1、10-11 28 31 00 - 1 SECTION 28 31 00 FIRE DETECTION AND ALARM SPEC WRITER NOTES: This specification addresses fire alarm systems installations of the following configurations/conditions: 1. A fully addressable fire alarm system. 2. A fully addressable fire alarm system as an extension of an existing
2、non-addressable fire alarm system. 3. A non-addressable fire alarm system as an extension of an existing non-addressable fire alarm system. As a result, this specification is organized as shown in the chart below. Spec Writer Notes: 1. PART 1 GENERAL This section addresses requirements for configura
3、tion/conditions (1), (2), and (3) as defined above. PART 2 (A) PRODUCTS This section addresses requirements for configuration/condition (1) as defined above. If this section is applicable, delete Part 2 (B) and 2 (C) PART 3 EXECUTION This section addresses requirements for configuration/conditions (
4、1), (2), and (3) as defined above. PART 2 (B) PRODUCTS This section addresses requirements for configuration/condition (2) as defined above. If this section is applicable, delete Part 2 (A) and 2 (C) PART 2 (C) PRODUCTS This section addresses requirements for configuration/condition (3) as defined a
5、bove. If this section is applicable, delete Part 2 (A) and 2 (B) Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-10-11 28 31 00 - 2 SPEC WRITER NOTES: 1. The A/E must obtain a copy of the most recent VA FIRE PROTECTION DESIGN MANUAL which provides fi
6、re alarm system criteria that is to be followed for VA projects. It may be obtained at: www.cfm.va.gov/til/dManual/dmFPfire.pdf 2. Fire alarm system design is required to be performed by competent engineers with experience in fire protection in accordance with the information located on the internet
7、 at: www.cfm.va.gov/contract/ae/fp_engr.doc 3. This specification provides the basis for a “campus“ type fire alarm system with buildings containing voice communication systems for defend in place occupancies (healthcare) as well as buildings that require total evacuation such as stand alone clinics
8、. 4. Modifications to this section will need to be made to meet specific project requirements and conditions. Delete text between sets of double slashes / - / if not applicable to the project or enter the information identified. Also delete any other item or reference which is not applicable and ren
9、umber the paragraphs. Insert additional provisions as required for this project. 5. No firemens phones are included in the specification. PART 1 - GENERAL 1.1 DESCRIPTION A. This section of the specifications includes the furnishing, installation, and connection of the fire alarm equipment to form a
10、 complete coordinated system ready for operation. It shall include, but not be limited to, alarm initiating devices, alarm notification appliances, control units, fire safety control devices, annunciators, power supplies, and wiring as shown on the drawings and specified. The fire alarm system shall
11、 not be combined with other systems such as building automation, energy management, security, etc. SPEC WRITER NOTE: The A/E should provide a design in compliance with the NFPA fire codes unless a variation is approved in writing by the VA. It is recommended that approval come those knowledgeable in
12、 Fire Alarm Design (e.g. Safety and Fire Protection Engineer, VACO Chief Fire Protection, etc.). Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-10-11 28 31 00 - 3 B. Fire alarm systems shall comply with requirements of the most recent VA FIRE PROTEC
13、TION DESIGN MANUAL and NFPA 72 unless variations to NFPA 72 are specifically identified within these contract documents by the following notation: “variation“. The design, system layout, document submittal preparation, and supervision of installation and testing shall be provided by a technician tha
14、t is certified NICET level III or a registered fire protection engineer. The NICET certified technician shall be on site for the supervision and testing of the system. Factory engineers from the equipment manufacturer, thoroughly familiar and knowledgeable with all equipment utilized, shall provide
15、additional technical support at the site as required by the /Resident Engineer/ /COTR/or his authorized representative. Installers shall have a minimum of 2 years experience installing fire alarm systems. SPEC WRITER NOTE: Identify in the following paragraphs which buildings are to be “defend in pla
16、ce“ type occupancies and which buildings are to be “totally evacuated“ when an alarm sounds. Unless buildings are to be totally evacuated upon alarm, the circuits required for occupant notification are required to meet the survivability requirements of NFPA 72. C. Fire alarm signals: 1. Building(s)
17、/ identify which buildings / shall have an automatic digitized voice fire alarm signal with emergency manual voice override to notify occupants to evacuate. The digitized voice message shall identify the area of the building (smoke zone) from which the alarm was initiated. 2. Building(s) / identify
18、which buildings / shall have a general evacuation fire alarm signal in accordance with ASA S3.41 to notify all occupants in the respective building to evacuate. D. Alarm signals (by device), supervisory signals (by device) and system trouble signals (by device not reporting) shall be distinctly tran
19、smitted to the main fire alarm system control unit located in the / security office / telephone operators office / boiler plant / fire department /. SPEC WRITER NOTE: A (DACT) digital alarm communicator transmitter should be connected to a pair of dedicated telephone lines to transmit an alarm Provi
20、ded by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-10-11 28 31 00 - 4 signal only to a central station that is responsible for dispatching the fire department. The connection to the fire department is usually via a central station monitoring company that is
21、contracted on a monthly basis by the facility. If a connection to the fire department is not already present, the facility will need to determine if there are 2 telephone lines available for this connection. E. The main fire alarm control unit shall automatically transmit alarm signals to a listed c
22、entral station using a digital alarm communicator transmitter in accordance with NFPA 72. 1.2 SCOPE SPEC WRITER NOTE: Scope of Work to include one of the following 3 options for new fire alarm systems. 1. A fully addressable fire alarm system. 2. A fully addressable fire alarm system as an extension
23、 of an existing non-addressable fire alarm system. 3. A non-addressable fire alarm system as an extension of an existing non-addressable fire alarm system. The following section addresses each scenario. Modify specification accordingly for this project. A. A /fully addressable fire alarm system/ /fu
24、lly addressable fire alarm system as an extension of an existing non-addressable fire alarm system/ /non-addressable fire alarm system as an extension of an existing non-addressable fire alarm system / shall be designed and installed in accordance with the specifications and drawings. Device locatio
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- VA2831002011FIREDETECTIONANDALARMPDF