BS 5583-1978 Specification for low voltage switchgear and controlgear for industrial use - Terminal marking distinctive number and distinctive letter for particular contactor relay.pdf
《BS 5583-1978 Specification for low voltage switchgear and controlgear for industrial use - Terminal marking distinctive number and distinctive letter for particular contactor relay.pdf》由会员分享,可在线阅读,更多相关《BS 5583-1978 Specification for low voltage switchgear and controlgear for industrial use - Terminal marking distinctive number and distinctive letter for particular contactor relay.pdf(12页珍藏版)》请在麦多课文档分享上搜索。
1、BRITISH STANDARD BS 5583:1978 EN 50011 Specification for Low voltage switchgear and controlgear for industrial use Terminal marking, distinctive number and distinctive letter for particular contactor relays This European Standard EN 50011 was given as from31May1978 the status of a British Standard U
2、DC 621.316.54:621.3.027.2:003.62BS5583:1978 This British Standard was published under the authority ofthe Executive Board on 31 May 1978 BSI 08-1999 The following BSI references relate to the work on this standard: Committee reference PEL/92 Draft for comment 73/26489 DC ISBN 0 580 101231 Cooperatin
3、g organizations The European Committee for Electrotechnical Standardization (CENELEC), under whose supervision this European Standard was prepared, comprises the National Committees of the following countries. Austria Netherlands Belgium Norway Denmark Portugal Finland Spain France Sweden Germany Sw
4、itzerland Ireland United Kingdom Italy Amendments issued since publication Amd. No. Date of issue CommentsBS5583:1978 BSI 08-1999 i Contents Page Cooperating organizations Inside front cover Foreword 2 Text of EN 50011 3 National appendix A Inside back cover National appendix B Inside back coverBS55
5、83:1978 ii BSI 08-1999 A British Standard does not purport to include all the necessary provisions of a contract. Users of British Standards are responsible for their correct application. Compliance with a British Standard does not of itself confer immunity from legal obligations. Summary of pages T
6、his document comprises a front cover, an inside front cover, pages i and ii, theEN title page, pages 2 to 6, an inside back cover and a back cover. This standard has been updated (see copyright date) and may have had amendments incorporated. This will be indicated in the amendment table on the insid
7、e front cover.EUROPEAN STANDARD NORME EUROPENNE EUROPISCHE NORM EN 50011 Edition 1 February 1977 UDC 621.316.54:621.3.027.2:003.62 Key words: Electrical switchgear and controlgear: industrial use: low voltage: terminal: marking: distinctive number: distinctive letter contactor relay auxiliary contac
8、t English version Low voltage switchgear and controlgear for industrial use Terminal marking, distinctive number and distinctive letter for particular contactor relays Appareillage industriel basse tension. Marquage des bornes, nombre caractristique et lettre caracteristique pour des contacteurs aux
9、iliaires particuliers Industrielle Niederspannungs-Schaltgerte. Anschlussbezeichnungen, Kennzahlen und Kennbuchstaben fr bestimmte Hilfsschtze This European Standard was accepted by CENELEC on 31 January 1977. CENELEC members are committed in accordance with CENELEC Internal Regulations to give this
10、 European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CENELEC General Secretariat or to any CENELEC member. This European Standard is established by CENELEC
11、 in three official versions (English, French, German). A translation made by another member under its own responsibility, in its own language, and notified to CENELEC has the same status. CENELEC members are the national electrotechnical committees of Austria, Belgium, Denmark, Finland, France, Germ
12、any, Ireland, Italy, Netherlands, Norway, Portugal, Spain, Sweden, Switzerland and UnitedKingdom. CENELEC European Committee for Electrotechnical Standardization Comit Europen de Normalisation Electrotechnique Europisches Komitee fr Elektrotechnische Normung Central Secretariat: rue de Stassart 35,
13、B-1050 Brussels Copyright reserved to all CENELEC membersEN50011 BSI 08-1999 2 Foreword This European Standard has been prepared byCENELEC Technical Committee 17X. Contactor relays may be given a distinctive number and terminal marking according to the General rules, EN50005. On this basis, it is de
14、sirable to lay down more detailed rules for particular contactor relays, such as those defined in clause1. Contents Page Foreword 2 1 Scope 3 2 Terminal marking rule 3 3 Distinctive number and distinctive letter 3 4 Contactor relays designated by the distinctive letter E 4 Table 1 Diagrams of contac
15、tor relays designatedby the distinctive letter E 5 Table 2 Diagrams of contactor relays designatedby the distinctive letter Y 6 Appendix A Contactor relays designated bydistinctive letters X, Y or Z 6EN50011 BSI 08-1999 3 1 Scope This standard applies to contactor relays according to IEC Standard337
16、, having specific relative positions of the contact elements and an associated terminal numbering sequence. These particular contactor relays are designated by a distinctive number followed by a specified distinctive letter. The use of this standard is recommended where terminal marking is a require
17、ment of the relevant standard for contactor relays, or is usual practice. 2 Terminal marking rule The contactor terminal marking of a contactor relay is formed, in principle, by two figures. 2.1 Function number. The unit number is a function number, i.e.: 1 2 for break-contacts; 3 4 for make-contact
18、s. 2.2 Sequence number. The figure of the tens is a continuous sequence number beginning with 1 (except for contactor relays designated01E), independently of the contact function. Terminals belonging to the same contact are marked with the same sequence number. For contactor relays having 10 contact
19、 elements, the sequence number 10 shall be replaced by 0. 2.3 Numbering method. The contact numbering is made, without any break, from left to right on the device; for devices with tiers, the numbering begins with the tier next to the mounting level. Example of contact numbering methods on contactor
20、 relays of various constructional types, but with the same distinctive number 62 E The prescribed numbering method does not allow blank contact cells inside a contact series. 3 Distinctive number and distinctive letter The number, type and location of contact elements of contactor relays according t
21、o this standard are indicated by a distinctive number followed by a distinctive letter. 3.1 Distinctive number. In accordance with EN 50005, clause 6, the first figure of the distinctive number gives the quantity of make-contact elements and the second figure the quantity of break-contact elements.
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- BS55831978SPECIFICATIONFORLOWVOLTAGESWITCHGEARANDCONTROLGEARFORINDUSTRIALUSETERMINALMARKINGDISTINCTIVENUMBERANDDISTINCTIVELETTERFORPARTICULARCONTACTORRELAYPDF

链接地址:http://www.mydoc123.com/p-545238.html