1、 Tentative Interim Amendment NFPA 51A Standard for Acetylene Cylinder Charging Plants 2012 Edition Reference: 3.3 (New), 10.6, 11.2.1.3, and B.1.2.1 TIA 12-1 (SC 12-3-5/TIA Log #1036) Pursuant to Section 5 of the NFPA Regulations Governing Committee Projects, the National Fire Protection Association
2、 has issued the following Tentative Interim Amendment to NFPA 51A, Standard for Acetylene Cylinder Charging Plants, 2012 edition. The TIA was processed by the Technical Committee on Industrial and Medical Gases, and was issued by the Standards Council on March 6, 2012, with an effective date of Marc
3、h 26, 2012. A Tentative Interim Amendment is tentative because it has not been processed through the entire standards-making procedures. It is interim because it is effective only between editions of the standard. A TIA automatically becomes a proposal of the proponent for the next edition of the st
4、andard; as such, it then is subject to all of the procedures of the standards-making process. 1. Add the following definitions to Section 3.3 of Chapter 3: 3.3.xx Fast Acting Detection System. A Detection system designed to detect a fire more rapidly than standard smoke or heat detectors. A.3.xx Fas
5、t Acting Detection System. Examples for outdoor installations are optical (UV/IR) systems that detect visible flames and do not rely on products of combustion to be transported by the energy of the heat plume to the location of the detector. For indoor installations examples include high sensitivity
6、 smoke detection (HSSD), optical (UV/IR) or other early detection systems. 3.3.xx Fill Valve. A shutoff valve on the charging system for charging MATS where the acetylene supply first enters the charging connection. 3.3.xx MATS Building. A single-story detached building, without an attic, basement,
7、crawl space or false ceiling, used for acetylene trailer(s) or mobile acetylene trailer system (MATS) operations located indoors and the balance of the building is used exclusively for acetylene operations including storage and use of hazardous materials. 3.3.xx MATS Fire Area. The area or footprint
8、 occupied by the individual mobile acetylene trailer(s) to include the control system up to the point of the source valve for MATS being discharged or to the point of the fill valve for MATS being charged. 3.3.xx Source Valve. A shutoff valve on the piping system serving MATS where the acetylene sup
9、ply first enters the users supply line. 2. Modify Section 10.6 as follows: 10.6* Mobile Acetylene Trailer Systems (MATS). In addition to the general requirements of NFPA 51A, MATS charging and discharge stations located at acetylene charging plants shall be in accordance with 10.6. 10.6.1 General. M
10、ATS fire areas used for charging or discharging operations shall be separated from each other by not less than 30 ft. or by fire barriers or fire walls: 10.6.1.1 When fire barriers are used to separate outdoor MATS fire areas without weather protection, the fire barriers shall be not less than 2-hou
11、r fire resistive construction and shall separate individual fire areas by line of sight. 10.6.1.2 When fire barriers are used to separate outdoor MATS fire areas covered by weather protection constructed in accordance with the requirements of NFPA 55, Compressed Gases and Cryogenic Fluids Code, the
12、fire barriers shall be full height walls without openings extending from the foundation to the roof constructed of not less than 2-hour fire resistive construction. The allowable area occupied by weather protection shall be in accordance with the requirements of the building code. 10.6.1.3 When MATS
13、 are installed indoors in a MATS building, fire walls, fire barriers or 2-hour fire rated exterior walls are permitted to be used to separate MATS fire areas. Walls shall be constructed in accordance with the requirements of the building code. 10.6. 2 MATS Charging Stations 10.6.2.1 Location. The mo
14、bile acetylene trailer, including fill connections, shall be located in accordance with the following criteria: (1) Not less than 25 ft (7.6 m) from property lines. (2) Not less than 50 feet (15.2 m) from buildings of combustible construction. (3) Not less than 15 ft (4.6 m) from buildings of noncom
15、bustible construction not associated with the charging or discharging of the mobile acetylene trailer. (4) Not less than 15 ft (7.6 m) horizontal distance from the vertical plane below the nearest overhead electrical utility power lines. (5) Not less than 15 ft (4.6 m) horizontal distance from the v
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- NFPA51AAMD12012STANDARDFORACETYLENECYLINDERCHARGINGPLANTSEFFECTIVEDATE3262012 乙炔 充气 设备 标准 生效 日期 20120326

链接地址:http://www.mydoc123.com/p-1008683.html