ANSI THERMO FRP DUCT CON MAN-2016 THERMOSET FRP DUCT CONSTRUCTION MANUAL (SECOND EDITION).pdf
《ANSI THERMO FRP DUCT CON MAN-2016 THERMOSET FRP DUCT CONSTRUCTION MANUAL (SECOND EDITION).pdf》由会员分享,可在线阅读,更多相关《ANSI THERMO FRP DUCT CON MAN-2016 THERMOSET FRP DUCT CONSTRUCTION MANUAL (SECOND EDITION).pdf(228页珍藏版)》请在麦多课文档分享上搜索。
1、THERMOSET FRP DUCT CONSTRUCTION MANUALSHEET METAL AND AIR CONDITIONING CONTRACTORS NATIONAL ASSOCIATION, INC. www.smacna.orgANSI/SMACNA 011-2017THERMOSET FRP DUCT CONSTRUCTION MANUALSECOND EDITION 2016SHEET METAL AND AIR CONDITIONING CONTRACTORS NATIONAL ASSOCIATION, INC.4201 Lafayette Center DriveC
2、hantilly, VA 20151 1219www.smacna.orgTHERMOSET FRP DUCT CONSTRUCTION MANUALCOPYRIGHT 2016All Rights ReservedbySHEET METAL AND AIR CONDITIONING CONTRACTORS NATIONAL ASSOCIATION, INC.4201 Lafayette Center DriveChantilly, VA 20151 1219Printed in the U.S.A.FIRST EDITION 1997SECOND EDITION 2016ISBN 978-1
3、-61721-120-1 PrintISBN 978-1-61721-121-8 PDFExcept as allowed in the Notice to Users and in certain licensing contracts, no part of this book may be reproduced, stored in a retrievable system, or transmitted, in any form or by any means, electronic, mechanical, photocopying, recording, or otherwise,
4、 without the prior written permission of the publisher.Thermoset FRP Duct Construction Manual Second Edition iiiFOREWORDThis is the second edition of the Thermoset FRP Duct Construction Manual with the fi rst edition published in 1997. As with the fi rst edition, this second edition is an authoritat
5、ive manual that design engineers, industrial engineering departments, pollution control authorities, FRP manufactures and installation contractors can rely upon for the proper selection, manufacture, and installation of FRP duct systems. Key updates of this second edition include: Recognize the incr
6、eased use of FRP ductwork in commercial/HVAC applications. New language is included on FRP ductwork for commercial/HVAC applications. Chapter added covering underground FRP duct installation Round duct sizes are expanded to 96 in. Hanger and Support section is now expanded into a separate chapter. U
7、pper attachments are now covered. Rectangular and round duct hanger tables added for easier selection. Hanger bar and hanger rod sizes increased. Riser support details added Rectangular duct stiffener tables are added for easier selection Appendix added indicating information on extended hanger spac
8、ing Appendix added indicating general information on safe handling of thermoset fi berglass reinforced plastic duct Glossary updatedSMACNA thanks the SMACNA contractors who, as members of the Thermoset FRP Duct Construction Task Force, volunteered their time and effort to the development of this man
9、ual. SMACNA appreciates their dedication and willingness to share their knowledge and experience in the fabrication and installation of Thermoset FRP Ductwork.SHEET METAL AND AIR CONDITIONING CONTRACTORS NATIONAL ASSOCIATION, INC.iv Thermoset FRP Duct Construction Manual Second EditionFRP TASK FORCE
10、CONSULTANTAndy Groh, ChairpersonAlthoff Industries, Inc.Crystal Lake, ILTerry CahillCrawford CompanyRock Island, ILBrian FlannaganPrimary Plastics, Inc.Endwell, NYBrian LindholmStreimer Sheet Metal Works, Inc.Portland, OregonShawn OHara, Staff LiaisonSMACNAChantilly, VAJoseph M. Plecnik, PhD, P.E.Te
11、sting, Inspection constructing the ductwork in conformance with the FRP DCS, and; notwithstanding the inherent low leakage of FRP ducts, identifying joints and duct wall penetra-tions which require sealer and sealing the ductwork properly.The designer is responsible for determining the pres-sure cla
12、ss or classes required for duct construction and Thermoset FRP Duct Construction Manual Second Edition 1.3for evaluating the amount of sealing necessary to achieve system performance objectives. It is recom-mended that all FRP ducts used in commercial HVAC applications operating at 1 in. (250 Pa) an
13、d in. (125 Pa) pressure class meet Seal Class C. However, because designers sometimes deem leakage in unsealed ducts not to have adverse effects, the sealing of all ducts in the 1 in. (250 Pa) and in. (125 Pa) pressure class is not required by the FRP DCS. When Seal Class C is to apply to all 1 in.
