《UL SUBJECT 246A-2013 OUTLINE OF INVESTIGATION FOR NON-THREADED CONNECTIONS FOR FIRE HYDRANTS AND FIRE DEPARTMENT CONNECTIONS (Issue 1)《用于消防栓和消防部门连接的非螺纹连接件的调查大纲 (议题1)》.pdf》由会员分享,可在线阅读,更多相关《UL SUBJECT 246A-2013 OUTLINE OF INVESTIGATION FOR NON-THREADED CONNECTIONS FOR FIRE HYDRANTS AND FIRE DEPARTMENT CONNECTIONS (Issue 1)《用于消防栓和消防部门连接的非螺纹连接件的调查大纲 (议题1)》.pdf(10页珍藏版)》请在麦多课文档分享上搜索。
1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULApril 12, 20131UL 246AOUTLINE OF INVESTIGATIONFORNON-THREADED CONNECTIONS FOR FIRE HYDRANTS AND FIREDEPARTMENT CONNECTIONSIssue Number: 1April 12, 2013Summary of TopicsThis is the first issue of
2、the Outline of Investigation for Non-ThreadedConnections for Fire Hydrants and Fire Department Connections, Subject246ACOPYRIGHT 2013 UNDERWRITERS LABORATORIES INC.UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULAPRIL 12, 2013UL 246A2No Text o
3、n This PageUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULCONTENTSINTRODUCTION1 Scope .42 Units of Measurement .43 Undated References 4CONSTRUCTION4 General 4PERFORMANCE5 General 55.1 Details 55.2 Leakage and hydrostatic tests .55.3 Assembly
4、test 55.4 Tensile test 65.5 Corrosion resistance 65.6 Tests on gasket seal materials .75.7 Vacuum test .75.8 Force to connect and disconnect .85.9 10-day moist ammonia air stress cracking test .8MARKING6 General 9MANUFACTURING AND PRODUCTION TESTS7 General 9APRIL 12, 2013 UL 246A 3UL COPYRIGHTED MAT
5、ERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULINTRODUCTION1 Scope1.1 This Outline of Investigation covers requirements for the construction and performance ofnon-threaded connections when used as outlets on fire hydrants and inlets on fire department connecti
6、onsin the nominal 4 and 5 inch sizes.1.2 These non-threaded connections are intended for use:a) For hydrant pumper connections,b) To adapt from threaded hydrant pumper connections, andc) With couplings on fire department hoses that comply with the dimensions specified in theNational Fire Protection
7、Association Standard for Fire Hose Connections, NFPA 1963.2 Units of Measurement2.1 The metric unit shall be designated as the official unit for purposes of this outline. Where values ofmeasurement are specified in both SI and English units, either unit is used. In cases of dispute, the metricunit s
8、hall be used.3 Undated References3.1 Any undated reference to a code or standard appearing in the requirements of this standard shall beinterpreted as referring to the latest edition of that code or standard. Any undated reference to a code orstandard appearing in the requirements of this outline sh
9、all be interpreted as referring to the latest editionof that code or standard.CONSTRUCTION4 General4.1 A non-threaded fire hydrant or fire department connection shall be provided with a metal face andcomply with the dimensional requirements specified in the National Fire Protection Association Stand
10、ardfor Fire Hose Connections, NFPA 1963, for metal-face hydrant connections.4.2 These connections shall be able to withstand the test requirements in Performance, Section 5 and theleakage and hydrostatic test requirements in the applicable product standard Hydrants for Fire-ProtectionService, UL 246
11、 or Fire Department Connection Devices, UL 405.4.3 Caps for non-threaded fire department connections or non-threaded hydrant connections shall beprovided with suction or pressure gaskets complying with Standard for Fire Hose Connections, NFPA1963.APRIL 12, 2013UL 246A4UL COPYRIGHTED MATERIAL NOT AUT
12、HORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM UL4.4 Cap assemblies for hydrants and fire department connections shall be permitted to omit locks.4.5 The cap used for a non-threaded fire department connection or a non-threaded hydrant connectionshall be provided with a means
13、 of indicating water pressure behind the cap. A hole with a diameter notless than 3.18 mm (1/8 inch) or larger than 6.35 mm (1/4 inch) located in the cap that is exposed tointernal pressure shall be permitted to indicate water pressure behind the cap.PERFORMANCE5 General5.1 Details5.1.1 Representati
14、ve samples of fire hydrants or fire department connections equipped with non-threadedconnections shall be subjected to the tests described in these requirements.5.2 Leakage and hydrostatic tests5.2.1 The leakage and hydrostatic tests shall be conducted on either a fire hydrant or fire departmentconn
15、ection in accordance with the requirements specified in Hydrants for Fire-Protection Service, UL 246and Fire Department Connection Devices, UL 405, as applicable.5.2.2 For connections intended for hydrants, the leakage and hydrostatic tests shall be conducted usingthe cap intended for the hydrant. I
16、f the cap is vented, a test cap of the same configuration, but withoutvents shall be used for these tests.5.2.3 Caps intended for fire department connections shall not be required to withstand the test pressurerequired for the leakage and hydrostatic tests. Test caps or adapters of the same seal con
17、figuration shallbe permitted to be used for this test.5.3 Assembly test5.3.1 A non-threaded connection shall be capable of maintaining structural integrity and comply with theleakage test after being assembled and disassembled 3000 times as tested in 5.3.2 and 5.3.3.5.3.2 One sample of each non-thre
18、aded connection type and size cap assembly shall be used.5.3.3 The cap shall be assembled and disassembled onto the connection 3000 times without lubrication.After the 3000 cycles, the assembly shall be subjected to the leakage and hydrostatic tests in 5.2, exceptthe test pressure shall be the press
19、ure rating of the fire hydrant or fire department connection, asapplicable. The cap shall be permitted to be replaced with an untested cap without a vent hole, whensubjected to the Leakage and hydrostatic tests.APRIL 12, 2013 UL 246A 5UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION O
20、RDISTRIBUTION WITHOUT PERMISSION FROM UL5.4 Tensile test5.4.1 A non-threaded connection shall be capable of maintaining structural integrity and comply with theleakage test after being subjected to a tensile force equal to 1627 Nm (1200 lb-ft) times the nominaldiameter of the connection in inches.Ex
21、ception: When a non-threaded connection and cap assembly is subjected to the leakage andhydrostatic tests specified in 5.2, the tensile test shall not be required.5.4.2 Two samples of each non-threaded connection type and size cap assemblies shall be used.5.4.3 The sample shall be installed on a ten
22、sile machine and subjected to a force equal to 1627 Nm(1200 lb-ft) multiplied by the nominal diameter of the connection in inches applied at a travel rate notexceeding 2 inches per minute. After the test load is achieved, the load is to be released and the assemblyshall be subjected to the leakage a
23、nd hydrostatic tests in 5.2, except the pressure shall be the pressurerating of the fire hydrant or fire department connection, as applicable.5.5 Corrosion resistance5.5.1 A non-threaded connection manufactured from material other than material having strength andcorrosion resistance equivalent to h
24、igh-strength yellow brass No. 8A as defined in the StandardSpecification for Copper-Brass Alloys in Ingot Form, ASTM B 30, or the Standard Specification for CopperAlloy Sand Castings for General Applications, ASTM B 584, shall be capable of being assembled anddisassembled using common tools and show
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ULSUBJECT246A2013OUTLINEOFINVESTIGATIONFORNONTHREADEDCONNECTIONSFORFIREHYDRANTSANDFIREDEPARTMENTCONNECTIONSISSUE1

链接地址:http://www.mydoc123.com/p-1069288.html