1、MIL-M-60903A (AR)14 May 1986SUPERSEDINGMIL-M-60903(Mu)29 September 1967MILITARY SPECIFICATIONMARKING OF ELECTRICAL WIRES AND CABLESThis specification is approved for use by the U.S. Army Armament,Munitions and Chemical Command, and is available for use by allDepartments and Agencies of the Departmen
2、t of Defense.1. SCOPE1.1 This specification covers the process for marking ofidentification and designations on electrical wires and cables.Marking is normally accomplished by direct hot stamping on theouter insulation or jacket. Alternate methods involving the useof hot-stamped or ink-stamped ident
3、ification tapes and sleeves areused in special applications. The hot-stamped markings are inkedto provide visual contrast and are impressed for permanency.2. APPLICABLE DOCUMENTS2.1 The following documents, of the issue in effect on dateof invitation for bids, form a part of this specification:SPECI
4、FICATIONSMILITARYMIL-I-7444 - Insulation Sleeving, Electric, FlexibleMIL-T-713 - Twine, Fibrous, Impregnated, Lacing andTying(Copies of specifications, standards, drawings, and publicationsrequired by contractors in connection with specific procurementfunctions, should be obtained from the procuring
5、 activity, or asdirected by the contracting officer.)Beneficial comments (recommendations, additions, deletions), and any pertinent data whichmay be of use in improving his document, should be addressed to: Commander, US ArmyArmament, Munitions and Chemical Command, ATTN: AMSMC-QAN-Q(D), Dover, NewJ
6、ersey, 07801-5001, by using the self-addressed Standardization Document ImprovementProposal(DD Form 1426), appearing at the end of this document, or by letter.AMSC N/A FSC: 1195DISTRIBUTION STATEMENT A. Approved for public release; distribu-tion is unlimited.Provided by IHSNot for ResaleNo reproduct
7、ion or networking permitted without license from IHS-,-,-MIL-M-60903A (AR)3. REQUIREMENTS3.1 Designations.3.1.1 General application. The required designations shallbe applied by the method specified on the product drawing usingthe applicable procedure specified herein.3.1.2 Manufacturers designation
8、. When required, manufac-turers code letters will be assigned by the procuring activityand shall be located as shown on the product drawing. In addi-tion, the date code shall be marked by the manufacturer, whenrequired, in accordance with the following system:“A” for January, “B” for February, etc.,
9、 “77” for 1977, “78” for1978. etc. Example: “D78” indicates April 1978 manufacture.3.2 Hot-stamp marking.3.2.1 General information. When hot stamping is specified,the outer jacket or sleeving insulation shall be marked usinginked marking foils designed for the particular material beingmarked. The ma
10、rking shall be impressed to a depth not exceedingone-fourth of the thickness of the material. Markings shall bewhite on black, dark brown, dark blue, dark red, dark green, anddark purple material. Markings on other colors shall be black.Markings on transparent insulation sleeving shall be black exce
11、ptwhen the materials underneath are dark colors listed above, inwhich case the markings shall be white. Unless otherwise speci-fied, markings on white hook-up wires shall be black, Or of acontrast color to white if colored markings are desired tofacilitate production. The use of colored markings sha
12、ll beapproved by the procuring activity prior to being used inproduction.3.2.2 Equipment and accessories.3.2.2.1 Marking machine. Hot-stamp marking machines maybe either manually operated or automatic and shall be capableof marking the various forms of insulation materials at tempera-ture up to 500
13、Fahrenheit (F).2Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-MIL-M-60903A (AR)3.2.2.2 Marking foils. Marking foils must be chosen forcompatibility with the materials being marked to effect goodadhesion.3.2.2.3 Type. Type shall consist of vertical
14、capitals ofGothic or similar design. Flat-faced type shall be used formarking on flat surfaces such as on tape and polyvinyl sleeving,and curved-faced type for marking on curved surfaces such as onwires, cables, and sleeving where the type used shall be thelargest size which will produce impressed c
15、haracters on the par-ticular size of material.3.2.3 Procedure. The marking machine shall be fitted withthe correct size type, guide blocks, and foil and then heatedto the proper temperature before marking is begun. The sectionof the insulation to be marked should be well supported andcentered under
16、the type and the surface should be as parallelto the face of the type as possible; otherwise, some of the typemay cut through the insulation before all the characters areprinted. The optimum dwell time and pressure used for each typeand thickness of material shall be determined prior to markingthe p
17、roduction part. (The operation varialbes must be care-fully controlled. A short dwell time of 1 second or less isnormally employed except for nylon insulation which requires adwell time of 1 to 2 seconds. Polyvinyl plastic can be markedat 400 25F. and polyethylene and synthetic rubber insula-tion at
18、 375 25F. Nylon requires a temperature of approxi-mately 450F. Automatic machines may require higher temperaturethan hand-operated machines since shorter dwell times arenormally employed.)3.2.3.1 Hook-up wires. Markings on hook-up wires shallbe of two types as specified on figure 1. Either type may
19、beemployed unless otherwise specified on the product drawing.Type I - Markings shall be applied recurrently along thelength of the wire with at least one markingappearing near each end.Type II - Markings shall be applied twice at each end ofthe wire as illustrated. Markings may in addi-tion appear a
20、t intervals along the length ofthe wire.Markings need not be applied a specific distance from the endof the wire but shall be applied in such a location that thedesignation is readily visible near the end of the wire after3Provided by IHSNot for ResaleNo reproduction or networking permitted without
21、license from IHS-,-,-MIL-M-60903A (AR)FIGURE 14Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-MIL-M-60903A (AR)installation. Wires shorter than three inches, such as jumperwires, need not be marked unless specifically designated on theproduct drawin
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ARMYMILM60903A1986MARKINGOFELECTRICALWIRESANDCABLES 电线 电缆 标识 PDF

链接地址:http://www.mydoc123.com/p-445884.html