BS 7623-1993 Electrical and pneumatic analogue chart recorders for use in industrial-process control systems - Guidance for inspection and routine testing《工业处理控制系统用电气和气动模拟图表记录器 检验和.pdf
《BS 7623-1993 Electrical and pneumatic analogue chart recorders for use in industrial-process control systems - Guidance for inspection and routine testing《工业处理控制系统用电气和气动模拟图表记录器 检验和.pdf》由会员分享,可在线阅读,更多相关《BS 7623-1993 Electrical and pneumatic analogue chart recorders for use in industrial-process control systems - Guidance for inspection and routine testing《工业处理控制系统用电气和气动模拟图表记录器 检验和.pdf(8页珍藏版)》请在麦多课文档分享上搜索。
1、BRITISH STANDARD BS 7623:1993 IEC 1153:1992 Electrical and pneumatic analogue chart recorders for use in industrial-process control systems Guidance for inspection and routine testingBS7623:1993 This British Standard, having been prepared under the directionof the Industrial-process Measurement and
2、Control Standards Policy Committee, was published underthe authority of the Standards Board and comes intoeffect on 15 January 1993 BSI 10-1999 The following BSI references relate to the work on this standard: Committee reference PCL/1 Draft for comment 90/26001 DC ISBN 0 580 21553 9 Committees resp
3、onsible for this British Standard The preparation of this British Standard was entrusted by the Industrial-process Measurement and Control Standards Policy Committee (PCL/-) to Technical Committee PCL/1, upon which the following bodies were represented: British Coal Corporation British Gas plc Briti
4、sh Telecommunications plc Department of Energy (Gas and Oil Measurement Branch) Electricity Association Energy Industries Council Engineering Equipment and Materials Users Association GAMBICA (BEAMA Ltd.) Health and Safety Executive Institution of Gas Engineers The following bodies were also represe
5、nted in the drafting of the standard, through subcommittees and panels: Department of Trade and Industry (National Engineering Laboratory) Engineering Industries Association Institute of Metals Institution of Electrical Engineers Amendments issued since publication Amd. No. Date CommentsBS7623:1993
6、BSI 10-1999 i Contents Page Committees responsible Inside front cover National foreword ii 1 Scope and object 1 2 Normative references 1 3 Sampling for test 1 4 Definitions 1 5 Performance test 1 List of references Inside back coverBS7623:1993 ii BSI 10-1999 National foreword BS 7623 has been prepar
7、ed under the direction of the Industrial-process Measurement and Control Standards Policy Committee. It is identical with IECPublication 1153:1992 Electrical and pneumatic analogue chart recorders for use in industrial-process control systems Guidance for inspection and routine testing, published by
8、 the International Electrotechnical Commission (IEC). The Technical Committee has reviewed the provisions of IEC 382:1991 and IEC410:1973, to which normative reference is made in the text, and has decided that they are acceptable for use in conjunction with this standard. A related British Standard
9、to IEC 873:1986 is BS 4671:1987. A British Standard does not purport to include all the necessary provisions of a contract. Users of British Standards are responsible for their correct application. Compliance with a British Standard does not of itself confer immunity from legal obligations. Cross-re
10、ferences International Standard Corresponding British Standard IEC 381-1:1982 BS 5863 Analogue signals for process control systems Part 1:1984 Specification for direct current signals (Identical) IEC 381-2:1978 Part 2:1980 Specification for direct voltage signals (Identical) Summary of pages This do
11、cument comprises a front cover, an inside front cover, pages i and ii, pages1 and 2, an inside back cover and a back cover. This standard has been updated (see copyright date) and may have had amendments incorporated. This will be indicated in the amendment table on the inside front cover.BS7623:199
12、3 BSI 10-1999 1 1 Scope and object This International Standard applies to electrical and pneumatic analogue chart recorders (for use in industrial process control systems) using analogue signals which are in accordance with IEC 381 andIEC 382. Some tests may not apply to all instruments and addition
13、al tests may be required for certain types of recorders. This standard is intended to provide technical guidance for inspection and routine testing of electrical and pneumatic analogue chart recorders, for instance, as acceptance tests or after repair. For a full evaluation, IEC 873 should be used.
14、Quantitative criteria for acceptable performance shall be established by agreement between manufacturer and user. The requirements of this standard shall be effective when agreed by the manufacturer and the user. 2 Normative references The following normative documents contain provisions which, thro
15、ugh reference in this text, constitute provisions of this International Standard. At the time of publication, the editions indicated were valid. All normative documents are subject to revision, and parties to agreements based on this International Standard are encouraged to investigate the possibili
16、ty of applying the most recent editions of the normative documents indicated below. Members of IEC and ISO maintain registers of currently valid International Standards. IEC 381, Analogue signals for process control systems. IEC 382:1971, Analogue pneumatic signal for process control systems. IEC 41
17、0:1973, Sampling plans and procedures for inspection by attributes. IEC 873:1986, Methods of evaluating the performance of electrical and pneumatic analogue chart recorders for use in industrial-process control systems. 3 Sampling for test If, by agreement between user and manufacturer, tests are to
18、 be performed on a sample lot, it is recommended that a sampling method such as presented in IEC 410 be selected. When sampling is used, recorders to be tested may be chosen by the users inspector. 4 Definitions The main terms used for measuring the physical quantities are those used in IEC 873. acc
19、eptance test the acceptance test is intended to prove to the user that the device complies with certain conditions of its requirements as they appear in the contract 5 Performance test Environmental conditions at the location of testing shall be recorded. (See 5.1 of IEC 873.) Adjustments: For zero,
20、 span and damping, the routine tests shall be carried out with the final manufacturing adjustments (e.g., as acceptance tests) or with the adjustments determined by the user (e.g., after repair). The following tests shall be performed unless another series of tests is agreed between user and manufac
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- BS76231993ELECTRICALANDPNEUMATICANALOGUECHARTRECORDERSFORUSEININDUSTRIALPROCESSCONTROLSYSTEMSGUIDANCEFORINSPECTIONANDROUTINETESTING

链接地址:http://www.mydoc123.com/p-546928.html