VA 07 54 23-2010 THERMOPLASTIC POLYOLEFIN (TPO) ROOFING.pdf
《VA 07 54 23-2010 THERMOPLASTIC POLYOLEFIN (TPO) ROOFING.pdf》由会员分享,可在线阅读,更多相关《VA 07 54 23-2010 THERMOPLASTIC POLYOLEFIN (TPO) ROOFING.pdf(22页珍藏版)》请在麦多课文档分享上搜索。
1、10-10 07 54 23 - 1 SECTION 07 54 23 THERMOPLASTIC POLYOLEFIN (TPO) ROOFING SPEC WRITER NOTES: 1. Delete or edit text within if not applicable to project. Also delete any other item or paragraph not applicable in the section and renumber the paragraphs. 2. Follow the recommendations of the National R
2、oofing Contractors Association “Roofing and Waterproofing Manual“ for design criteria. 3. Slopes: Do not use on slopes over 1:12 (one inch per foot). Provide 1:50 (1/4 inch per foot) minimum slope to drains without any “Gutters“ (no slopes between drains. NO EXCEPTIONS TO MINIMUM SLOPE. Slope cricke
3、ts 1:50 (1/4-inch per foot). 4. Coordinate with plumbing requirements for roof drains and drain locations at low points and mid span where maximum deflection occurs. Do not put drains at columns or on slopes. Coordinate with insulation to provide “dishes“ at drains. 5. Coordinate details and systems
4、 used to provide for code required fire rated roofing system. Do not use unsurfaced membranes over combustible insulation on decks. 6. Use of adhered system is preferred over mechanically anchored or ballasted system. 7. Coordinate with Section 07 22 00, ROOF AND DECK INSULATION. 8. Coordinate with
5、Section 07 22 00, ROOF AND DECK INSULATION for roof insulation under the membrane. Decrease “R“ value 5 percent when mechanical fasteners are used through the insulation to compensate for parallel heat flow. 9. Do not use over polystyrene, urethane, or wood fiberboard insulation under the membrane.
6、10. Do not use over bituminous materials where direct contact occurs, including grease, oil, or other substances not compatible with TPO. Use a thin layer of insulation, slip sheet or separator sheet depending upon method of attachment or felt back sheet when minimum amount of asphalt occurs. 11. Te
7、rminate base flashings not less than 200 mm (8 inches) above roof surface including curb for building expansion joints. 12. Do not put expansion joints at roof surface level. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-10-10 07 54 23 - 2 13. Do n
8、ot use “pitch pocket“ or “sealant pocket“ in lieu of base flashings and cap flashings. 14. This specification is for use over concrete, cellular insulating concrete decks, or insulation. Insert additional text when installed directly to other decks or insulation systems not specified in Section 07 2
9、2 00, ROOF AND DECK INSULATION. PART 1 GENERAL 1.1 DESCRIPTION A. Thermoplastic Polyolefin (TPO) sheet roofing /adhered/ /mechanically fastened/ to roof deck. 1.2 RELATED WORK SPEC WRITER NOTE: Edit Related Work to reflect other sections relating directly to this section or referenced in this sectio
10、n. A. General sustainable design documentation requirements: Section 01 81 13 SUSTAINABLE DESIGN REQUIREMENTS. B. Treated wood framing, blocking, and nailers: Section 06 10 00, ROUGH CARPENTRY C. Roof Insulation: Section 07 22 00, ROOF AND DECK INSULATION. D. Sheet metal components and wind uplift r
11、equirements for roof-edge design: Section 07 60 00, FLASHING AND SHEET METAL. E. Roof hatches, equipment supports, dome type skylights, and gravity ventilators: Section 07 72 00, ROOF ACCESSORIES F. Miscellaneous items: Section 07 71 00, ROOF SPECIALTIES/ Section 07 72 00, ROOF ACCESSORIES. 1.3 APPL
12、ICABLE PUBLICATIONS SPEC WRITER NOTES: 1. Update applicable publications to current issue at time of project specification preparation. 2. Update material requirements to agree with applicable requirements (types, grades, classes,) specified in the referenced Applicable Publications. A. Publications
