BS 5126-2-1993 Mining type flameproof supply and control units for use on systems up to 1100 V Specification for circuit breaker units《电压可达1100V的系统用矿山型阻燃式电源和控制装置 第2部分 断路器装置规范》.pdf
《BS 5126-2-1993 Mining type flameproof supply and control units for use on systems up to 1100 V Specification for circuit breaker units《电压可达1100V的系统用矿山型阻燃式电源和控制装置 第2部分 断路器装置规范》.pdf》由会员分享,可在线阅读,更多相关《BS 5126-2-1993 Mining type flameproof supply and control units for use on systems up to 1100 V Specification for circuit breaker units《电压可达1100V的系统用矿山型阻燃式电源和控制装置 第2部分 断路器装置规范》.pdf(26页珍藏版)》请在麦多课文档分享上搜索。
1、BRITISH STANDARD BS 5126-2: 1993 Mining type flameproof supply and control units for use on systems up to1100 V Part 2: Specification for circuit breaker unitsBS5126-2:1993 This British Standard, having been prepared under the directionof the Mining RequisitesStandards Policy Committee, was publishe
2、d underthe authority of the Standards Board and comesintoeffect on 15 December 1993 BSI 09-1999 First published November 1976 Second edition December 1993 The following BSI references relate to the work on this standard: Committee reference MRE/16 Draft for comment 89/79378 DC ISBN 0 580 22422 8 Com
3、mittees responsible for this BritishStandard The preparation of this British Standard was entrusted by the Mining Requisites Standards Policy Committee (MRE/-) to Technical Committee MRE/16, upon which the following bodies were represented: Association of British Mining Equipment Companies British C
4、oal Corporation Health and Safety Executive Amendments issued since publication Amd. No. Date CommentsBS5126-2:1993 BSI 09-1999 i Contents Page Committees responsible Inside front cover Foreword 2 1 Scope 1 2 References 1 3 Definitions 1 4 Information and requirements to be agreed and to be document
5、ed 2 5 Service conditions 3 6 Rated values 3 7 Design and construction 3 8 Verification and tests 10 9 Marking 10 Figure 1 Outline of enclosures showing arrangements for earthing terminals and skid couplings 12 Figure 2 Busbar chamber end flange 13 Figure 3 Busbar interconnecting trunk with cover pl
6、ate 14 Figure 4 650/1100 V busbar interconnecting adaptor trunk 15 Figure 5 650/1100 V skid coupling plate 16 Figure 6 End cover for busbar chamber 17 Figure 7 Example of outgoing cable fittings 18 Figure 8 Envelope dimensions for padlocks 19 Table 1 Circuit breaker performance 7 Table 2 Creepage di
7、stance and clearance 10 List of references 20BS5126-2:1993 ii BSI 09-1999 Foreword This Part of BS 5126 has been prepared, under the direction of the Mining Requisites Standards Policy Committee. It supersedes BS 5162-2:1976 which is withdrawn. This revision updates the standard to reflect todays us
8、age of 1100 V mining type flameproof supply and control units (commonly known in the UK as“gate-end boxes”) and takes account of expected future development. This Part of BS 5126 covers circuit breaker units, whilst Parts 1, 3 and 4 cover direct-on-line motor starter units, lighting transformer unit
9、s and units to power drilling machines, respectively. All have standard busbar and other fixing dimensions, enabling the different units to be fastened together to form a switchboard. This standard is arranged to be in close alignment with IEC (International Electrotechnical Commission) criteria for
10、 various electrical features. A British Standard does not purport to include all the necessary provisions of a contract. Users of British Standards are responsible for their correct application. Compliance with a British Standard does not of itself confer immunity from legal obligations. Attention i
11、s drawn to the Health and Safety at Work etc. Act 1974 1, the Mines and Quarries Act 1954 2, the Regulations made under these Acts, and also any other appropriate statutory requirements or byelaws. These place responsibility for complying with certain specific safety requirements on the manufacturer
12、 and the user. The addresses of the recognized certification authorities in the United Kingdom for Group I (for mines susceptible to firedamp) apparatus are: Health and Safety Executive Mining Equipment Certification Service Harpur Hill, Buxton, Derbyshire, SK17 9JN SIRA Certification Service Saight
13、on Lane Saighton Chester, CH3 6EG Summary of pages This document comprises a front cover, an inside front cover, pages i and ii, pages1 to 20, an inside back cover and a back cover. This standard has been updated (see copyright date) and may have had amendments incorporated. This will be indicated i
14、n the amendment table on the inside front cover.BS5126-2:1993 BSI 09-1999 1 1 Scope This Part of BS 5126 specifies requirements for flameproof supply and control units designed primarily for use in the coal mining industry on1100 V three-phase a.c. circuits and dual-voltage1100 V/550 V units with ci
15、rcuit breakers for the control and protection of power circuits. Provision is also made for operation on other voltages, where required. In addition to the definitive requirements, this standard also requires the items detailed in clause 4 to be documented. For compliance with this standard, both th
16、e definitive requirements and the documented items have to be satisfied. NOTE 1To facilitate cross-reference and subject location recall between the Parts of this standard, a uniformity of clause arrangements is maintained. At subclause level, because of the different purposes and individual technic
17、al features of the four types of control unit, some differences in title and/or subclause arrangements have been unavoidable, but have been made without disturbing the general pattern. NOTE 2The figures in this standard show only such features and dimensions essential for function and interchangeabi
18、lity. Dimensions are in millimetres. Untoleranced values less than100 mm are 0.15 mm and those greater than 100 mm are 0.25 mm. 2 References 2.1 Normative references This Part of BS 5126 incorporates, by reference, provisions from specific editions of other publications. These normative references a
19、re cited at the appropriate points in the text and the publications are listed on page 20. Subsequent amendments to, or revisions of, any of these publications apply to this Part of BS 5126 only when incorporated in it by updating or revision. 2.2 Informative references This Part of BS 5126 refers t
20、o other publications that provide information or guidance. Editions of these publications current at the time of issue of this standard are listed on the inside back cover, but reference should be made to the latest editions. 3 Definitions For the purposes of this Part of BS 51126, the following def
21、initions apply. 1) 3.1 supply and control unit (gate-end box) a flameproof enclosure containing electrical apparatus, such as transformer, control gear, switchgear and/or protective gear, designed primarily for use underground NOTE 1In this Part of BS 5126, the term “unit” has in many instances been
22、 used in abbreviation of “supply and control unit”. NOTE 2For the purposes of this Part of BS 5126, the enclosed apparatus is essentially an electrical circuit breaker with associated equipment. 3.2 circuit breaker a mechanical switching device, capable of making, carrying and breaking currents unde
23、r normal circuit conditions and also making, carrying for a specified time and breaking currents under specified abnormal circuit conditions such as those of short circuit NOTEA circuit breaker is usually intended to operate infrequently, although some types are suitable for frequent operation. 3.3
24、disconnector (isolator) a mechanical device capable of opening or closing a circuit under conditions of no load or negligible current 3.4 cable half coupler (flit plug) a detachable cable sealing box utilizing contact tubes and pins to facilitate ready connection to, ordisconnection from, a similar
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- BS512621993MININGTYPEFLAMEPROOFSUPPLYANDCONTROLUNITSFORUSEONSYSTEMSUPTO1100VSPECIFICATIONFORCIRCUITBREAKERUNITS

链接地址:http://www.mydoc123.com/p-544868.html