14、(250 Pa) and in. (125 Pa) pressure class duct, the designer must require this in the project specifi cation. The designer should review the ANSI/SMACNA HVAC Air Duct Leakage Test Manual for estimated and practical leakage allowances. Specifi c to duct sealing, if the designer does not desig-nate a p
15、ressure class for duct construction on the con-tract drawings, the basis of compliance with the FRP DCS is as follows: 2 in. wg (500 Pa) for all ducts between the supply fan and any terminal unit and 1 in. wg (250 Pa) for all other ducts of any application.Some sealants can adversely affect the rele
16、ase func-tion of breakaway connections to fi re dampers; consult the damper manufacturer for installation restrictions.For standard duct sealing requirements for commer-cial HVAC applications, reference Table 1-1.1.8 DUCT LEAKAGE TESTS1.8.1 FRP ducts used in process/corrosive applicationsIf FRP duct
17、s used in process/corrosive application require duct leakage tests, the contract documents must clearly designate the portions of the system(s) to be tested and the appropriate method of test and the appropriate test pass/fail criteria.1.8.2 FRP ducts used in commercial HVAC applicationsFor FRP duct
18、s used in commercial HVAC applications and constructed in accordance with the FRP DCS, there is no need to verify leakage control by fi eld testing when adequate methods of FRP fabrication and assembly are used. Leakage tests are an added expense in system installation. It is not recommended that du
19、ct systems constructed to 3 in. wg (750 Pa) class or lower be tested because this is generally not cost effective. For duct systems constructed to 4 in. wg (1000 Pa) class and higher, the designer must deter-mine if any justifi cation for testing exists. If it does, the contract documents must clear
20、ly designate the por-tions of the system(s) to be tested and the appropriate test methods. ASHRAE energy conservation standards series 90 text on leakage control generally requires tests only for pressures in excess of 3 in. wg (750 Pa).The ANSI/SMACNA HVAC Air Duct Leakage Test Manual as necessaril
21、y altered to incorporate FRP ducts, provides practical and detailed procedures for conducting leakage tests.Note for the Designer: For duct leakage testing, the test pressure shall not exceed the duct construction pressure class. The designer must specify duct system pressure relief procedures and p
22、recautions to protect and prevent duct systems from over pressurization.Note: For underground FRP duct installations, required duct leakage testing procedures shall be completed and approved prior to commencing backfi ll procedures. 1.9 CONTENTSThe manual is subdivided into twelve chapters and nine
23、appendices, which are briefl y described as follows:Seal Class Sealing Requirements Applicable Static Pressure Construction ClassA Class A: All Transverse joints, longitudinal seams, and duct wall penetrations4 in. wg and up (1000 Pa)B Class B: All Transverse joints and longitudinal seams only3 in.
24、wg (750 Pa)C Class C: Transverse joints only 2 in. wg (500 Pa)Table 11 Standard Duct Sealing Requirements For Commercial HVAC ApplicationsIn addition to the above, any duct systems up to 1 in. wg (250 Pa) construction class that is upstream of terminal units shall meet Seal Class C.1.4 Thermoset FRP
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ANSITHERMOFRPDUCTCONMAN2016THERMOSETFRPDUCTCONSTRUCTIONMANUALSECONDEDITIONPDF

链接地址:http://www.mydoc123.com/p-438228.html