IEEE C62 92-1989 en Guide for the Application of Neutral Grounding in Electrical Utility Systems Part II-Grounding of Synchronous Generator Systems《电力事业系统中性接地应用.pdf
《IEEE C62 92-1989 en Guide for the Application of Neutral Grounding in Electrical Utility Systems Part II-Grounding of Synchronous Generator Systems《电力事业系统中性接地应用.pdf》由会员分享,可在线阅读,更多相关《IEEE C62 92-1989 en Guide for the Application of Neutral Grounding in Electrical Utility Systems Part II-Grounding of Synchronous Generator Systems《电力事业系统中性接地应用.pdf(25页珍藏版)》请在麦多课文档分享上搜索。
1、n IEEE Guide for the Application of Neutral Grounding in Electrical Utility Systems Part Il-Grounding of Synchronous Generator Systems Energy and Power Sponsored by the Surge Protective Devices Committee of the IEEE Power Engineering Society hbhhed by the InSMute of Electrical and Elecironics Engine
2、em, Inc., 345 East 47th Street. New Y Fig l(b) gives the results with one re- strike followed by a clearing at the next current zero. For the arc extinction voltage assumed, Fig 1 (b) indicates that the ratio of Xo/X1 should not exceed 3 if the transient voltages are to be limited to less than 250 p
3、ercent of normal line-to-neutral crest voltage. However, this voltage is still less than 75 percent of the manufacturers generator high-potential test voltage 7, 8. Each case should be studied using specific characteristics and appropriate modeling techniques. Figure 2 gives peak transient voltages
4、for high- resistance grounding. The voltage is plotted against the ratio of the 3-phase capacitive reactance to ground and the effective neutral resistance of the circuit, Xcg/R, (see ANSI/IEEE C62.92-1987, Figs 1 and 2 6). If this ratio is kept to 1 or greater, the peak voltage can be limited to ab
5、out 260 percent of normal peak line-to-neutral voltage, which is also less than 75 percent of the generator test voltage. This curve applies for any number of restrikes for ratios greater than 1 because each oscillation is damped out and a buildup in transient voltage is prevented. Figure 2 can also
6、 be used to indicate the magni- tude of possible transient voltages on ungrounded machines. The case to be compared is where the ratio of the 3-phase capacitive reactance to ground (X,) and thr neutral resistance (R,) of the circuit is less thai, the 0.1 lower limit of Fig 2. Thus, transient voltage
7、s of 4 to 5 times normal line-to-ground voltage crest may be reached if breaker restriking occurs on the ungrounded system. Temporary overvoltages on a generator can also be caused by a ground fault on the high- voltage side of the main power step-up trans- former. Such an occurrence impresses a neu
8、tral displacement voltage on the generator grounding equipment. The generator neutral grounding in conjunction with the transformer high to low side capacitive coupling forms a voltage divider circuit for the zero-sequence voltage impressed upon the transformer high-voltage winding 23. Consider- ati
9、on must be given to the generator grounding impedance and associated protective features to avoid temporary overvoltages that can damage the insulating systems or cause undesirable gen- erator ground relay operations. The lower the generator system zero-sequence impedance, the lower will be the impr
10、essed neutral displacement voltage. Therefore, this occurrence is a particular consideration for resonant grounded generator systems. The user of this guide should be aware that there is a degree of uncertainty as to the impulse strength of the generator insulation as compared to that of oil-insulat
11、ed apparatus of the same volt- age because of the different types of insulation systems and general construction. Because of this uncertainty, care should be taken in selecting both the class of grounding and the ratings of surge protective equipment. 2.4 Providing a Means of Generator System Ground
12、-Fault Protection. The grounding class chosen for a generator has a significant impact on the sensitivity and speed of ground-fault relaying for the generator and other apparatus connected to the generator voltage system. In general, ungrounded, high-resistance, and resonant- grounded systems allow
13、for the most sensitive ground-fault detection. In systems where genera- tors are bussed together at generator voltage or where feeders are taken out at the generator volt- age, relaying requirements may dictate a ground- ing class other than one which would provide maximum sensitivity for generator
14、stator ground faults. The effects which the choice of grounding class may have on ground relaying are discussed in a general way in Section 3. A complete discus- sion of generator ground-fault protection, includ- ing specific relaying systems, can be found in ANSI/IEEE C37.101-1985 4. 2.5 Coordinati
15、ng with the Other Apparatus at Generator Voltage Level. When a generator is interconnected with other systems, eg, other generators, plant auxiliaries, feeders, etc, at the generated voltage level, the class of generator grounding should not be determined by consider- ing the generators needs alone.
16、 Requirements for selective relaying, overvoltage control, inductive coordination, etc, in other parts of the system may constrain the choice of a generator ground- ing means. The specifics of these requirements for other systems may be found in the appropriate parts of this guide. The manner in whi
17、ch they may be 12 NEUTRAL GROUNDING IN ELECTRICAL UTILITY SYSTEMS IEEE C62.92 - 1989 reconciled with the generator requirements is discussed in 3.3. 3. Generator Grounding Qpes Various generator grounding classes and types have tended to become associated with particular generator system configurati
18、ons. It is a logical development since configurations that allow com- plete independence of choice of grounding means, ie, the unit generator transformer, are usually associated with grounding classes that maximize protection of the generator. When other equip- ment must be considered, the higher gr
19、ound current schemes are often used. In the following subsections, the various grounding classes are discussed in connection with the configuration with which they are normally employed. This subdivision is not intended to imply that other classes cannot be used, but that the ones dis- cussed are us
20、ed most frequently. 3.1 Unit-Connected Generation Systems. A unit-connected system is one in which a single generator is connected directly to a delta/wye step-up transformer with the delta windings at generator voltage. The unit configuration provides the maximum freedom of choice of a means for ge
21、nerator neu- tral grounding. The delta-connected winding of the unit transformer isolates the generator zero- sequence network from the rest of the system, allowing the neutral grounding of the generator to be chosen for maximum generator protection. The classes commonly used with the unit configu-
22、ration are discussed below. 3.1.1 High-Resistance Grounding. High- resistance grounding normally takes the form of a low-ohmic value resistor connected to the second- ary of a distribution transformer with the pri- mary winding of the transformer connected from the generator neutral to ground. The a
23、dvantage of the distribution transformer resistor combina- tion is that the resistor used in the secondary of Fig 3 Distribution Transformer Neutral Grounding VOLTAGE RELAY in other words, the ratio X,lR, is equal to or greater than 1 (see Fig 2). This prac- tice is described in equivalent terms suc
24、h as: (1) To make the resistive component of ground- fault current equal to or greater than the capacitive component (2 j To increase the power factor of the ground- fault current to at least 0.707 (3) To shift the phase angle of ground-fault current to less than 45” (4) To make the resistor power l
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- IEEEC62921989ENGUIDEFORTHEAPPLICATIONOFNEUTRALGROUNDINGINELECTRICALUTILITYSYSTEMSPARTIIGROUNDINGOFSYNCHRONOUSGENERATORSYSTEMS

链接地址:http://www.mydoc123.com/p-1249281.html