13、 listed below form a part of this specification to the extent referenced. Publications are referenced in the text by the basic designation only. Editions of applicable publications current on date of issue of bidding documents apply unless otherwise indicated. Provided by IHSNot for ResaleNo reprodu
14、ction or networking permitted without license from IHS-,-,-10-10 07 54 23 - 3 B. American National Standards Institute/Single-Ply Roofing Institute (ANSI/SPRI): ANSI/SPRI ES-1-03.Wind Design Standard for Edge Systems Used with Low Slope Roofing Systems. C. American Society of Civil Engineers/Structu
15、ral Engineering Institute (ASCE/SEI): ASCE/SEI-7-10.Minimum Design Loads for Buildings and Other Structures D. ASTM International (ASTM): C67-09Standard Test Methods for Sampling and Testing Brick and Structural Clay Tile C140-09.Standard Test Methods for Sampling and Testing Concrete Masonry Units
16、and Related Units C1371-04Standard Test Method for Determination of Emittance of Materials Near Room Temperature Using Portable Emissometers C1549-04Standard Test Method for Determination of Solar Reflectance Near Ambient Temperature Using a Portable Solar Reflectometer D4263.Standard Test Method fo
17、r Indicating Moisture in Concrete by the Plastic Sheet Method D4434-06Standard Specification for Poly (Vinyl Chloride) Sheet Roofing D6878-08Standard Specification for Thermoplastic Polyolefin Based Sheet Roofing E108-10.Standard Test Methods for Fire Tests of Roof Coverings E408-71(R2008)Standard T
18、est Methods for Total Normal Emittance of Surfaces Using Inspection-Meter Techniques E1918-06Standard Test Method for Measuring Solar Reflectance of Horizontal and Low-Sloped Surfaces in the Field E1980-01Standard Test Method for Measuring Solar Reflectance of Horizontal and Low-Sloped Surfaces in t
19、he Field E. American Society of Heating, Refrigeration, and Air Conditioning Engineers (ASHRAE) ASHRAE 90.1-2007Energy Standard for Buildings Except Low-Rise Residential Buildings, Appendix f. F. Cool Roof Rating Council: Provided by IHSNot for ResaleNo reproduction or networking permitted without l
20、icense from IHS-,-,-10-10 07 54 23 - 4 CRRC-1Product Rating Program, www.coolroofs.org G. FM Approvals: RoofNav Approved Roofing Assemblies and Products. 4450-89.Approved Standard for Class 1 Insulated Steel Deck Roofs 4470-10.Approved Standard for Class 1 Roof Coverings 1-28-09.Loss Prevention Data
21、 Sheet: Design Wind Loads. 1-29-09.Loss Prevention Data Sheet: Above-Deck Roof Components 1-49-09.Loss Prevention Data Sheet: Perimeter Flashing H. National Roofing Contractors Association: Roofing and Waterproofing Manual I. U.S. Department of Agriculture (USDA): USDA BioPreferred Catalog, www.biop
22、referred.gov J. U.S. Department of Energy (DoE): Roof Products Qualified Product List, www.energystar.gov 1.4 PERFORMANCE REQUIREMENTS A. Material Compatibility: Provide roofing materials that are compatible with one another under conditions of service and application required, as demonstrated by me
23、mbrane roofing manufacturer based on testing and field experience. SPEC WRITER NOTE: Retain one or more paragraphs below for typical roofing applications based upon current Federal mandates, which may include one or more of the following: 1) Guiding Principles for Federal Leadership in High Performa
24、nce and Sustainable Buildings incorporated in Executive Order 13423 “Strengthening Federal Environmental, Energy, and Transportation Management, dated January 24, 2007; 2) Energy Policy Act of 2005 (EPA 2005); 3) Energy Independence and Security Act of 2007 (EISA 2007); 4) LEED mandate; 5) Conforman
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- VA0754232010THERMOPLASTICPOLYOLEFINTPOROOFINGPDF

链接地址:http://www.mydoc123.com/p-1074725.html