DLA DSCC-DWG-87059 REV E-2008 CIRCUIT BREAKERS MAGNETIC LOW-POWER SEALED TRIP-FREE SHOCK ENHANCED THREE-POLE AUXILIARY CONTACTS.pdf
《DLA DSCC-DWG-87059 REV E-2008 CIRCUIT BREAKERS MAGNETIC LOW-POWER SEALED TRIP-FREE SHOCK ENHANCED THREE-POLE AUXILIARY CONTACTS.pdf》由会员分享,可在线阅读,更多相关《DLA DSCC-DWG-87059 REV E-2008 CIRCUIT BREAKERS MAGNETIC LOW-POWER SEALED TRIP-FREE SHOCK ENHANCED THREE-POLE AUXILIARY CONTACTS.pdf(10页珍藏版)》请在麦多课文档分享上搜索。
1、 REVISIONS LTR DESCRIPTION DATE APPROVED A Added lever operating force requirement and eliminated 135 percent calibration tripping time. 28 Jan 88 Randy Larson B Updated document references, edit 6.3. 22 Aug 00 Kendall Cottongim C Deleted part number and substitute PIN, editorial changes, update to
2、latest DSCC drawing format. 11 DEC 02 Kendall Cottongim D Corrected 4.2.1 shock test condition, corrected vendor similar designation or type numbers, update to latest DoD requirements. 4 Jun 04 Kendall Cottongim E Update the approved source of supply to reflect Sensata Technologies, Incorporated and
3、 update to the latest DSCC drawing format. 25 Nov 08 Michael Radecki THE ORIGINAL FIRST PAGE OF THIS DRAWING HAS BEEN REPLACED. Prepared in accordance with ASME Y14.100 Source control drawing REV PAGE REV PAGE REV E E E E E E E E E E REV STATUS OF PAGES PAGES 1 2 3 4 5 6 7 8 9 10 PMIC N/A PREPARED B
4、Y Dan McGrath DESIGN ACTIVITY DEFENSE ELECTRONICS SUPPLY CENTER DAYTON, OH 45444-5000 CHECKED BY Dan McGrath APPROVED BY D. E. Morgan TITLE CIRCUIT BREAKERS, MAGNETIC, LOW-POWER, SEALED, TRIP-FREE, SHOCK ENHANCED, THREE-POLE, AUXILIARY CONTACTS SIZE A CODE IDENT. NO. 14933 DWG NO. 87059 Original dat
5、e of drawing 31 Aug 1987 REV E PAGE 1 OF 10 AMSC N/A 5925-E081 CURRENT DESIGN ACTIVITY CAGE CODE 037Z3 DEFENSE LOGISTICS AGENCY DEFENSE SUPPPLY CENTER COLUMBUS COLUMBUS, OHIO 43218-3990 Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-DEFENSE ELECTRON
6、ICS SUPPLY CENTER DAYTON, OHIO SIZE A CODE IDENT NO. 14933 DWG NO. 87059 REV E PAGE 2 1. SCOPE 1.1 Scope. This drawing describes the requirements for a family of circuit breakers with shock enhancement for use in overcurrent protection. 1.2 Part or Identifying Number (PIN). The complete PIN is as fo
7、llows: 87059 -001 | | | |_ Drawing Dash number number (see table I) 2. APPLICABLE DOCUMENTS 2.1 General. The documents listed in this section are specified in sections 3 and 4 of this specification. This section does not include documents cited in other sections of this specification or recommended
8、for additional information or as examples. While every effort has been made to ensure the completeness of this list, document users are cautioned that they must meet all specified requirements of documents in sections 3 and 4 of this specification, whether or not they are listed. 2.2 Government docu
9、ments. 2.2.1 Specifications, standards, and handbooks. The following specifications, standards, and handbooks form a part of this document to the extent specified herein. Unless otherwise specified, the issues of these documents are those listed in the solicitation or contract. DEPARTMENT OF DEFENSE
10、 SPECIFICATIONS MIL-PRF-39019 - Circuit Breakers, Magnetic, Low-Power, Sealed, Trip-Free, General Specification for. (Copies of this document are available online at http:/assist.daps.dla.mil/quicksearch/ or from the Standardization Document Order Desk, 700 Robbins Avenue, Building 4D, Philadelphia,
11、 PA 19111-5094.) 2.3 Non-Government publications. The following document forms a part of this document to the extent specified herein. Unless otherwise specified, the issues of the documents are those cited in the solicitation or contract (see 6.2). SOCIETY OF AUTOMOTIVE ENGINEERS, INCORPORATED (SAE
12、 International) SAE-AMS-QQ-N-290 - Nickel Plating (Electrodeposited). (Copies of this document are available online at http:/www.sae.org/ or from SAE, 400 Commonwealth Drive, Warrendale, PA 15096-0001.) 2.4 Order of precedence. Unless otherwise noted herein or in the contract, in the event of a conf
