DLA A-A-59223-1998 COOLING TOWERS LIQUID《液体冷却器》.pdf
《DLA A-A-59223-1998 COOLING TOWERS LIQUID《液体冷却器》.pdf》由会员分享,可在线阅读,更多相关《DLA A-A-59223-1998 COOLING TOWERS LIQUID《液体冷却器》.pdf(8页珍藏版)》请在麦多课文档分享上搜索。
1、INCH-POUNDA-A-59223May 18, 1998SUPERSEDINGF-C-2791November 29, 1991COMMERCIAL ITEM DESCRIPTIONCOOLING TOWERS, LIQUIDThe General Services Administration has authorized the use of thiscommercial item description for all Federal agencies.1. SCOPE. This commercial item description (CID) covers factory a
2、ssembled, inducedmechanical draft and forced mechanical draft cooling towers for commercial and industrial use.2. CLASSIFICATION. The cooling towers shall be of the following types, as specified(see 7.2).TYPEType I - Induced mechanical draft.Type II - Forced mechanical draft.3. SALIENT CHARACTERISTI
3、CS.3.1 Description . The cooling towers shall be of the induced mechanical draft or forcedmechanical draft type as specified (see 2. and 7.2). The cooling towers shall be comprised of thefollowing components and parts: frames and casings, louvers, drift eliminators, partitions, coldwater basin equip
4、ment, fans, blowers, drives, electric motors, access doors, ladders, workingplatforms (if specified), inspection plates, and panels.3.2 Standard commercial product . The cooling tower shall, as a minimum, be in accordance withthe requirements of this CID and shall be the manufacturers standard comme
5、rcial product.Additional or better features which are not specifically prohibited by this CID, but which are aBeneficial comments, recommendations, additions, deletions, clarifications, etc. and any datawhich may improve this document should be sent to: Commanding Officer (Code 15E2), NavalConstruct
6、ion Battalion Center, 1000 23 rd Avenue, Port Hueneme, CA 93043-4301, by usingthe Standardization Document Improvement Proposal (DD Form 1426) appearing at the end ofthis document or by letter.AMSC N/A FSC 4130Provided by IHSNot for ResaleNo reproduction or networking permitted without license from
7、IHS-,-,-A-A-592232part of the manufacturers standard commercial product, shall be included in the cooling towerbeing furnished. A standard commercial product is a product which has been sold or is beingcurrently offered for sale on the commercial market through advertisements or manufacturerscatalog
8、s or brochures, and represents the latest production model.3.3 Interchangeability . All units of the same classification furnished with similar options under aspecific contract shall be identical to the extent necessary to ensure interchangeability ofcomponent parts, assemblies, accessories, and spa
9、re parts.3.4 Safety . Heavy-duty metal guards or enclosures shall be provided over all fans and aroundother rotating or reciprocating parts in accordance with Occupational Safety and HealthAdministration (OSHA) regulations. Inlets and openings other than louvered openings shall beprovided with readi
10、ly removable screens. Discharge fans shall be protected by a ruggedly framedscreen or guard installed outside the fan and removable for service conforming to OSHAregulations. Ladders, safety cages, handrailings, working platforms, and fittings shall be providedwhere required, in accordance with OSHA
11、 regulations. All towers shall be designed andconstructed to provide ready access for maintenance, servicing and repair.3.5 Construction . The design of the cooling tower shall meet the requirements of this CID. Alltowers shall be constructed to withstand a wind pressure of not less than 30 pounds f
12、orce persquare foot ( psf) (1.44 kilopascal (kPa) on any external surface. Fan decks shall be constructedto withstand a live load of not less than 60 psf (2.87 kPa) in addition to the concentrated ordistributed loads of equipment mounted thereon. When specified (see 7.2), a 15 percent increasedloadi
13、ng shall be included for ice or snow load. The hot water distribution system shall be of theopen basin gravity feed type or the pressurized spray header type design.3.5.1 Towers and tower frames. The tower frame material shall be as specified (see 7.2).3.5.2 Cold water basins and casings. Casings sh
14、all have suitable seals and flashings at joints andconnections to ensure watertight construction and to minimize and control leakage.3.5.3 Inlet and discharge terminations. When specified (see 7.2), on forced draft centrifugal typeunits the air inlet and discharge terminations shall have flanged or
15、lipped projections forconnecting to duct work.3.5.4 Frames and louvers. Intermediate structural members shall be provided, wheneverrequired, for rigidity and support of casings, louvers, fill, distribution systems, fan decks, andother equipment. Inlet air louvers shall permit free air passage and be
16、 designed to prevent debrisand sunlight from entering the cold water basin while eliminating splashout.3.5.5 Fill or contact surfaces. The fill shall support expected loads without sag or failure andarranged to effectively break up the water. The fill shall be manufactured and performance testedby t
17、he cooling tower manufacturer. The fill shall be of the materials as specified (see 7.2).Polyvinyl chloride fill is suitable for inlet temperatures to 125 degrees Fahrenheit ( F)Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-A-A-592233(51.7 degrees
18、Celsius ( C) on cross flow type units and temperatures to 130 F (54.4 C) oncounterflow type units. Chlorinated polyvinyl chloride fill shall be used for applications whereinlet temperatures are greater than 130 F (54.4 C).3.5.6 Drift eliminators. Drift eliminator sections shall be designed in accord
19、ance with commercialpractice and arranged to effectively trap water droplets entrained in the discharge airstream.Sections shall be assembled in easily removable sections for type II and counterflow type I towers.3.5.7 Partitions, windbreak baffles, drift-check walls, and fan walls. Partitions, wind
20、break baffles,drift-check walls, and fan walls, when provided, shall be installed to suit design and capacity oftower, as ordered.3.5.8 Cold water basin equipment. The following equipment shall be furnished by the equipmentsupplier for all towers: sump with removable screen and vortex breaker, float
21、 valves, and allnecessary pipe connections and fittings within the tower. Float valves when provided shall be ofadequate sizes on adjustable arms. Sizes larger than 0.50-inch (12.70 mm) shall be the balancedpiston type. Valve seats and composition disks shall be replaceable.3.5.9 Fans, blowers, and
22、drives. The towers shall have propeller-type fans having not less thanfour blades or squirrel-cage, centrifugal-type blowers, as applicable. Centrifugal type blower fansshall be dynamically balanced. Wood fan blades are not acceptable. Fans and blowers shall becapable of withstanding 50 percent over
23、speed above normal maximum operating speeds. Fan andblower tip speeds shall be held within ranges which will permit conformance to sound levelrequirements specified herein (see 3.6.1). Drive components and supports shall be heavy-dutythroughout. Forced draft towers shafts shall be the hollow type wi
24、th outboard ball bearings or thesolid type with outboard ball bearings and oil lubricated intermediate sleeve bearings. Induceddraft towers shafts shall be solid type with outboard ball bearings. Bearings shall have L10 life ofnot less than 75,000 hours for type I towers and 40,000 hours for type II
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- DLAAA592231998COOLINGTOWERSLIQUID 液体 冷却器 PDF