1、 2011 Standard for Performance Rating of Air Terminals Approved by ANSI on December 6, 2012 ANSI/AHRI Standard 881 (SI) with Addendum 1 Price $10.00 (M) $20.00 (NM) Copyright 2011, by Air-Conditioning, Heating, and Refrigeration Institute Printed in U.S.A. Registered United States Patent and Tradema
2、rk Office ANSI/AHRI STANDARD 881 (SI)-2011 WITH ADDENDUM 1, PERFORMANCE RATING OF AIR TERMINALS June 2012 Addendum 1 (dated June 2012) of ANSI/AHRI Standard 881 (SI)-2011 modifies AHRI Standard 880 (SI)-2011 as follows. The following changes have been incorporated (additions are shown by shading and
3、 deletions are shown by strikethroughs) into the second sentence of Section 6.1.3.4 of the already published 2011 version of ANSI/AHRI Standard 881 (SI)-2011. Also, ANSI/AHRI Standard 260-2011 has been added to Appendix A. The changes include: 6.1.3.4 Discharge Sound Power. To determine discharge So
4、und Power Level, the Air Terminal shall be installed in accordance with Figures 9.1 through 9.3 of ASHRAE Standard 130. The test duct shall be flush with the inside wall of the reverberation room and shall be constructed in accordance with Section 4.5.1 of ANSI/AHRI Standard 260. Alternatively, for
5、Integral Diffuser Air Terminals, the discharge Sound Power Level may be determined in accordance with Figure 9.4 of ASHRAE Standard 130. For Modulating Diffuser Air Terminals, the discharge Sound Power Level shall be determined in accordance with Figures 5 and 6 of ANSI/ASHRAE Standard 70. APPENDIX
6、A. REFERENCES NORMATIVE A1 Listed here are all standards, handbooks, and other publications essential to the formation and implementation of the standard. All references in this appendix are considered as part of this standard. A1.1 AHRI Standard 220-2007, Reverberation Room Qualification and Testin
7、g Procedures for Determining Sound Power of HVAC Equipment, 2007, Air-Conditioning, Heating, and Refrigeration Institute, 2111 Wilson Boulevard, Suite 500, Arlington, VA 22201, U.S.A. A1.2 AHRI Standard 410-2001, Forced Circulation Air-Cooling and Air-Heating Coils, 2001, Air-Conditioning, Heating,
8、and Refrigeration Institute, 2111 Wilson Blvd., Suite 500, Arlington, VA 22201, U.S.A. A1.3 AHRI Standard 440-2008, Performance Rating of Room Fan-Coils, 2008, Air-Conditioning, Heating, and Refrigeration Institute, 2111 Wilson Blvd., Suite 500, Arlington, VA 22201, U.S.A. A1.4 AHRI Standard 885-200
9、8 (with Addendum 1 dated March 2011) , Procedure for Estimating Occupied Space Sound Levels in the Application of Air Terminals and Air Outlets, 2008, Air-Conditioning, Heating, and Refrigeration Institute, 2111 Wilson Blvd., Suite 500, Arlington, VA 22201, U.S.A. A1.5 ANSI/AHRI Standard 260-2011, S
10、ound Rating of Ducted Air Moving and Conditioning Equipment, 2011, Air-Conditioning, Heating, and Refrigeration Institute, 2111 Wilson Boulevard, Suite 500, Arlington, VA 22201, U.S.A. A1.6 ANSI/ASHRAE 70-2006 (R2011), Method of Testing for Rating the Performance of Air Outlets and Inlets, 2006, Ame
11、rican Society of Heating, Refrigerating, and Air-Conditioning Engineers, Inc., 1791 Tullie Circle N.E., Atlanta, GA 30329, U.S.A. A1.7 ASHRAE 130-2008, Methods of Testing for Rating Ducted Air Terminal Units, 2008, American Society of Heating, Refrigerating, and Air-Conditioning Engineers, Inc., 179
12、1 Tullie Circle N.E., Atlanta, GA 30329, U.S.A. A1.8 ASHRAE Terminology of Heating, Ventilation, Air Conditioning, classifications; test requirements; rating requirements; minimum data requirements for Published Ratings; marking and nameplate data; and conformance conditions. 1.1.1 Intent. This stan
