ASTM B812-2018 Standard Test Method for Resistance to Environmental Degradation of Electrical Pressure Connections Involving Aluminum and Intended for Residenti.pdf
《ASTM B812-2018 Standard Test Method for Resistance to Environmental Degradation of Electrical Pressure Connections Involving Aluminum and Intended for Residenti.pdf》由会员分享,可在线阅读,更多相关《ASTM B812-2018 Standard Test Method for Resistance to Environmental Degradation of Electrical Pressure Connections Involving Aluminum and Intended for Residenti.pdf(11页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: B812 18Standard Test Method forResistance to Environmental Degradation of ElectricalPressure Connections Involving Aluminum and Intended forResidential Applications1This standard is issued under the fixed designation B812; the number immediately following the designation indicates the y
2、ear oforiginal adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.INTRODUCTIONElectrical pressure connection systems involving alum
3、inum are those in which one or more of thecomponents of the system in the direct electrical path or carrying any electrical current is fabricatedof aluminum, including aluminum wires, aluminum bus bars, aluminum bolts, aluminum terminations,or any other aluminum current-carrying member. Included are
4、 systems which must carry current forsafety purposes such as ground shields or straps attached to aluminum framing or other structuralmembers. Pressure connection systems can be evaluated by this test method. Such systems arecomprised of the wire or other structure being connected and the means of c
5、onnection, any elementof which is made of aluminum.Connection systems tested are exposed sequentially to ambients of high relative humidity andtemperature cycles of 75C, such as may be encountered by some connections in actual residentialapplications. Periodic observation of the potential drop acros
6、s the connection interfaces while carryingrated current provides a measurement of connection performance.1. Scope1.1 This test method covers all residential pressure connec-tion systems. Detailed examples of application to specific typesof connection systems, set-screw neutral bus connectors andtwis
7、t-on wire-splicing connectors, are provided in AppendixX1 and Appendix X2.1.2 The purpose of this test method is to evaluate theperformance of residential electrical pressure connection sys-tems under conditions of cyclic temperature change (withinrating) and high humidity.1.3 The limitations of the
8、 test method are as follows:1.3.1 This test method shall not be considered to confirm aspecific lifetime in application environments.1.3.2 The applicability of this test method is limited topressure connection systems rated at or below 600 V d-c or a-cRMS.1.3.3 This test method is limited to tempera
9、ture and watervapor exposure in addition to electrical current as required tomeasure connection resistance.1.3.4 This test method does not evaluate degradation whichmay occur in residential applications due to exposure of theelectrical connection system to additional environmental con-stituents such
10、 as (but not limited to) the following examples:1.3.4.1 Household chemicals (liquid or gaseous) such asammonia, bleach, or other cleaning agents.1.3.4.2 Chemicals as may occur due to normal hobby orprofessional activities such as photography, painting, sculpture,or similar activities.1.3.4.3 Environ
11、ments encountered during construction orremodeling such as direct exposure to rain, uncured wetconcrete, welding or soldering fluxes and other agents.1.3.5 This test method is limited to evaluation of pressureconnection systems.1.4 This standard does not purport to address all of thesafety concerns,
12、 if any, associated with its use. It is theresponsibility of the user of this standard to become familiarwith all hazards including those identified in the appropriateSafety Data Sheet (SDS) for this product/material as providedby the manufacturer, to establish appropriate safety, health,and environ
13、mental practices, and determine the applicabilityof regulatory limitations prior to use.1.5 This standard should be used to measure and describethe properties of materials, products, or assemblies in responseto electrical current flow under controlled laboratory condi-tions and should not be used to
14、 describe or appraise the fire1This test method is under the jurisdiction of ASTM Committee B02 onNonferrous Metals and Alloys and is the direct responsibility of SubcommitteeB02.11 on Electrical Contact Test Methods.Current edition approved Nov. 1, 2018. Published December 2018. Originallyapproved
15、in 1990. Last previous edition approved in 2013 as B812 96 (2013).DOI: 10.1520/B0812-18.Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United StatesThis international standard was developed in accordance with internationally recognized principles
16、on standardization established in the Decision on Principles for theDevelopment of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.1hazard or fire risk of materials, products, or assemblies underactual installatio
17、n conditions or under actual fire conditions.However, results of this test may be used as elements of a firerisk assessment which takes into account all of the factorswhich are pertinent to an assessment of the fire hazard of aparticular end use.1.6 This international standard was developed in accor
18、-dance with internationally recognized principles on standard-ization established in the Decision on Principles for theDevelopment of International Standards, Guides and Recom-mendations issued by the World Trade Organization TechnicalBarriers to Trade (TBT) Committee.2. Referenced Documents2.1 ASTM
19、 Standards:2B542 Terminology Relating to Electrical Contacts and TheirUse2.2 Underwriter Laboratory Standards:UL486B Standard for Wire Connectors For Use With Alu-minum Conductors, ANSI/UL 486B3UL486C Standard for Splicing Wire Connectors32.3 NEC Document:ANSI/NFPA 70 National Electric Code43. Termi
20、nology3.1 residential applications, nresidential applications arethose involving a structure or vehicle used for permanent ortemporary human habitation. Included are homes (single ormultiple-unit houses and mobile or modular structures),motels, hotels, dormitories, hospitals, rest homes, and recre-a
21、tional vehicles. Excluded are railroad cars, boats, airplanes,nonresidential, commercial (office buildings, stores) and indus-trial applications (factories, warehouses).3.2 pressure connection system, nan electrical connectionintended to carry current between components or conductors incontact under
22、 mechanical pressure.3.2.1 DiscussionThe mechanical pressure may be appliedby clamping, tightening of threaded components, spring force,crimping, swaging, or other means. For the purpose of the testprocedure, the connection system consists of all componentsnormally present in the application, includ
23、ing both current-carrying and other metallic components, and non-metalliccomponents (insulators, insulation, protective boots or sleeve,etc.). Also see definition of “Connection, Pressure(Solderless),” in Article 100 of reference noted in Section 2.3(NEC).3.3 aluminum, nas the term “aluminum,” the m
24、aterial ofwhich conductors (wire, cable, busbars, etc.), connectioncomponents, and test board components may be made, includesaluminum metal and its alloys.3.4 reference conductor, na continuous length of the sameconductor material (wire, cable, busbar, etc.) incorporated inthe connection system bei
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMB8122018STANDARDTESTMETHODFORRESISTANCETOENVIRONMENTALDEGRADATIONOFELECTRICALPRESSURECONNECTIONSINVOLVINGALUMINUMANDINTENDEDFORRESIDENTIPDF

链接地址:http://www.mydoc123.com/p-1243430.html