ARI GUIDELINE E-1997 Fouling Factors A Survey of Their Application in Today磗 Air Conditioning and Refrigeration Industry《污垢系数 空调和冷却工业使用调查》.pdf
《ARI GUIDELINE E-1997 Fouling Factors A Survey of Their Application in Today磗 Air Conditioning and Refrigeration Industry《污垢系数 空调和冷却工业使用调查》.pdf》由会员分享,可在线阅读,更多相关《ARI GUIDELINE E-1997 Fouling Factors A Survey of Their Application in Today磗 Air Conditioning and Refrigeration Industry《污垢系数 空调和冷却工业使用调查》.pdf(8页珍藏版)》请在麦多课文档分享上搜索。
1、 STD-AR1 GUIDELINE E-ENGL 1997 0352320 00LlLOb 039 M 1997 GUIDELINE for AIR-CONDITIONING thus increasing operating com by8Z. The impact couid be greater or less tim this, depending m the typeandamount of tube surface used in condenser and evaporam. waterchillingrefiigmoperatingfullyloadedat Section
2、5. Current Status Sevaal events have occurred in recent years to change the way the industry deals with fouling, as noted in the foUOwing paragraphs: 5.1 The air canditiang industry has beai under pressure to improve unit efficiency and has responded with signiflcant improvements. This has been done
3、 Uuough improved compressors and improved heat exchangers to reduce the approach temperatures within heat exchangers. Where heat exchangers used to have 5“ to 6F 2.7“ to now have and 2F l.l“C leaving temptwe differences. With these small leaving temperature diEerences the field fouling allowance of
4、O.ooO25 or 2.5 x 104 hr ff “F/Btu 4.4 x lo5 n? “C/Wl is now more of the total heat transfer resistance than it was when designs were based on 5F and 6F 2.7“C and 3.3“CJ leaving temperature differences. Due to this, the use of a field fouling allowance of 0.00025 or 2.5 x lo4 hr ff“F/Btu 14.4 x 18 m2
5、 “C/wJ can in some cases result in the selection of different equipment than if the field fouling allowance were lower. This will then result in equipment that may not be as efficient when operating with clean tubes. 3.3“C leawig tnnperatirre differences, many applications 5.2 As a result ofa lack o
6、fhdamental data to justify the use ofa field fouling allowance of 0.00025 or 2.5 x lo“ hr ff “F/Btu 4.4 x lo- m2 “Cm, a research project was undertaken by ASHRAE to evaluate water quality and its effecs on fixding and to experimentally study the tubside fouling resistance in water chiilex flooded ev
7、aporators. The detailsofthesestudiesare Summarized in ASHRAE papers listed in Appendix B. 53 in the work associated with refemce B1.2, several experimental tests wererun with various connbinations of clean water, dirty water, different tube types, and 3 ft/sec. 0.9 ds and 7 ft/sez. 2.1 ds water veio
8、cities. The results inciicateci that even in the worst Case, the levei of fouing aftaexteridedoperation was less than 11.6% of the standard practice of using 0.00025 or 2.5 x IV hr HZ“FBtu 4.4 x 10 m2 “C/WJ. This result indimes that fa evapmtm, the O.ooo25 a 2.5 x lo- hr ft2“F/Btu 4.4 x 10-5 m2 “Cm
9、is overly conservative and is counter to the efforts to impwe opemtng efciency of chillers. From these results, a field fouling allowance of O.OOO1 or 1.0 x lo4 hr ffF/Btu 1.8 x lo- m2 “C/wJ appears to be more appqrbte for evaporators and is the recommendation of this guideline. This does not apply
10、to condensers, as experimental data for condensers has not bem developed. It is expected that the condenser would most likely have a higher fouling due to the higher temperatures of the water and the formation of biological fcung. Natethatresearchhas shown that temperanire can be a strong amhibutor
11、to the rate of fouling and condenser waterismuchwannerdianevaporator water. Ais0 mling tom tend tohave more contaminants in the water due to the loss of water due to evaporation in the tower. 5.4 ASHRAE is pianning to Continue fouling research on condensers, but results are now conclusive that a fou
12、ling allowance for evaporators of 0.00025 or 2.5 x 104 hr ft2“F/Btu 4.4 x lo d “Cm is overly conservative and should be reduced to the O.OOO1 or 1.0 x lV hr ff “F/Btu f1.8 10-5 rn2 ocm . Section 6. Implementation 6.1 In response to the above mentioned developments, Al began an effart to moncile the
13、treatment of fouling in its product standards with current lmowiedge and methods. By so doing, it was anticipated that old unsupported practices would be dropped and the new evaporam field fouling allowances adopted. This effort will ailow for the continued improvement and opthkation of air- conditi
14、oning and refiigdon equipment and the reduction in energy operating costs through proper selection of equipment. Section 7. Conclusions 7.1 The air-conditioning and refrigeration industry will adopt the new evaporam field fouling allowance of O.OOO1 or 1.0 x 104hr*?“F/Btu 1.8 x los m2 “C/Wl under th
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ARIGUIDELINEE1997FOULINGFACTORSASURVEYOFTHEIRAPPLICATIONINTODAY AIRCONDITIONINGANDREFRIGERATIONINDUSTRY

链接地址:http://www.mydoc123.com/p-429477.html