1、10-11 28 16 00-1 SECTION 28 16 00 INTRUSION DETECTION SYSTEM SPECS WRITER NOTE: Delete / _ / if not applicable to project. Also delete any other item or paragraph not applicable in the section and renumber the paragraphs. Insert additional provisions as required for this project. PART 1 GENERAL 1.1
2、DESCRIPTION A. Provide and install a complete Intrusion Detection System, hereinafter referred to as IDS, as specified in this section. B. This Section includes the following: 1. Intrusion detection with hard-wired multiplexed, modular, microprocessor-based controls, intrusion sensors and detection
3、devices, and communication links to perform monitoring, alarm, and control functions. 2. Responsibility for integrating electronic and electrical systems and equipment is specified in the following Sections, with Work specified in this Section: a. Division 08 Section “DOOR HARDWARE“. b. Division 14
4、Section “ELECTRIC TRACTION ELEVATORS“. c. Division 27 Section “INTERCOMMUNICATIONS AND PROGRAM SYSTEMS“. d. Division 28 Section “PHYSICAL ACCESS CONTROL“. e. Division 28 Section “FIRE DETECTION AND ALARM“. f. Division 28 Section “VIDEO SURVEILLANCE“. g. Division 32 Section “CHAIN LINK FENCES AND GAT
5、ES“. C. Related Sections include the following: 1. Division 28 Section “VIDEO SURVEILLANCE“ for closed-circuit television cameras that are used as devices for video motion detection. 2. Division 28 Section “CONDUCTORS AND CABLES FOR ELECTRONIC SAFETY AND SECURITY“ for cabling between central-station
6、 control units and field-mounted devices and controllers. 1.2 RELATED WORK SPECS WRITER NOTE: Delete any item or paragraph not applicable in the section. A. Section 01 00 00 - GENERAL REQUIREMENTS. For General Requirements. B. Section 07 84 00 - FIRESTOPPING. Requirements for firestopping applicatio
7、n and use. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-10-11 28 16 00-2 C. Section 14 21 00 - ELECTRIC TRACTION ELEVATORS. Requirements for elevators. D. Section 14 24 00 - HYDRAULIC ELEVATORS. Requirements for elevators. E. Section 10 14 00 - SI
8、GNAGE. Requirements for labeling and signs. F. Section 26 05 11 - REQUIREMENTS FOR ELECTRICAL INSTALLATIONS. Requirements for connection of high voltage. G. Section 26 05 21 - LOW VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES (600 VOLTS AND BELOW). Requirements for power cables. H. Section 28 05 00
9、 COMMON WORK RESULTS FOR ELECTRONIC SAFETY AND SECURITY. Requirements for general requirements that are common to more than one section in Division 28. I. Section 28 05 13 - CONDUCTORS AND CABLES FOR ELECTRONIC SAFETY AND SECURITY. Requirements for conductors and cables. J. Section 28 05 26 - GROUND
10、ING AND BONDING FOR ELECTRONIC SAFETY AND SECURITY. Requirements for grounding of equipment. K. Section 28 05 28.33 - CONDUITS AND BACKBOXES FOR ELECTRONIC SAFETY AND SECURITY. Requirements for infrastructure. L. Section 28 08 00 - COMMISIONING OF ELECTRONIC SAFETY AND SECURITY. Requirements for com
11、missioning - systems readiness checklists, and training. M. Section 28 13 00 - PHYSICAL ACCESS CONTROL SYSTEMS (PACS). Requirements for physical access control integration. N. Section 28 13 16 - ACCESS CONTROL SYSTEM AND DATABASE MANAGEMENT. Requirements for control and operation of all security sys
12、tems. O. Section 28 23 00 - VIDEO SURVEILLANCE. Requirements for security camera systems. P. Section 28 26 00 - ELECTRONIC PERSONAL PROTECTION SYSTEM (EPPS). Requirements for emergency and interior communications. Q. Section 28 31 00 - FIRE DETECTION AND ALARM. Requirements for integration with fire
13、 detection and alarm system. 1.3 QUALITY ASSURANCE A. The Contractor shall be responsible for providing, installing, and the operation of the IDS as shown. The Contractor shall also provide certification as required. B. The security system shall be installed and tested to ensure all components are f
14、ully compatible as a system and can be integrated with all associated security subsystems, whether the security system is Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-10-11 28 16 00-3 stand-alone or a part of a complete Information Technology (IT)
15、 computer network. C. The Contractor or security sub-contractor shall be a licensed security Contractor as required within the state or jurisdiction of where the installation work is being conducted. 1.4 DEFINITIONS A. Controller: An intelligent peripheral control unit that uses a computer for contr
16、olling its operation. Where this term is presented with an initial capital letter, this definition applies. B. I/O: Input/Output. C. Intrusion Zone: A space or area for which an intrusion must be detected and uniquely identified, the sensor or group of sensors assigned to perform the detection, and
17、any interface equipment between sensors and communication link to central-station control unit. D. LED: Light-emitting diode. E. NEC: National Electric Code F. NEMA: National Electrical Manufacturers Association G. NFPA: National Fire Protection Association H. NRTL: Nationally Recognized Testing Lab
18、oratory. I. SMS: Security Management System A SMS is software that incorporates multiple security subsystems (e.g., physical access control, intrusion detection, closed circuit television, intercom) into a single platform and graphical user interface. J. PIR: Passive infrared. K. RF: Radio frequency
19、. L. Standard Intruder: A person who weighs 45 kg (100 lb.) or less and whose height is 1525 mm (60 in) or less; dressed in a long-sleeved shirt, slacks, and shoes. M. Standard-Intruder Movement: Any movement, such as walking, running, crawling, rolling, or jumping, of a “standard intruder“ in a pro
20、tected zone. N. TCP/IP: Transport control protocol/Internet protocol incorporated into Microsoft Windows. O. UPS: Uninterruptible Power Supply P. UTP: Unshielded Twisted Pair 1.5 SUBMITTALS SPEC WRITER NOTE: Delete and/or amend all paragraphs and sub-paragraphs and information as needed to ensure th
21、at only Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-10-11 28 16 00-4 the documentation required is requested per the Request for Proposal (RFP). /A. Refer to Section 28 05 00, Part1/ A. Submit below items in conjunction with Master Specification
22、Sections 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES, and Section 02 41 00, DEMOLITION. B. Provide certificates of compliance with Section 1.3, Quality Assurance. C. Provide a shop drawing and as-built design package in both electronic format and on paper, minimum size 1220 x 1220 millimeters
23、 (48 x 48 inches); drawing submittals shall be per the established project schedule. D. Shop drawing and as-built packages shall include, but not be limited to: 1. Index Sheet that shall: a. Define each page of the design package to include facility name, building name, floor, and sheet number. b. P
24、rovide a list of all security abbreviations and symbols. c. Reference all general notes that are utilized within the design package. d. Specification and scope of work pages for all security systems that are applicable to the design package that will: 1) Outline all general and job specific work req
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- VA2816002011INTRUSIONDETECTIONSYSTEMPDF