ANSI ATIS 0600320-2015 Above-Baseline Electrical Protection for Designated Telecommunications Central Offices and Similar-Type Facilities Against High-Altitude Electromagnetic Puls.pdf
《ANSI ATIS 0600320-2015 Above-Baseline Electrical Protection for Designated Telecommunications Central Offices and Similar-Type Facilities Against High-Altitude Electromagnetic Puls.pdf》由会员分享,可在线阅读,更多相关《ANSI ATIS 0600320-2015 Above-Baseline Electrical Protection for Designated Telecommunications Central Offices and Similar-Type Facilities Against High-Altitude Electromagnetic Puls.pdf(18页珍藏版)》请在麦多课文档分享上搜索。
1、 AMERICAN NATIONAL STANDARD FOR TELECOMMUNICATIONS ATIS-0600320.2015 Above-Baseline Electrical Protection for Designated Information and Communications Technology (ICT) Facilities Against High-Altitude Electromagnetic Pulse (HEMP) As a leading technology and solutions development organization, the A
2、lliance for Telecommunications Industry Solutions (ATIS) brings together the top global ICT companies to advance the industrys most pressing business priorities. ATIS nearly 200 member companies are currently working to address the All-IP transition, network functions virtualization, big data analyt
3、ics, cloud services, device solutions, emergency services, M2M, cyber security, network evolution, quality of service, billing support, operations, and much more. These priorities follow a fast-track development lifecycle from design and innovation through standards, specifications, requirements, bu
4、siness use cases, software toolkits, open source solutions, and interoperability testing. ATIS is accredited by the American National Standards Institute (ANSI). The organization is the North American Organizational Partner for the 3rd Generation Partnership Project (3GPP), a founding Partner of the
5、 oneM2M global initiative, a member of and major U.S. contributor to the International Telecommunication Union (ITU), as well as a member of the Inter-American Telecommunication Commission (CITEL). For more information, visit www.atis.org. AMERICAN NATIONAL STANDARD Approval of an American National
6、Standard requires review by ANSI that the requirements for due process, consensus, and other criteria for approval have been met by the standards developer. Consensus is established when, in the judgment of the ANSI Board of Standards Review, substantial agreement has been reached by directly and ma
7、terially affected interests. Substantial agreement means much more than a simple majority, but not necessarily unanimity. Consensus requires that all views and objections be considered, and that a concerted effort be made towards their resolution. The use of American National Standards is completely
8、 voluntary; their existence does not in any respect preclude anyone, whether he has approved the standards or not, from manufacturing, marketing, purchasing, or using products, processes, or procedures not conforming to the standards. The American National Standards Institute does not develop standa
9、rds and will in no circumstances give an interpretation of any American National Standard. Moreover, no person shall have the right or authority to issue an interpretation of an American National Standard in the name of the American National Standards Institute. Requests for interpretations should b
10、e addressed to the secretariat or sponsor whose name appears on the title page of this standard. CAUTION NOTICE: This American National Standard may be revised or withdrawn at any time. The procedures of the American National Standards Institute require that action be taken periodically to reaffirm,
11、 revise, or withdraw this standard. Purchasers of American National Standards may receive current information on all standards by calling or writing the American National Standards Institute. Notice of Disclaimer and NOTE Additional bonding conductor B1 is not required if the existing bond between t
12、he grounding electrode system (GES) and Reference Point 0, or Building Principal Ground (BPG) in ATIS-0600333, is less than 3 meters (10 feet). b) The main ac service equipment ground (bond B2 in Figure 6.2). This bond can be omitted if the ground bars for the cable entrance facility, the main ac se
13、rvice equipment, and the building grounding electrode are within 10 meters (32 feet) of each other. Direct bonds should also be placed between the ground bars of cable entrance facilities if there is more than one in a building. This measure shall not be in conflict with measures for insulating entr
14、ance cables as discussed in clause 8.2.3 of ATIS-0600313. 6.3.1.2 Bonds to Building Steel If the building has structural steel, direct bonds should be installed between the steel and: a) The main ac service equipment ground (bond B3 in Figure 6.2); and b) The ground bar for metallic members of outsi
15、de plant cables in each cable entrance facility (bond B3 in Figure 6.2). The building steel should be accessed at the closest practical point to these components. In new construction, the access to structural steel should be within 1 meter (3 feet) of the grounding bar in a cable entrance facility.
16、6.3.1.3 Bonds to an Exterior Ground Ring If the building has an exterior ground ring, direct bonds shall be installed at the closest practical point between the ground ring and: a) The main ac service equipment ground (bond B4 in Figure 6.2); and b) The ground bar for metallic members of outside cab
17、les in each cable entrance facility (bond B4 in Figure 6.2). ATIS-0600320.2015 6 6.3.2 Surge Protective Device (SPD) at AC Power Service Entrance A surge protective device (SPD) shall be placed between the phase and neutral/ground conductors at the main ac power service entrance. This protective mea
18、sure applies even when the serving ac power distribution line is not considered to be subject to overvoltage disturbances caused by lightning surges or power system transients (see ANSI/IEEE C62.41). 6.3.2.1 Surge Protective Device (SPD) To limit surge voltages that may enter the building on the ac
19、power service conductors, a surge protective device (SPD), which can withstand the standard waveshapes characteristic of premises wiring (see ANSI/IEEE C62.41) and shall be Listed to UL 1449. Application of the device, including the placement and method of installation, should provide for connecting
20、 leads from the power line conductors to the active elements of the device that are as short and straight as is practical, ideally less than 0.5 meters (1.6 feet) - see Annex A, reference 5. 6.3.3 Pair Protection Present understanding of HEMP induced voltages that appear at pair terminations at prot
21、ector frames indicates that baseline protection, if present, on pairs as described in ATIS-0600313 is adequate to protect equipment from HEMP induced surges. The voltages that develop due to the inductances associated with the paths to ground from the protectors are likely to be more significant tha
22、n the voltages that appear across the terminals of protectors. 6.3.4 Protection of Local Antenna Leads (Coaxial, Waveguide) A waveguide or outer conductor (shield) of a coaxial cable from a local antenna shall be grounded at the Point Of Entry (POE) to the exterior grounding electrode system. The PO
23、E should be located close to an existing exterior earth grounding conductor directly connected to the exterior grounding electrode system. This ground can also be accomplished by a connection to a nearby lightning protection system of a rooftop mounted tower, if the system conforms to 10.3.3 of ATIS
24、-0600313. If such grounding is not practical, connection should be made to a horizontal equalizer conductor (if present) of the CBN of the building. Where a lightning protection system is in place, common bonding to provide equalization shall meet the requirements of NFPA 780. If the antenna has a r
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ANSIATIS06003202015ABOVEBASELINEELECTRICALPROTECTIONFORDESIGNATEDTELECOMMUNICATIONSCENTRALOFFICESANDSIMILARTYPEFACILITIESAGAINSTHIGHALTITUDEELECTROMAGNETICPULSPDF

链接地址:http://www.mydoc123.com/p-433480.html