13、lict between the text of this document and the references cited herein (except for related specification sheets), the text of this document takes precedence. Nothing in this document, however, supersedes applicable laws and regulations unless a specific exemption has been obtained. 3. REQUIREMENTS 3
14、.1 Interface and physical dimensions. The interface and physical dimensions shall be as specified herein (see table I, ll, lll, and figure 1). 3.2 Voltage and frequency rating. 50 V dc, maximum and 240 V ac, maximum at 60 and 400 Hz. 3.3 Current rating. See table I. Provided by IHSNot for ResaleNo r
15、eproduction or networking permitted without license from IHS-,-,-DEFENSE ELECTRONICS SUPPLY CENTER DAYTON, OHIO SIZE A CODE IDENT NO. 14933 DWG NO. 87059 REV E PAGE 3 3.5 Time delay. Time delay shall be in accordance with table I, table II, and table III. 3.6 Shock. 3.6.1 Shock (100 gs). When circui
16、t breakers are tested as specified in 4.2.1, main circuit breaker contacts shall not trip. There shall be no closing of open main contacts, nor opening of closed main contacts in excess of 10 s duration, nor shall there be any evidence of mechanical or electrical damage. 3.6.2 Shock (150 gs). When c
17、ircuit breakers are tested as specified in 4.2.2, the main circuit breaker contacts shall not trip. There shall be no evidence of mechanical or electrical damage. 3.6.3 Shock (200 gs). When circuit breakers are tested as specified in 4.2.3, the main circuit breaker contacts shall not trip. There sha
18、ll be no evidence of mechanical or electrical damage. 3.7 Endurance. Endurance shall be in accordance with MIL-PRF-39019, except that the number of operations shall be 5,000. 3.8 Resistance or impedance. See table I. 3.9 Interrupting capacity. Interrupting capacity shall be in accordance with MIL-PR
19、F-39019. 3.10 Dielectric withstanding voltage. Dielectric withstanding voltage shall be in accordance with MIL-PRF-39019. 3.11 Vibration. Vibration shall be in accordance with MIL-PRF-39019. 3.12 Insulation resistance. Insulation resistance shall be in accordance with MIL-PRF-39019. 3.13 Lever opera
20、ting force. Lever operating force shall be in accordance with MIL-PRF-39019 except for the following: One-pole breaker: 7 pounds maximum; two-pole breaker: 10 pounds maximum; and three-pole breaker: 16 pounds maximum. 3.14 Auxiliary contacts. Auxiliary contacts shall be 0.5 amperes maximum at 120 V
21、ac or 50 V dc. 3.15 Marking. Marking shall be as specified in MIL-PRF-39019, except the DSCC drawing PIN in accordance with 1.2 herein shall be used instead of the military part number. 3.16 Recycled, recovered, or environmentally preferable materials. Recycled, recovered, or environmentally prefera
22、ble materials should be used to the maximum extent possible provided that the material meets or exceeds the operational and maintenance requirements, and promotes economically advantageous life cycle costs. 3.17 Manufacturer eligibility. To be eligible for listing as an approved source of supply, a
23、manufacturer shall be listed on the MIL-PRF-39019 Qualified Product List for at least one part, or perform the Group A inspection specified herein on a sample of parts agreed upon by the manufacturer and DSCC-VA. 3.18 Certificate of compliance. A certificate of compliance shall be required from a ma
24、nufacturer requesting to be an approved source of supply. 3.19 Workmanship. Parts shall be free of flash pits, voids, and excessive mold marks. Visible parting line is acceptable. 4. VERIFICATION 4.1 Conformance inspection. 4.1.1 Inspection of product for delivery. Inspection of product for delivery
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- DLADSCCDWG87059REVE2008CIRCUITBREAKERSMAGNETICLOWPOWERSEALEDTRIPFREESHOCKENHANCEDTHREEPOLEAUXILIARYCONTACTSPDF

链接地址:http://www.mydoc123.com/p-688857.html