1、 Tentative Interim Amendment NFPA 13 Standard for the Installation of Sprinkler Systems 2016 Edition Reference: 17.2.3.5.6, A.17.2.3.5 and A.17.3.3.5 TIA 16-1 (SC 15-8-14 / TIA Log #1165) Note: Text of the TIA was issued and approved for incorporation into the document prior to printing. 1. Revise s
2、ection 17.2.3.5.6 to read as follows: 17.2.3.5.6 The minimum operating pressure shall be either 30 psi (2.0 bar) or 60 psi (4.1 bar) based upon the applicable storage and ceiling height for the installation as follows: a) 30 psi (2.0 bar) for storage heights up to 25 ft (7.6 m) with a maximum ceilin
3、g height of 30 ft (9.1 m) b) 60 psi (4.1 bar) for storage heights up to 25 ft. (7.6 m) with a maximum ceiling height of 40 ft (12.2 m). 2. Revise section A.17.2.3.5 to read as follows: A.17.2.3.5 The Fire Protection Research Foundation conducted a series of full-scale fire tests at Underwriters Labo
4、ratories to develop protection criteria for the rack storage of exposed expanded Group A plastic commodities. The tests are documented in the report, “Protection of Rack Stored Exposed Expanded Group A Plastics with ESFR Sprinklers and Vertical Barriers.” The criteria for exposed expanded plastics a
5、re based on Tests 2, 3, 7 and 8 of the series, which investigated a 40 ft (12.2 m) ceiling with a range of storage heights. The tests used K-25.2 intermediate-temperature ESFR sprinklers with vertical barriers attached to the rack uprights at nominal 16 ft (4.9 m) apart. Vertical barriers of sheet m
6、etal and 38 -in. plywood were both investigated. In Tests 1 through 6, transverse flue spaces between commodities were blocked. Comparing the results of Test 6 with blocked transverse flue spaces and Test 7 with no blocking of transverse flue spaces, the number of operated sprinklers decreased from
7、11 to 7 and improved suppression of the fire. The criteria for exposed expanded plastics are based on Tests 9 and 10 of the series, which investigated a 30 ft (9.1 m) ceiling with a range of storage heights. The tests used K-25.2 intermediate-temperature ESFR sprinklers with vertical barriers attach
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- NFPA13AMD12015STANDARDFORTHEINSTALLATIONOFSPRINKLERSYSTEMSEFFECTIVEDATE972015PDF

链接地址:http://www.mydoc123.com/p-1008266.html