ASTM C1238-1997(2012) Standard Guide for Installation of Walk-Through Metal Detectors 《内置穿过式金属探测器的安装标准指南》.pdf
《ASTM C1238-1997(2012) Standard Guide for Installation of Walk-Through Metal Detectors 《内置穿过式金属探测器的安装标准指南》.pdf》由会员分享,可在线阅读,更多相关《ASTM C1238-1997(2012) Standard Guide for Installation of Walk-Through Metal Detectors 《内置穿过式金属探测器的安装标准指南》.pdf(4页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: C1238 97 (Reapproved 2012)Standard Guide forInstallation of Walk-Through Metal Detectors1This standard is issued under the fixed designation C1238; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revision, the year of last revis
2、ion. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope1.1 Some facilities require that personnel entering desig-nated areas be screened for concealed weapons and othermetallic materials.
3、 Also, personnel exiting designated areas areoften screened for metallic shielding material and other typesof metallic contraband. Walk-through metal detectors arewidely used to implement these requirements. This guidedescribes various elements to be considered when planning toinstall walk-through m
4、etal detectors.1.2 This guide is not intended to set performance levels, noris it intended to limit or constrain operational technologies.1.3 This standard does not purport to address all of thesafety concerns, if any, associated with its use. It is theresponsibility of the user of this standard to
5、establish appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use.2. Referenced Documents2.1 NRC Document:NUREG-1329 Entry/Exit Control At Fuel Fabrication Fa-cilities Using or Possessing Formula Quantities of Strate-gic Special Nuclear Materi
6、al22.2 U.S. Government Documents:DOE 5632.2A Physical Protection of Special Nuclear Ma-terials and Vital Equipment, February 9, 19883DOE 5633.3 Control and Accountability of Nuclear Mate-rials, February 3, 198832.3 National Fire Protection Associations (NPA) Life SafetyCode Handbook:NFPA-101-1988, C
7、hapter 28, Industrial Occupancy42.4 ANSI Standard:Z41.1-PT-1983 Class 50 and 75For Non-ferrous andFerrous Safety Footwear52.5 National Institute of Law Enforcement and CriminalJustice (NILECJ) Standard:0601.00 For Design, Performance, andAllowable MagneticField Strength33. Terminology3.1 Definitions
8、 of Terms Specific to This Standard:3.1.1 continuous-wave-type metal detectora system gen-erally employing one or more pairs of closely coupled coils.One coil is electrically energized to establish an electromag-netic field; the other detects disturbances in that field. Inoperation, the coils are co
9、nfigured so that the person or objectbeing screened passes through the field. When metal passesthrough the field, the field is modified by the magnetic andelectrical properties of the metal. Any change in the field issensed by measuring one or more of many possible parameters,including mutual induct
10、ance, power loss, phase shift, fre-quency shift, permeability, etc.3.1.2 nuisance alarman alarm not caused by a weapon orshielding material but by other causes such as outside interfer-ence or other operationally or environmentally induced stimu-lus. In practice, these alarms are a nuisance because
11、they arenot obvious and must be investigated and the cause eliminated.3.1.3 pulse-wave-type metal detectorsa system in whichbrief current pulses are generated in transmitter coils when theyare switched on. The electromagnetic field generated by thesepulses induces eddy currents in metallic objects i
12、n the field.The eddy currents decay when the transmitter coils are shut off.The decay of the eddy currents produces secondary voltages inthe receiver coils, which are switched on only when thetransmitter coils are switched off. The voltages induced in thereceiver coils are processed and compared aga
13、inst a bias orbackground level.3.1.4 shieldinga metallic material configured as a crediblegamma-radiation shield for special nuclear materials (SNM).1This guide is under the jurisdiction of ASTM Committee C26 on Nuclear FuelCycle and is the direct responsibility of Subcommittee C26.12 on SafeguardAp
14、plications.Current edition approved Jan. 1, 2012. Published January 2012. Originallyapproved in 1993. Last previous edition approved in 1997 as C1238 - 97(2003).DOI: 10.1520/C1238-97R12.2Available from the U.S. Nuclear Regulatory Commission, Washington, DC20555.3Available from U.S. Government Printi
15、ng Office Superintendent of Documents,732 N. Capitol St., NW, Mail Stop: SDE, Washington, DC 20401, http:/www.access.gpo.gov.4Available from National Fire Protection Association (NFPA), 1 BatterymarchPark, Quincy, MA 02169-7471, http:/www.nfpa.org.5Available from American National Standards Institut
16、e (ANSI), 25 W. 43rd St.,4th Floor, New York, NY 10036, http:/www.ansi.org.1Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.3.1.5 throughputthe actual rate at which a metal detectorand system can screen personnel for a given applicati
17、on.3.1.6 walk-through metal detectora free-standing screen-ing device having an electromagnetic field within its portalstructure (aperture) for detecting metallic objects, includingsome nuclear shielding materials, carried by persons walkingthrough the aperture.3.1.7 weapona device intended to do da
18、mage to personnelor equipment without intentionally harming the attacker, butrequiring the attacker to physically activate or use the device.4. Significance and Use4.1 This guide is intended for use by the designers, evalu-ators, and users of walk-through metal detectors to be installedto screen per
19、sons entering or leaving a controlled access area.This guide is not meant to constrain design liberty but is to beused as a guide in the selection of location and installation ofwalk-through metal detectors.5. Safety Considerations5.1 Warning signs should be posted if the metal detectorselectromagne
20、tic field strength is of such a magnitude thatpersonal medical devices may be affected or damaged whenthey pass through the portal. See NILECJ Standard 0601.00.5.2 Local fire and safety codes should be reviewed concern-ing requirements for areas selected for metal detector installa-tion. Metal-detec
21、tor installations needing exemption from thefire and safety requirements should be approved in advance.6. Throughput Consideration6.1 The rate at which persons may be screened is generallyan important factor in security applications. Metal-detectorsystems should be capable of dealing with large tran
22、sient trafficflow such as found during shift changes.6.1.1 Throughput varies from one metal detector model tothe next. Throughput also varies from one application to thenext. Applications that require high-sensitivity settings willhave lower throughput.6.1.2 Once the application specific throughput
23、for a detectormodel has been established, the number of detector lanesrequired to achieve system throughput at peak times can becalculated. See 9.2.7. Other Considerations7.1 Review applicable regulatory orders and policies ofappropriate regulatory agencies and facilities for informationpertinent to
24、 metal detector installation and operation.7.2 Examine the power capability of the building electricalsystem to ensure that it is adequate to support the metal-detector system, especially current, voltage, and voltage sta-bility.7.3 Confirm that the available primary and emergencypower are free of n
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMC123819972012STANDARDGUIDEFORINSTALLATIONOFWALKTHROUGHMETALDETECTORS 内置 穿过 金属探测器 安装 标准 指南 PDF

链接地址:http://www.mydoc123.com/p-463864.html