UL 1059 CRD-2015 UL Standard for Safety Terminal Blocks - Section Paragraph Reference Sections 50 and 51 (Performance) Subject Protective Conductor Terminal Blocks (PCTB) Rated fo.pdf
《UL 1059 CRD-2015 UL Standard for Safety Terminal Blocks - Section Paragraph Reference Sections 50 and 51 (Performance) Subject Protective Conductor Terminal Blocks (PCTB) Rated fo.pdf》由会员分享,可在线阅读,更多相关《UL 1059 CRD-2015 UL Standard for Safety Terminal Blocks - Section Paragraph Reference Sections 50 and 51 (Performance) Subject Protective Conductor Terminal Blocks (PCTB) Rated fo.pdf(6页珍藏版)》请在麦多课文档分享上搜索。
1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULUNDERWRITERS LABORATORIES INC. CERTIFICATION REQUIREMENT DECISIONThis Certification Requirement Decision is prepared and published by Underwriters Laboratories Inc.(UL). It is normative for the a
2、pplicable UL Product Certification Program(s); however, it is currently notpart of the UL Standard(s) referenced below.Product Category (CCN): XCFR2Standard Number: UL 1059Standard Title: Standard for Terminal BlocksEdition Date: December 27, 2001Edition Number: 4Section / Paragraph Reference: Secti
3、ons 50 and 51 (Performance)Subject: Protective Conductor Terminal Blocks (PCTB) Rated for Use WithAluminum ConductorsDECISION:PART V - PROTECTIVE CONDUCTOR TERMINAL BLOCKS (PCTB)PERFORMANCE50 Short Time Current Sequence (Commercial and Industrial Applications)50.1 General50.1.1 A protective conducto
4、r terminal block (PCTB) or pole of a PCTB intended for use in commercialand industrial applications, as specified in items B and C of Table 8.1, shall be subjected to the testsdescribed in 50.2 - 50.4.50.1.2 The tests are to be conducted on a protective conductor terminal block installed on its supp
5、ortaccording to the manufacturers instructions. The tests are to be repeated for each alternate supportconstruction, support material, or both.50.1.3 A copper conductor of the largest size for which the terminal block is rated, not less than 2 feet(0.609 m) long, is to be installed. A terminal block
6、 rated for use with copper shall be tested with a copperconductor, a terminal block rated for use with aluminum shall be tested with an aluminum conductor, anda terminal block rated for use with both copper and aluminum conductors shall be tested with copper. Theconductor connection and the connecti
7、on to the support are to be made using the torque specified in 10.5.50.2 Voltage drop test50.2.1 The voltage drop is to be measured on each terminal block as shown in Figure 50.1, with a d-ccurrent of 0.1 times the maximum rated current of the terminal block passing through the measurementpoints.a)
8、The voltage drop shall not exceed 3.2 mV, when measured across the clamping units; andb) The voltage drop shall not exceed 6.4 mV, when measured from the clamping units to thesupport.This is generated text for figtxt.UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITH
9、OUT PERMISSION FROM UL50.3 Current test50.3.1 Following the measurement of voltage drop, three separate applications of the test currentspecified in Table 50.1 are to be applied, one after another, through the current paths 1-1 and 2-2, asappropriate, as shown in Figure 50.2. The test current is to
10、be applied for 1 second during eachapplication with an interval of 6 minutes or less between applications of the current. There shall be nodamage to the terminal block or its support.Table 50.1Short-time test currentsCopper cConductor size, AWG/kcmil (mm2) Test current, amperesCopper Aluminum14 AWG
11、(2.1) 252 17012 (3.3) 396 27010 (5.3) 636 4308 (8.4) 1008 6806 (13.3) 1596 8804 (21.2) 2544 14003 (26.7) 3204 17702 (33.6) 4032 22301 (42.4) 5088 28001/0 (53.5) 6420 29002/0 (67.4) 8088 36003/0 (85.0) 10,200 4600Figure 50.1Voltage drop measurement pointsSTANDARD NUMBER: UL 1059 -2-UL COPYRIGHTED MAT
12、ERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULTable 50.1 ContinuedCopper cConductor size, AWG/kcmil (mm2) Test current, amperesCopper Aluminum4/0 (107) 12,840 5800250 kcmil (127) 15,240 6900300 (152) 18,240 8200350 (177) 21,240 9600400 (203) 24,360 11000500 (
13、253) 30,360 13700600 (304) 36,480 16500700 (355) 42,600 19250750 (380) 45,600 20600800 (405) 48,600 2200900 (456) 54,720 247001000 (507) 60,840 27500This is generated text for figtxt.50.4 Voltage drop test repeated50.4.1 Following the test described in 50.3.1 and after cooling to room temperature an
14、d without anychange to the arrangement, the voltage drop test described in 50.2.1 is to be repeated.a) The voltage drop shall not exceed 3.2 mV, when measured across the clamping units;Figure 50.2Current path for short time current testSTANDARD NUMBER: UL 1059 -3-UL COPYRIGHTED MATERIAL NOT AUTHORIZ
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- UL1059CRD2015ULSTANDARDFORSAFETYTERMINALBLOCKSSECTIONPARAGRAPHREFERENCESECTIONS50AND51PERFORMANCESUBJECTPROTECTIVECONDUCTORTERMINALBLOCKSPCTBRATEDFOPDF

链接地址:http://www.mydoc123.com/p-1067296.html