UL 873 CRD-2010 UL Standard for Safety Temperature-Indicating and -Regulating Equipment - Section Paragraph Reference 29 38 69 Subject Requirements for controls incorporating equi.pdf
《UL 873 CRD-2010 UL Standard for Safety Temperature-Indicating and -Regulating Equipment - Section Paragraph Reference 29 38 69 Subject Requirements for controls incorporating equi.pdf》由会员分享,可在线阅读,更多相关《UL 873 CRD-2010 UL Standard for Safety Temperature-Indicating and -Regulating Equipment - Section Paragraph Reference 29 38 69 Subject Requirements for controls incorporating equi.pdf(2页珍藏版)》请在麦多课文档分享上搜索。
1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULUNDERWRITERS LABORATORIES INC. CERTIFICATION REQUIREMENT DECISIONThis Certification Requirement Decision is prepared and published by Underwriters Laboratories Inc.(UL). It is normative for the a
2、pplicable UL Product Certification Program(s); however, it is currently notpart of the UL Standard(s) referenced below.Product Category (CCN): XAPXStandard Number: UL 873Edition Date: November 16, 2007Edition Number: 12Section / Paragraph Reference: 29, 38, 69Subject: Requirements for controls incor
3、porating equipment ground-fault protectionintended for use in fixed outdoor electric deicing and snow-melting equipmentDECISION:29 Short-Circuit, Ground-Fault, Overload, and Thermal Protection29.3 Controls intended for use in fixed outdoor electric deicing and snow-melting equipment thatincorporate
4、equipment ground-fault protective devices (EGFPD) in its design, shall comply with therelevant requirements of this standard and also the referenced requirements of the Standard forGround-Fault Sensing and Relaying Equipment, UL 1053. See 38.10 of UL 873.29.4 The EGFPD circuit of an ice and snow-mel
5、ting equipment control shall comply with section 38.10.1.If the control is not provided with an alarm or test means to indicate an inoperative EGFPD condition, theEGFPD function of the control shall be evaluated as a protective function in accordance with the relevantrequirements of this standard, a
6、nd the Standard for Tests for Safety-Related Controls EmployingSolid-State Devices, UL 991. If software is relied upon as part of the electronic control, it shall beevaluated in accordance with the Standard for Software in Programmable Components, UL 1998 asSoftware Class 1.29.5 An ice and snow melt
7、ing equipment control may be provided with a common switching device tocontrol normal operation and provide EGFPD functionality. The control shall be marked in accordance with69.27.38.10 Ice and Snow-Melting Equipment Controls38.10.1 In addition to the applicable performance requirements of this sta
8、ndard, a EGFPD operation of anice and snow-melting equipment control shall be subjected to the following tests of UL 1053:a) Calibration Test sequence of Section 21. Devices with adjustable fault current setpoints, thecalibration sequence is conducted at the minimum and maximum values of the range.b
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- UL873CRD2010ULSTANDARDFORSAFETYTEMPERATUREINDICATINGANDREGULATINGEQUIPMENTSECTIONPARAGRAPHREFERENCE293869SUBJECTREQUIREMENTSFORCONTROLSINCORPORATINGEQUIPDF

链接地址:http://www.mydoc123.com/p-1069007.html