《UFC 4-024-01-2008 SECURITY ENGINEERING PROCEDURES FOR DESIGNING AIRBORNE CHEMICAL BIOLOGICAL AND RADIOLOGICAL PROTECTION FOR BUILDINGS《安全工程 建筑物空气传播化学品 生物制品及放射防护的设计程序》.pdf》由会员分享,可在线阅读,更多相关《UFC 4-024-01-2008 SECURITY ENGINEERING PROCEDURES FOR DESIGNING AIRBORNE CHEMICAL BIOLOGICAL AND RADIOLOGICAL PROTECTION FOR BUILDINGS《安全工程 建筑物空气传播化学品 生物制品及放射防护的设计程序》.pdf(123页珍藏版)》请在麦多课文档分享上搜索。
1、UFC 4-024-01 10 June 2008 UNIFIED FACILITIES CRITERIA (UFC) SECURITY ENGINEERING: PROCEDURES FOR DESIGNING AIRBORNE CHEMICAL, BIOLOGICAL, AND RADIOLOGICAL PROTECTION FOR BUILDINGS APPROVED FOR PUBLIC RELEASE; DISTRIBUTION UNLIMITED Provided by IHSNot for ResaleNo reproduction or networking permitted
2、 without license from IHS-,-,-UFC 4-024-01 10 June 2008 UNIFIED FACILITIES CRITERIA (UFC) SECURITY ENGINEERING: PROCEDURES FOR DESIGNING AIRBORNE CHEMICAL, BIOLOGICAL, AND RADIOLOGICAL PROTECTION FOR BUILDINGS Any copyrighted material included in this UFC is identified at its point of use. Use of th
3、e copyrighted material apart from this UFC must have the permission of the copyright holder. U.S. ARMY CORPS OF ENGINEERS (Preparing Activity) NAVAL FACILITIES ENGINEERING COMMAND AIR FORCE CIVIL ENGINEER SUPPORT AGENCY Record of Changes (changes are indicated by 1 . /1/) Change No. Date Location Pr
4、ovided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-UFC 4-024-01 10 June 2008 FOREWORD The Unified Facilities Criteria (UFC) system is prescribed by MIL-STD 3007 and provides planning, design, construction, sustainment, restoration, and modernization crite
5、ria, and applies to the Military Departments, the Defense Agencies, and the DoD Field Activities in accordance with USD (AT 3-5.4, Medium Level of Protection; and 3-5.5, High Level of Protection. Classes of overpressure are addressed in Paragraph 3-6.2, Overpressure Classification. 3-4.3 Protection
6、from Internal Release The most effective method to protect building personnel against an internal release is to prevent containers of hazardous materials from being brought into the building in the routine flow of people, mail, supplies, and other deliveries. An integrated building protection approa
7、ch is required to provide maximum protection. This approach includes access control, filtration of HVAC return air, and isolation of high-risk areas such as mailrooms, lobby areas, security screening areas, and supply delivery areas with separate ventilation systems as well as unscreened public acce
8、ss areas and any other general-access areas. The simplest way to respond to an internal release is to shut down the HVAC system to limit dispersion of CBR agents. Central air-handling filtration systems that are designed to remove specific CBR agents from recirculated air can help limit distribution
9、 Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-UFC 4-024-01 10 June 2008 3-7of the CBR agent within the building through the HVAC system. However, such filtration systems do not protect the immediate area where the internal release occurred or poss
10、ibly even the adjacent area, and contaminated air in return air ducts or plenums may be spread to other parts of the facility. 3-4.3.1 Access Control All secured doors should have an electronic entry or manual lock system that only authorized personnel can activate. All maintenance personnel and the
11、ir equipment and authorized deliveries should be checked for hazardous materials. Screening personnel should be provided with specific operational procedures to detect the presence of hazardous material containers. 3-4.3.2 Security Screening Entry screening is a two-step process: (1) detecting a clo
12、sed container and (2) determining whether the contents of the container are hazardous or likely to be hazardous. Both steps should be established in coordination with the appropriate security personnel and in accordance with guidance in UFC 4-020-02 for the applicable level of protection. The first
13、step could involve the use of x-ray equipment; the use of a metal detector; or a manual search of briefcases, handbags, packages, letters, boxes of supplies, and deliveries of food and bottled beverages. The following are items to consider for further examination or exclusion: Aerosol cans or other
14、pressurized containers Manual or electric spray devices Containers of liquids or powders Bottled gases typically used for repair or maintenance within the building Pressurized dispensers containing irritating agents, including pepper spray, mace, and tear-producing agents The second step involves ex
15、amining the container, its contents, and labels and then determining whether the contents agree with the label. Liquid or powder in an unlabeled container is reason for prohibiting it from entering the building. This step also involves checking for alterations to the label. 3-4.3.3 Ventilation Syste
16、m Isolation To limit the spread of agents after an internal release, areas having a higher risk of a release should have a separate HVAC system, exhaust fan, sealed full-height boundary walls, and low-leakage doors and dampers. These areas also should be kept at a slight negative pressure relative t
17、o the other areas of the building. 3-4.3.4 Windows Fixed and forced-entry-resistant exterior window designs can prevent a container with a CBR agent from being thrown through a window. Refer to UFC 4-010-01 for minimum window requirements and to UFC 4-020-02 for any additional requirements. Provided
18、 by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-UFC 4-024-01 10 June 2008 3-83-5 LEVELS OF PROTECTION The facility design requirements for each level of protection against varying CBR threats are discussed in Paragraphs 3-5.1 through 3-5.5, below. Levels of
19、protection are part of the design criteria established by a planning team during the project planning process. They are commonly based on asset value as established using a process in UFC 4-020-01 and should not be changed without consulting with the facility user or the planning team. The discussio
20、n of levels of protection in this UFC includes the following topics: Design requirements for the very low level of protection (Paragraph 3-5.1) Recommended measures to protect facilities regardless of the level of protection (Paragraph 3-5.2) Design considerations for the low level through the high
21、level of protection (Paragraphs 3-5.3 through 3-5.5) For a table summarizing the levels of protection, overpressure, and filtration system for each level, refer to Paragraph 3-7, Building Protection Summary. 3-5.1 Very Low Level of Protection The very low level of protection incorporates passive bui
22、lding component features at little or no additional cost when included in new facility designs and major retrofits. Protection measures that are recommended for all buildings and are required for new inhabited facility designs and major retrofits are a mass notification, public address, or alarm sys
23、tem; air distribution emergency shutoff; sealed mailrooms with separate, dedicated ventilation systems and exhaust fans; elevated outside air intakes; and restricted roof access. For additional information, refer to Paragraphs 3-5.1.1 through 3-5.1.3, below; Appendix D, Sheltering in Place; and UFC
24、4-010-01. 3-5.1.1 Mass Notification, Public Address, or Alarm System A mass notification, public address, or alarm system is critical to CBR protection. It is necessary to alert building occupants of a CBR release and to provide direction for evacuation. It indicates when to initiate evacuation proc
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- UFC4024012008SECURITYENGINEERINGPROCEDURESFORDESIGNINGAIRBORNECHEMICALBIOLOGICALANDRADIOLOGICALPROTECTIONFORBUILDINGS

链接地址:http://www.mydoc123.com/p-1066959.html