
9、y 6.12Bus duct 6.13Non-insulated duct 6.14Insulated duct 6.14.2Non-structural or service support member 6.15Mixed penetrations 6.161.8 Assemblies can be one of the following; concrete floorsor walls, masonry walls, gypsum walls, wood floor/ceilingassemblies, concrete floor/ceiling assemblies, chase
10、wall infloor/ceiling assemblies and fire-rated insulated walls.Concrete floors or walls 6.1Masonry walls 6.1Gypsum board wall assemblies 6.2Wood floor/ceiling assemblies 6.3Floor/ceiling assembly with concrete floor 6.4Chase wall intersecting a floor/ceiling assembly 6.5Fire-resistance insulated wal
11、ls 6.61.9 The extension of data using numerical calculationsbased on empirical data or theoretical models is not covered inthis guide.1.10 This guide does not cover the substitution of oneproprietary material for another proprietary material, or mate-rials for which fire-test data are not presently
12、available.1.11 This guide is used to predict or provide a quantitativemeasure of the fire hazard from a specified set of fire conditionsinvolving specific materials, products, or assemblies. Thisassessment does not necessarily predict the hazard of actualfires which involve conditions other than tho
13、se assumed in theanalysis.1.12 This guide is used to measure and describe the re-sponse of materials, products, or assemblies to heat and flameunder controlled conditions, but does not by itself incorporateall factors required for fire hazard or fire risk assessment of thematerials, products or asse
14、mblies under actual fire conditions.1.13 The values stated in SI units are to be regarded asstandard. No other units of measurement are included in thisstandard.1.14 This standard does not purport to address all of thesafety concerns, if any, associated with its use. It is the1This standard guide is
15、 under the jurisdiction of ASTM Committee E05 on FireStandards and is the direct responsibility of Subcommittee E05.11 on FireResistance.Current edition approved Nov. 1, 2017. Published December 2017. Originallyapproved in 2011. Last previous edition approved in 2013 as E2750-131. DOI:10.1520/E2750-
16、17.Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United StatesThis international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for theDevelopment of In
17、ternational Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.1responsibility of the user of this standard to establish appro-priate safety, health, and environmental practices and deter-mine the applicability of regulatory limit
18、ations prior to use.1.15 This international standard was developed in accor-dance with internationally recognized principles on standard-ization established in the Decision on Principles for theDevelopment of International Standards, Guides and Recom-mendations issued by the World Trade Organization
19、 TechnicalBarriers to Trade (TBT) Committee.2. Referenced Documents2.1 ASTM Standards:2C168 Terminology Relating to Thermal InsulationE119 Test Methods for Fire Tests of Building Constructionand MaterialsE176 Terminology of Fire StandardsE631 Terminology of Building ConstructionsE814 Test Method for
20、 Fire Tests of Penetration FirestopSystemsE1966 Test Method for Fire-Resistive Joint SystemsE2032 Guide for Extension of Data From Fire ResistanceTests Conducted in Accordance with ASTM E 119E2307 Test Method for Determining Fire Resistance ofPerimeter Fire Barriers Using Intermediate-Scale, Multi-s
21、tory Test Apparatus2.2 Other Standards:ACI 216 Fire Resistance of Concrete33. Terminology3.1 Definitions:3.1.1 For definitions used in this guide, refer to Terminolo-gies in E176, C168 and E631.3.1.2 For definitions of terms specific to this standard, referto E814 and E2032.4. Significance and Use4.
22、1 The methods and procedures set forth in this guide relateto the extension of the fire test results to firestop systems thathave not been tested.4.2 Users of this guide must have knowledge and under-standing of the provisions of Test Method E119 and TestMethod E814 including those pertaining to con
23、ditions ofacceptance.4.3 In order to apply some of the principles described in thisguide, reference to the original fire test report will be necessary.4.4 In Test Method E814, the specimens are subjected tospecific laboratory fire test exposure conditions. Differencesbetween the tested assembly and
24、the as-built assembly impactthe fire-test-response characteristics. Substitution of differenttest conditions also impacts the fire-test-response characteris-tics.4.5 The extension of data is valid only for the fire testexposure described in Test Method E814.4.6 This guide shall not be used to extrap
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTM E2750 17 Standard Guide for Extension of Data from Penetration Firestop System Tests Conducted in Accordance with E814

链接地址:http://www.mydoc123.com/p-287107.html