ANSI UL 199-2005 UL Standard for Safety Automatic Sprinklers for Fire-Protection Service (Eleventh Edition Reprint with Revisions Through and Including May 12 2017)《防火设施用自动喷水器的标准》.pdf
《ANSI UL 199-2005 UL Standard for Safety Automatic Sprinklers for Fire-Protection Service (Eleventh Edition Reprint with Revisions Through and Including May 12 2017)《防火设施用自动喷水器的标准》.pdf》由会员分享,可在线阅读,更多相关《ANSI UL 199-2005 UL Standard for Safety Automatic Sprinklers for Fire-Protection Service (Eleventh Edition Reprint with Revisions Through and Including May 12 2017)《防火设施用自动喷水器的标准》.pdf(137页珍藏版)》请在麦多课文档分享上搜索。
1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL UL 199 Automatic Sprinklers for Fire-Protection Service STANDARD FOR SAFETYUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM ULUL COPYRIGHT
2、ED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL UL Standard for Safety for Automatic Sprinklers for Fire-Protection Service UL 199 Eleventh Edition, Dated November 4, 2005 Summary of Topics This revision of ANSI/UL 199 is being issued to update the titl
3、e page to reect reaffirmation of ANSI approval. Text that has been changed in any manner or impacted by ULs electronic publishing system is marked with a vertical line in the margin. The new requirements are substantially in accordance with Proposal(s) on this subject dated March 17, 2017. All right
4、s reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted in any form by any means, electronic, mechanical photocopying, recording, or otherwise without prior permission of UL. UL provides this Standard as is without warranty of any kind, either expresse
5、d or implied, including but not limited to, the implied warranties of merchantability or tness for any purpose. In no event will UL be liable for any special, incidental, consequential, indirect or similar damages, including loss of prots, lost savings, loss of data, or any other damages arising out
6、 of the use of or the inability to use this Standard, even if UL or an authorized UL representative has been advised of the possibility of such damage. In no event shall ULs liability for any damage ever exceed the price paid for this Standard, regardless of the form of the claim. Users of the elect
7、ronic versions of ULs Standards for Safety agree to defend, indemnify, and hold UL harmless from and against any loss, expense, liability, damage, claim, or judgment (including reasonable attorneys fees) resulting from any error or deviation introduced while purchaser is storing an electronic Standa
8、rd on the purchasers computer system. The following table lists the future effective dates with the corresponding reference. MAY 12, 2017 UL 199 tr1UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL Future Effective Dates References February 20
9、, 2015 Paragraphs 7.7, 20.2, 28.1, 36A.1,36A.2,and 67.1.1 MAY 12, 2017 UL 199 tr2UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL NOVEMBER 4, 2005 (Title Page Reprinted: May 12, 2017) 1 UL 199 Standard for Automatic Sprinklers for Fire-Protec
10、tion Service First Edition December, 1919 Second Edition February, 1966 Third Edition December, 1967 Fourth Edition October, 1969 Fifth Edition May, 1974 Sixth Edition September, 1977 Seventh Edition July, 1982 Eighth Edition February, 1990 Ninth Edition December, 1995 Tenth Edition April, 1997 Elev
11、enth Edition November 4, 2005 This ANSI/UL Standard for Safety consists of the Eleventh Edition including revisions through May 12, 2017. The most recent designation of ANSI/UL 199 as a Reaffirmed American National Standard (ANS) occurred on May 12, 2017. ANSI approval for a standard does not includ
12、e the Cover Page, Transmittal Pages, and Title Page. Comments or proposals for revisions on any part of the Standard may be submitted to UL at any time. Proposals should be submitted via a Proposal Request in ULs On-Line Collaborative Standards Development System (CSDS) at https:/. ULs Standards for
13、 Safety are copyrighted by UL. Neither a printed nor electronic copy of a Standard should be altered in any way. All of ULs Standards and all copyrights, ownerships, and rights regarding those Standards shall remain the sole and exclusive property of UL. COPYRIGHT 2017 UNDERWRITERS LABORATORIES INC.
