ASHRAE OR-10-013-2010 Data Centers’ Energy Auditing and Benchmarking-Progress Update《数据中心的能源审计和评判 过程更新》.pdf
《ASHRAE OR-10-013-2010 Data Centers’ Energy Auditing and Benchmarking-Progress Update《数据中心的能源审计和评判 过程更新》.pdf》由会员分享,可在线阅读,更多相关《ASHRAE OR-10-013-2010 Data Centers’ Energy Auditing and Benchmarking-Progress Update《数据中心的能源审计和评判 过程更新》.pdf(9页珍藏版)》请在麦多课文档分享上搜索。
1、2010 ASHRAE 109ABSTRACTThis paper presents a summary of the energy audit andoptimization studies conducted on more than 40 data centers.Comparison of data center energy efficiency metrics is pre-sented. Those metrics include energy utilization metrics suchas the Power Usage Effectiveness (PUE), Data
2、 Center infra-structure Efficiency (DCiE), mechanical PUE, electrical PUEand thermal or air management metrics such as bypass andrecirculation air flow ratios. Additionally, percentages of cool-ing system, fans, UPS losses, and lighting to total data centerpower were analyzed and presented. The impa
3、ct of climatezone as well as the operational load density compared todesign load density were considered as well. These metricsincorporate and integrate together the major factors thatdecrease the effectiveness of computer room air cooling andthe entire data center infrastructure. The energy utiliza
4、tionmetrics determine the extent of the efficiencies of the datacenter supporting mechanical and electrical infrastructures.Interestingly, the database indicated that small data centersRaised Floor Area (RFA) 30,000 ft22.1Figure 2 Annual average PUE. 2010, American Society of Heating, Refrigerating
5、and Air-Conditioning Engineers, Inc. (www.ashrae.org). Published in ASHRAE Transactions 2010, Vol. 116, Part 1. For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAEs prior written permission. ASHRAE Transactions
6、 113growth rate, and the expected PUE for the second year isprojected to be 2.7.The impact of climate zone on data center energy effi-ciency is another important dimension. The dependence onclimate zone is presented in Figure 7. Climate zones were ex-pressed in terms of cooling degree days (CDD). Co
7、ld climatezones “low CCD” causes the mechanical cooling systems tooperate more efficiently and offer potential for “free cooling”directly via an air economizer or indirectly via a water sideeconomizer. Hence, substantial reduction in mechanicalpower consumption and improved PUE. Hot climate zones(hi
8、gh CDD) were observed to have cooling systems operateat full capacity and therefore energy conservation strategiessuch as variable frequency drives may not necessarily be ben-eficial. Additionally, economizers are typically not utilized inthese climates. As an example, for a data center in Phoenix(c
9、limate 2B), limited options can be considered to lower thePUE compared to a data center in San Francisco (3C). TheFigure 3 Annual average PUEmechanical.Figure 4 Annual average PUEelectrical. 2010, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Publi
10、shed in ASHRAE Transactions 2010, Vol. 116, Part 1. For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAEs prior written permission. 114 ASHRAE Transactionshigh ambient temperature year round in Phoenix makes itm
11、ore difficult on the mechanical cooling system to make useof energy reduction strategies such as economizers and vari-able frequency drives. In contrast, data centers in colder cli-mate will have less power consumed by the mechanicalcooling system due to higher efficiency of the components atcooler
12、outdoor temperature. The cooler climate offer moreenergy efficiency measures to implement than hot climates.For example, in San Francisco, air economizers have been im-plemented successfully to cool IT equipment with outdoor airfor more than 7000 h per year. In Chicago area (5A), waterside economize
13、rs, for example, can be used to eliminate chill-ers power consumption for at least 25% of the year resultingin an overall reduction of the data center total power or PUEby 5 to 12%, depending on a variety of factors.Figure 7 shows that data collected from the 40 datacenters are scattered and, due to
14、 poor correlation, no cleardetermination of the impact of the climate zone is identified.Mathematically, the correlation of the data shows dependenceon the climate as indicated by the trend line.Figure 5 Variation in data center energy use.Figure 6 PUE as a function of data center growth. Figure 7 C
15、ooling system power consumption as a functionof cooling degree days (CDD). 2010, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Published in ASHRAE Transactions 2010, Vol. 116, Part 1. For personal use only. Additional reproduction, distribution, or
16、 transmission in either print or digital form is not permitted without ASHRAEs prior written permission. ASHRAE Transactions 115Since most of the obtained data are from legacy datacenters which didnt implement free cooling; one may expectthat the dependence on climate not to be drastic. To trulyquan
17、tify the data and conclusions further, the most efficientdata centers were found in climate 6A.The UPS losses as a percentage of the total data centerpower is shown in Figure 8 above. The percentage is expectedto be higher for more redundant system. For example, forreserve redundant UPS with automat
18、ic static transfer switch(RR w ASTS), one may maximize the load on the UPS up to100% of the name plate data compared to 75% for an N+1 (4modules) UPS system, 50% for a 2N system, and only 37.5%for a 2 2(N+1) with ASTS system. As already known, thehigher the load factor (% loading) of the UPS system;
19、 thelower the UPS losses. The top data point on the graph refersto a fault tolerant data center, highly reliable, combined witha very low (5 to 10%) UPS load factor. Generally speaking,UPS losses below 5% of the total building power are consid-ered good.The dependence on tier level is not presented
20、graphically,the acquired data showed no clear dependence on theperceived tier level (I,II,III, IV) of the facility (Uptime Insti-tute 2009). In other words, when PUE was plotted as a func-tion of the tier level, it was not possible to identify anydependence. Some of the efficient data centers werepe
21、rceived as tier IV facilities.Although generally accounts for small percentage in adata center total power, lighting is considered usually an easymethod to save energy. Many of the data centers audited havelights ON all the time in the raised floor area and not efficientlighting systems or control s
22、trategies. A few data centers werefound to have high bay MH 250 W lighting fixtures that are ONall the time. In addition to their nominal power consumption,an equivalent load is also placed on the cooling system.Several data center were found to have efficient zoned T8lighting fixtures with occupanc
23、y sensors. In many datacenters, retrofitting the existing lighting systems with occu-pancy sensors resulted in acceptable simple payback of lessthan 4 years especially when local utility incentives are takeninto account. Generally, if the lighting power consumption isless than 1%, then one might con
24、sider that to be good.The cooling system power percentage of the total datacenter power is plotted against the IT load is Figure 10 above.Once can easily observe that small data center with criticalload of less than 500 kW have higher mechanical coolingpower consumption and this percentage decreases
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASHRAEOR100132010DATACENTERS ENERGYAUDITINGANDBENCHMARKINGPROGRESSUPDATE 数据中心 能源 审计 评判 过程 更新 PDF

链接地址:http://www.mydoc123.com/p-455675.html