ANSI American Society of Sanitary Engineering 1001-2016 Performance Requirements for Atmospheric Type Vacuum Breakers.pdf
《ANSI American Society of Sanitary Engineering 1001-2016 Performance Requirements for Atmospheric Type Vacuum Breakers.pdf》由会员分享,可在线阅读,更多相关《ANSI American Society of Sanitary Engineering 1001-2016 Performance Requirements for Atmospheric Type Vacuum Breakers.pdf(24页珍藏版)》请在麦多课文档分享上搜索。
1、Performance Requirements for Atmospheric Type Vacuum BreakersASSE InternationalASSE Standard #1001-2017ASSE Board Approved: November 2016ANSI Approved: April 2017ICS Codes: 23 060 9991 140 60An American National StandardAtmospheric Type Vacuum Breakers iASSE Standard #1001-2017ASSE InternationalMoke
2、na, IllinoisCopyright 2017, 2008, 2002, 1993, 1990, 1988, 1980, 1970, 1962All rights reserved.Neither this standard, nor any portion thereof, may be reproduced without the written consent of ASSE International.No product may be said to be listed by ASSE unless the manufacturer has applied to ASSE In
3、ternational, had its product tested by an official ASSE recognized independent laboratory according to the applicable standard, passed the tests, and had its documentation reviewed and approved by the consensus ASSE Seal Control Board. Having completed the aforementioned, the manufacturer may displa
4、y the ASSE Seal on the product.Instructions for receiving the authorization to display the seal are available from the ASSE International office. Organizations wishing to adopt or list any ASSE standard should print the ASSE standard number on the cover page first in equal or larger type to that of
5、the adopting or listing organization. General Informationii Atmospheric Type Vacuum Breakers ASSE Standard #1001-2017This foreword shall not be considered a part of the standard; however, it is offered to provide background information.ASSE standards are developed in the interest of consumer safety.
6、 ASSE considers product performance standards to be of great value in the development of improved plumbing systems.To accomplish this, ASSE, through its Product Standards Committee, encourages manufacturers to assist in the development of performance and testing procedures. Realizing the need for a
7、uniform standard that manufacturers and laboratory personnel could use in testing and evaluating the performance of anti-siphon vacuum breakers installed in potable water supply systems, ASSE formed a committee to develop such a standard in 1958. The committee consisted of directors and personnel of
8、 plumbing testing laboratories in Chicago, Detroit and Los Angeles, as well as a representative of the Bureau of Water Register of the New York City Department of Water Supply. Through the Product Standards Committee, with the cooperation of interested manufacturers, a standard was developed Perform
9、ance Requirements and Test Methods for Atmospheric Type, Anti-Siphon Devices.At the 1962 ASSE Annual Meeting in Little Rock, Ark., the work of the committee culminated in the acceptance of the standard, which was assigned the official number ASSE 1001. This 2017 revision of the standard has added pe
10、rformance criteria specific to vacuum breakers intended specifically for flushometer applications and for those intended to be integral to other plumbing devices. In those cases, flushometers and integral-type devices shall have standards associated with their function covering certain sections in A
11、SSE 1001, e.g. ASSE 1037/ASME A112.19.1037/CSA B125.37-2015 covers flushometers, ASME A112.18.1/CSA B125.1 covers plumbing supply fittings, and ASME A112.4.2/ CSA B45.16 covers personal hygiene devices.The working group that developed this standard revision was set up within the framework of the ASS
12、E International Product Standards Committee. Recognition is made of the time volunteered by members of this working group and of the support of manufacturers, who also participated in the meetings for this standard.This standard does not imply ASSEs endorsement of a product that conforms to these re
13、quirements.Compliance with this standard does not imply acceptance by any code body.It is recommended that these devices be installed consistent with local codes by qualified and trained professionals.This standard was promulgated in accordance with procedures developed by the American National Stan
14、dards Institute (ANSI). ForewordAtmospheric Type Vacuum Breakers iiiASSE Standard #1001-2017ASSE Vacuum Breaker StandardsASSE Standard NumberStandard Name Typical Use Highlights1001Atmospheric Type Vacuum Breakers Faucet with hose thread spout Water closet fill valvePrevents Backsiphonage: Outlet is
15、 open to atmosphere Not subjected to backpressure Not be subjected to more than twelve (12) hours of continuous water pressure1011Hose Connection Vacuum Breakers Hose connections, such as hose bib, wall hydrant, yard hydrant Prevents backflow by use of a SINGLE CHECK valve Prevents backsiphonage by
16、use of AIR PORTS Prevents backpressure by use of check valve and relief of backpressure through air ports. i.e. relieves pressure in the hose. Non-removable and non-testable1020Pressure Vacuum Breakers Irrigation systems Industrial processesPrevents Backsiphonage: Uses a SINGLE CHECK Not subjected t
17、o backpressure Can be subjected to continuous water pressure in excess of twelve (12) hours1052Hose Connection Backflow Preventers Hose connections, such as hose bib, wall hydrant, yard hydrantSame as a 1011 device except there are two check valves. One check valve holds the pressure in the hose. Th
18、e Intermediate chamber between check vales becomes atmospheric. Device is non-removable but is testable.1056Spill Resistant Vacuum Breakers Indoor plumbing assemblies Medical equipmentSame as 1020 but does not spill water when pressurized.Standard No. Dual Check Air Ports Backflow Backsiphonage Back
19、pressure Frost Free Removable TestableHigh Hazard1001N Y N Y N N Y N Y1011N Y Y Y Y N N N Y1020N Y N Y N N Y Y Y1052Y Y Y Y Y N N Y Y1056N Y N Y N N Y Y Yiv Atmospheric Type Vacuum Breakers ASSE Standard #1001-2017Edward J. Lyczko, ChairpersonCleveland Clinic Retiree Cleveland, OHWilliam Briggs, Jr.
20、MGJ AssociatesNew York, NYTerry BurgerNSF InternationalYpsilanti, MIWilliam ChapinProfessional Code Consulting, LLCCullman, ALMark FishZurn Industries, LLCCary, NCRon GeorgePlumb-Tech Design 2) Not be subjected to backpressure;3) Not be subjected to more than twelve (12) hours of continuous water pr
21、essure; and4) Be installed with its critical level (CL) not less than 6.0 inches (152.4 mm) above the flood level rim of the fixture or appliances served; or deck mounted/equipment mounted atmospheric vacuum breakers shall be installed in accordance with the manufacturers instructions, with its crit
22、ical level (CL) not less than 1.0 inch (25.4 mm) above the flood level rim of the fixture or appliance served.1.2 Scope1.2.1 DescriptionVacuum breakers shall be classified in two general types: Atmospheric type, as described herein Pressure type (See ASSE Standard 1020, Performance Requirements for
23、Pressure Vacuum Breaker Assembly, and ASSE Standard 1056, Spill Resistant Vacuum Breakers)The atmospheric type design shall consist of:a) A check valve memberb) An air inlet valve that is closed when the check valve member is open, and normally open when the check valve member is normally closed.The
24、 atmospheric type design can be further classified into three categories, depending on use:1) Pipe-applied2) Flushometer-applied3) Integrally-appliedDevices shall include an air inlet shield.2 Atmospheric Type Vacuum Breakers ASSE Standard #1001-20171.2.2 SizesPipe-applied vacuum breaker assembly in
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ANSIAMERICANSOCIETYOFSANITARYENGINEERING10012016PERFORMANCEREQUIREMENTSFORATMOSPHERICTYPEVACUUMBREAKERSPDF

链接地址:http://www.mydoc123.com/p-430838.html