14、 ANSI/UL 199-2013 (R2017)UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL FEBRUARY 20, 2013 AUTOMATIC SPRINKLERS FOR FIRE-PROTECTION SERVICE - UL 199 2 No Text on This PageUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DIS
15、TRIBUTION WITHOUT PERMISSION FROM UL CONTENTS INTRODUCTION 1 Scope .7 2 Components .7 3 Units of Measurements 7 4 Undated References 8 5 Glossary .8 6 Terminology .10A CONSTRUCTION 7 General .10B 8 Inlet Threads 12 9 Temperature Ratings .12 10 Pressure Rating 13 11 Nominal “K” Factor 13 12 Coatings
16、And Platings .14 13 Protective Covers .14 PERFORMANCE GENERAL 14 Details .14 15 Samples 19 PHYSICAL STRENGTH AND LEAKAGE TESTS 16 Load on Heat Responsive Element Test .19 17 Strength Of Heat Responsive Element Test 19 17.1 Fusible-alloy types .19 17.2 Glass-bulb types 20 18 Glass-bulb Thermal Shock
17、Test .20 19 Strength Of Frame Test 21 20 Impact Resistance Test 21 21 Impact Test for Protective Covers .23 22 Rough Usage Test 25 23 Flow Endurance Test 25 24 Leakage Test .26 25 Hydrostatic Strength Test .26 26 Dry Sprinkler Air Tightness Test .26 27 30-Day Leakage Test 28 28 Water Hammer Test .29
18、 29 Vacuum Test .30 FEBRUARY 20, 2013 AUTOMATIC SPRINKLERS FOR FIRE-PROTECTION SERVICE - UL 199 3UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL OPERATION TESTS 30 Operating Temperature (Bath) Test .30 30A Air Bath Test for Glass Bulb Sprink
19、lers .30A 31 Sensitivity Tests 30A 31.1 General .30A 31.2 Oven heat test .30B 31.3 Room heat test for ordinary and intermediate temperature rated standard response ceiling type sprinklers (including concealed, ush, and recessed) 36 31.4 Room heat test for standard response extended coverage sprinkle
20、rs 40 31.5 Room heat test for QR and QR extended coverage sprinklers .40B 32 Operation Lodgement Test 40F 33 Cycling Tests For Flow Control (FC) Sprinklers .40I 33.1 Operational cycling test 40I 33.2 Cycling after water exposure test .40I 33.3 Contaminated-water cycling test 40I EXPOSURE AND CORROSI
21、ON TESTS 34 High Temperature Exposure Test (90 Day) .40J 35 High Temperature Exposure Test For Wax Coated Sprinklers 41 36 High Temperature Exposure Test For Flow Control (FC) Sprinklers 41 36A Heat Resistance Test 41 37 Elastomeric Parts Test 42 38 Vibration Test .42 39 Freezing Test .43 40 Evapora
22、tion Test For Wax Coatings .43 41 10-Day Corrosion Test .44 42 30-Day Corrosion Test .44 42.1 General .44 42.2 20 Percent salt spray .44A 42.3 Moist hydrogen sulde air mixture 44A 42.4 Moist carbon dioxide-sulfur dioxide air mixture .44B 43 90-Day Moist Air Test 44B 44 Exposure Tests On Sprinklers I
23、ncorporating Polymeric Gaskets .44B 44.1 General .44B 44.2 Corrosive exposures .45 44.3 Temperature cycling exposure 45 44.4 Hydrocarbon exposure followed by moist air exposure .45 44.5 Hydrocarbon exposure followed by water immersion exposure 46 44.6 Exposure to antifreeze solutions 46 45 Dry-Type
24、Sprinkler Deposit Loading Test 46 46 Dezincication Test of Brass Parts 47 46.1 General .47 46.2 Reagent 49 46.3 Test Pieces .49 46.4 Method 49 47 Stress-Corrosion Cracking Of Brass Sprinkler Parts Test 50 48 Stress-Corrosion Cracking Of Stainless Steel Sprinkler Parts Test .50 FEBRUARY 20, 2013 AUTO
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ANSIUL1992005ULSTANDARDFORSAFETYAUTOMATICSPRINKLERSFORFIREPROTECTIONSERVICEELEVENTHEDITIONREPRINTWITHREVISIONSTHROUGHANDINCLUDINGMAY122017

链接地址:http://www.mydoc123.com/p-439015.html