《UL SUBJECT 246B-2011 OUTLINE OF INVESTIGATION FOR Tamper Resistant Features of Hydrants for Fire-Protection Service (Issue 1)《用于消防服务的消防龙头防篡改功能的调查大纲 (议题1)》.pdf》由会员分享,可在线阅读,更多相关《UL SUBJECT 246B-2011 OUTLINE OF INVESTIGATION FOR Tamper Resistant Features of Hydrants for Fire-Protection Service (Issue 1)《用于消防服务的消防龙头防篡改功能的调查大纲 (议题1)》.pdf(10页珍藏版)》请在麦多课文档分享上搜索。
1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULMay 19, 20111SUBJECT 246BOUTLINE OF INVESTIGATIONFORTamper Resistant Features of Hydrants for Fire-Protection ServiceIssue No. 1May 19, 2011COPYRIGHT 2011 UNDERWRITERS LABORATORIES INC.UL COPYRIG
2、HTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULMAY 19, 2011SUBJECT 246B2No Text on This PageUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULCONTENTSINTRODUCTION1 Scope .42 Components 43 Units of
3、Measurement .44 Undated References 4CONSTRUCTION5 Design Features 5PERFORMANCE6 Attack Test .57 Normal Operation Test 68 Variable Ambient Test .69 Corrosion Exposure Tests 69.1 General .69.2 Salt spray (fog) .69.3 Moist hydrogen sulfide (H2S) air mixture 79.4 Moist carbon dioxide (CO2)-sulfur dioxid
4、e (SO2) air mixture 710 Ultraviolet Light and Water Exposure Test 711 Gaskets and Seals used in Tamper Resistant Features 812 Dust Test .813 Humidity Test .814 Endurance Test 815 External Icing Test .9MARKING16 General .9MAY 19, 2011 SUBJECT 246B 3UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER R
5、EPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULINTRODUCTION1 Scope1.1 This Outline covers requirements for evaluating the tamper resistant features of fire hydrants thathave been evaluated and comply with all applicable requirements of the Standard for Hydrants for FireProtection Service, UL 2
6、46.2 Components2.1 Except as indicated in 2.2, a component of a product covered by this Outline of Investigation shallcomply with the requirements for that component.2.2 A component is not required to comply with a specific requirement that:a) Involves a feature or characteristic not required in the
7、 application of the component in theproduct covered by this Outline of Investigation; orb) Is superseded by a requirement in this Outline of Investigation.2.3 A component shall be used in accordance with its rating established for the intended conditions ofuse.2.4 Specific components are incomplete
8、in construction features or restricted in performance capabilities.Such components are intended for use only under limited conditions, such as certain temperatures notexceeding specified limits, and shall be used only under those specific conditions.3 Units of Measurement3.1 Values stated without pa
9、rentheses are the requirement. Values in parentheses are explanatory orapproximate information.4 Undated References4.1 Any undated reference to a code or standard appearing in the requirements of this standard shall beinterpreted as referring to the latest edition of that code or standard.MAY 19, 20
10、11SUBJECT 246B4UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULCONSTRUCTION5 Design Features5.1 Tamper resistant features of a hydrant shall be designed such that they do not result in a significantdelay of the intended operation of the hydran
11、t or allow access by breaching the body. See clause 7,Normal Operation Test and clause 6, Attack Test.PERFORMANCE6 Attack Test6.1 A hydrant with tamper resistant features shall, for a period of 5 minutes:a) For Wet Barrel Hydrants, not permit removal of the caps and not permit operation of thehydran
12、t to begin; or permit making a hole opening in any surface of the hydrant using the toolsspecified in 6.4 and 6.5, orb) For Dry Barrel Hydrants, not permit removal of the caps and not permit operation of thehydrant to begin or; not permit making a hole opening in any surface of the hydrant using the
13、tools specified in 6.4 and 6.5 and not permit operation of the hydrant to begin.6.2 A hole size opening referenced in 6.1 is defined as an opening that is 1 inches (25.4 mm) in diameteror larger, or an opening through which a 1 inch (25.4 mm) diameter sphere would pass.6.3 Several separate attacks s
14、hall be permitted to be conducted against the hydrant. The attacks arepermitted to be directed against the caps, the body, the locking mechanism, and any part of the hydrantabove the indicated “bury” line.6.4 The hand tools permitted to be used in the attack tests include hammers, chisels, pry bars,
15、 punches,screwdrivers, and wrenches (adjustable, socket and fixed open and closed-end type). The hammers shallnot exceed 3 pounds (1.36 kg) in head weight, and no hand tool is to exceed 18 inches (457 mm) inlength.6.5 The power tool permitted to be used in the attack tests shall be a variable speed
16、electric drill withcarbide tip and high-speed drill bits not exceeding 1/4 inch (6.4 mm) diameter.6.6 The hydrant shall be positioned as intended for use, and the attack performed by one operator whois familiar with its construction. Only the components in the location above the indicated “bury line
17、” of thehydrant shall be subjected to the attack procedure.6.7 After being subjected to the conditions described in 6.2 6.6, a hydrant shall not be required tofunction.MAY 19, 2011 SUBJECT 246B 5UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM UL
18、7 Normal Operation Test7.1 The hydrant with tamper resistant features shall be able to be operated as intended using the hydrantwrench provided by the manufacturer from the fully closed position to the fully opened position and backto the fully closed position without delaying operation of the hydra
19、nt in excess of 30 seconds. Anyindividual hydrant cap shall be able to be removed without a delay in excess of 30 seconds.7.2 The hydrant shall be mounted in the intended manner, in accordance with the manufacturersinstallation instructions.8 Variable Ambient Test8.1 A hydrant shall comply with the
20、Normal Operation Test, clause 7, after the tamper resistant featuresare exposed to ambient temperatures of minus 35 and plus 66C (minus 31 and plus 151F).8.2 A sample device shall be conditioned at the temperatures specified in 8.1 for a minimum of 4 hoursand subjected to the Normal Operation Test.9
21、 Corrosion Exposure Tests9.1 General9.1.1 A hydrant shall comply with the Normal Operation Test after the tamper resistant features areexposed to the Salt Spray (fog) described in 9.2, the Moist hydrogen sulfide (H2 S) - air mixture in 9.3and the Moist carbon dioxide (CO2)-sulfur dioxide (SO2)-air m
22、ixture in 9.4 for 30 days.9.1.2 One sample hydrant or the tamper resistant assembly shall be individually exposed to each of thefollowing atmospheres. If tamper resistant assemblies are used, they shall be re-installed in a hydrantprior to the Normal Operation Test.9.2 Salt spray (fog)9.2.1 The appa
23、ratus for salt spray (fog) testing is to consist of a fog chamber having inside dimensionsof 48 by 30 by 36 inches (1.2 by 0.8 by 0.9 m), a salt-solution reservoir, a supply of conditionedcompressed air, a dispersion tower that produces a salt fog, constructed in accordance with the Standardfor Meth
24、od of Salt Spray (Fog) Testing, ASTM B117, sample supports, provision for heating the chamber,and necessary means of control.9.2.2 The dispersion tower is to be located in the center of the chamber and shall be supplied withhumidified air at a pressure of 17 to 19 psig (117 to 131 kPa) so that the s
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ULSUBJECT246B2011OUTLINEOFINVESTIGATIONFORTAMPERRESISTANTFEATURESOFHYDRANTSFORFIREPROTECTIONSERVICEISSUE1

链接地址:http://www.mydoc123.com/p-1069289.html