13、dard is intended for the guidance of the industry, including manufacturers, engineers, installers, contractors and users. 1.1.2 Review and Amendment. This standard is subject to review and amendment as technology advances. Section 2. Scope 2.1 Scope. This standard applies to air control devices used
14、 in air distribution systems. These devices provide control of air volume with or without temperature control by one or more of the following means and may or may not include a fan: 2.1.1 Fixed or adjustable directional vanes (i.e. Bypass Air Terminal) 2.1.2 Pressure dependent volume dampers or valv
15、es (including air induction nozzles and Dampers) 2.1.3 Pressure compensated volume dampers or valves (including air induction nozzles and Dampers) 2.1.4 Integral heat exchange 2.1.5 On/off fan control 2.1.6 Variable speed fan control 2.1.7 Integral Diffuser Air Terminals 2.2 Exclusions. This standar
16、d does not apply to registers, diffusers and grilles or to products specifically covered by AHRI Standard 410 or AHRI Standard 440. Section 3. Definitions All terms in this document follow the standard industry definitions in the current edition of ASHRAE Terminology of Heating, Ventilation, Air Con
17、ditioning, and Refrigeration unless otherwise defined in this section. 3.1 Acoustic Test Duct. Duct used to convey the sound of the unit configuration under test to the reverberation room during a ducted discharge test. A duct end correction (E1) shall be added to the sound data measured in the reve
18、rberation room to account for the presence of an open-ended duct termination. 3.2 Acoustically Isolated. The specimen under test shall have a sound pressure level at least 10 dB higher than any extraneous sound sources, such as sound generated from the air supply or duct walls, to insure that the te
19、st specimen is the sole contributor to the sound level being measured. 3.3 Air. 3.3.1 Primary Air. Air supplied to an air terminal inlet under positive static gage pressure, normally from an air handling unit. 3.3.2 Secondary Air. Air drawn into an Air Terminal by means of induction and discharged t
20、hrough the air terminal outlet. 3.3.3 Standard Air. Air weighing 1.2 kg/m3which approximates dry air at 21C and at a barometric pressure of 101.3 kPa . ANSI/AHRI STANDARD 881 (SI)-2011 2 3.4 Airflow. Unit volume displacement of standard air per unit time, m3/s . The various types of airflow are defi
21、ned as follows: 3.4.1 Induced Airflow. The flow of secondary air into an Air Terminal resulting from a pressure differential within the terminal.3.4.2 Rated Airflow. The flow of air through an Air Terminal at which test or performance data is generated. 3.4.3 Standard Airflow. Airflow corrected for
22、standard air density. Qs= Qa(a/s) 1 3.5 Air Terminal . A device that modulates the volume of air delivered to or removed from a defined space in response to an external demand (Figure 1). The various types of Air Terminals are: 3.5.1 Bypass Air Terminal. Air Terminal, typically having more than one
23、outlet, that uses a method of volume modulation whereby airflow is varied by distributing that volume required to meet the space requirements with the balance of primary air being diverted away from the space. 3.5.2 Dual Duct Air Terminal. Air Terminal that mixes varying portions of two independent
24、sources of primary air. 3.5.3 Induction Air Terminal. Air Terminal, typically having more than one inlet, that supplies varying proportions of primary and induced air (excludes Fan-Powered Terminals). 3.5.4 Integral Diffuser Air Terminal. Diffuser with the features of an Air Terminal. Air is modulat
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ANSIAHRI881SI2011PERFORMANCERATINGOFAIRTERMINALSINCORPORATESADDENDUM1062012PDF

链接地址:http://www.mydoc123.com/p-430627.html