ASHRAE 4836-2006 Model Predictive Control of Supply Air Temperature and Outside Air Intake Rate of a VAV Air-Handling Unit《某变风量空气处理机组 室外空气摄入率和送风温度模型预测控制》.pdf
《ASHRAE 4836-2006 Model Predictive Control of Supply Air Temperature and Outside Air Intake Rate of a VAV Air-Handling Unit《某变风量空气处理机组 室外空气摄入率和送风温度模型预测控制》.pdf》由会员分享,可在线阅读,更多相关《ASHRAE 4836-2006 Model Predictive Control of Supply Air Temperature and Outside Air Intake Rate of a VAV Air-Handling Unit《某变风量空气处理机组 室外空气摄入率和送风温度模型预测控制》.pdf(17页珍藏版)》请在麦多课文档分享上搜索。
1、4836 Model Predictive Control of Supply Air Temperature and Outside Air Intake Rate of a VAV Air-Handling Unit Shui Yuan Ronald A. Perez, PhD, PE ABSTRACT This paper presents an integrated approach to controlling dry-bulb supply air temperature and outside air intake rate of an air-handling unit (AH
2、U) by adopting a model predictive control strategy. The dynamics ofthe AHU are modeled with a multi-input-multi-output (MIMO) model that has a linear structure and time-variant gains. The model predictive control (MPC) controller can respond properly to different working conditions by assigning diff
3、erent weighting factors and constraint limits to a convex quadratic optimization problem. Weighting factors andconstraint limits can be tuned in an intu- itive way and their control effects are easy to understand. A building simulator was created based on the jrst-principle component models develope
4、d in ASHRAE research project RP-825. The simulation-based experiments demonstrated that good temperature andflow rate controls were both achieved by using MPC. INTRODUCTION An air-handling unit (AHU), as a subsystem of a build- ings air distribution system, has two basic functions-condi- tioning and
5、 distributing air into thermal zones through ductwork and bringing enough outside air into a building to meet the ventilation requirement. The functions are expected to be performed with energy consumption as low as possible. Figure 1 shows a schematic of a single-duct variable-air- volume (VAV) air
6、-handling unit. Air is drawn from thermal zones by an extract fan, part of it is released through the exhaust damper, and the rest is recirculated and mixed with fresh air drawn in from ambient. The amount of outside air can be adjusted by varying positions of the three interlocked dampers. The mixe
7、d air then flows through a filter, a heating coil, and a cooling coil in sequence and is discharged into the thermal zones by a supply fan. Each damper is driven by a motor with a linkage. The flow rates of hot and chilled water entering the coils are regulated by motor-driven control valves. In a V
8、AV system, static pressure in supply-air duct should be maintained at some setpoint so that the volume flow rate of supply air varies based on demand of the thermal zones. In order to pressurize a building against infiltration, a volume flow rate difference between the supply and extract air is kept
9、 intentionally, which requires that the rotational speed of supply and extract fans both be under closed-loop controls. The AHU controller manipulates dampers and heating and cooling coils to regulate the dry-bulb temperature of the supply air. For the control of supply air temperature, since there
10、is one controlled variable (the supply air temperature) and three control elements (the dampers, the heating coil, and the cool- ing coil), a split-range control is commonly used in such a situ- ation (Astrm and Hgglund 1995). The spilt-control of supply air temperature is also called AHUsequencing
11、strategy (ASHRAE 1999b). The sequencing control uses a single proportional-plus-integral (PI) controller, which generates control signals based on the difference between supply air temperature and its setpoint. Based on the magnitude of the PI controllers output, only one of the dampers or the heati
12、ng coil and cooling coil will be under control by receiving nonzero control signals, while the other two are inactive receiving zero control signals. There are three operating states in terms of active components, i.e., mechanical cooling (when cooing coil is active), free cooling (when dampers are
13、active), and mechanical heating (when heating coil is active). For the _ Shui Yuan is a doctoral student and Ronald A. Perez is an associate professor in the Department of Mechanical Engineering, University of Wisconsin-Milwaukee. 02006 ASHRAE. 145 Il I ,I I I I I I I purpose of energy saving, the A
14、HU controller usually includes air-side economizer control that uses outside air to take partial cooling load of supply air. When the outside air conditions permit, i.e., when its dry-bulb temperature or enthalpy is lower than that of recirculated air, the outside-air damper will fully open to intro
15、duce 100% outside air. When outside air condi- tions are not favorable for energy saving, the outside-air damper will be set to its minimum position. The minimum position of the outside-air damper is expected to bring in a minimal amount of outside air to maintain indoor air quality (IAQ). Due to th
16、e economizer, a fourth operating state should be added to the sequencing control-partial free plus mechan- ical cooling (when the cooling coil is active and the outside- air damper is fully open). One drawback of the AHU sequencing strategy is using only one controller to control three components th
17、at have quite different dynamics and whose dynamics vary under different working conditions. Tuning such a controller is difficult (Astrm and Hgglund 1995). Another drawback is that the sequencing strategy may oscillate between two operating states. The occurrence of such a problem is due to the fac
18、t that the state transition is determined based on the difference between supply air temperature and its setpoint. When large overshoot or undershoot, caused by poorly tuned PI control- lers or state shifting, appear in the supply air temperature, alternate jumps between operating states may take pl
19、ace. An experiment conducted by Seem et al. (1999) showed that the dampers and heating coil alternately oscillated between their limit positions, which means the sequencing control worked alternately in free cooling and mechanical heating states. This unstable control led to supply air temperature o
20、scillating I 1 1 I AIRMWRATB Figure 1 Schematic of a single-duct VAV air-handling unit. around its setpoint. Such unstable control actions affect the system performance adversely in terms of poor setpoint track- ing, waste of energy, and unnecessary wearing of mechanical components. Using three sepa
21、rate PI controllers to control the dampers and the heating and cooling coils and using an ad hoc control- ler to manage the state transition of the sequencing control have been proposed (Seem et al. 1999; ASHRAE 1999b). The ad hoc controller is built based on the concept of a finite state machine, a
22、 modeling tool of event-driven systems, The ad hoc controller allows only one PI controller to operate at any time and determines whether or not a state transition is needed. If output of the then-active controller has reached and stayed at its limit for a time period equal to a predefined transitio
23、n delay, the sequencing control will be shifted to an appropriate state. The value of the delay should be carefully selected in order to achieve good control performance and avoid the oscillation problem. Xu et al. (2004) addressed the same issue by a similar methodology. They also used three dedica
24、ted PI controllers and one ad hoc controller, which was called a “freezing scheme.” The ad hoc controller always allowed one PI control- ler to be in charge while freezing outputs of the other two at zero. In addition, they applied a gain scheduling scheme to the PI controllers to improve their perf
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASHRAE48362006MODELPREDICTIVECONTROLOFSUPPLYAIRTEMPERATUREANDOUTSIDEAIRINTAKERATEOFAVAVAIRHANDLINGUNIT

链接地址:http://www.mydoc123.com/p-454382.html