AIR FORCE A-A-59823-2009 LOAD BANK ELECTRICAL 28 VOLTS DC 350 AMPS《28V DC 350A电气负荷组》.pdf
《AIR FORCE A-A-59823-2009 LOAD BANK ELECTRICAL 28 VOLTS DC 350 AMPS《28V DC 350A电气负荷组》.pdf》由会员分享,可在线阅读,更多相关《AIR FORCE A-A-59823-2009 LOAD BANK ELECTRICAL 28 VOLTS DC 350 AMPS《28V DC 350A电气负荷组》.pdf(5页珍藏版)》请在麦多课文档分享上搜索。
1、 A-A-59823 19 February 2009 COMMERCIAL ITEM DESCRIPTION LOAD BANK, ELECTRICAL 28 VOLTS DC, 350 AMPS The General Services Administration has authorized the use of this commercial item description for all federal agencies. 1. SCOPE. This Commercial Item Description (CID) describes a direct current (DC
2、) lightweight, suitcase size, and portable type load bank, accessories and case. The commercially available load bank shall be suitable for electrical performance testing of ground power supplies, battery banks and generators. 2. CLASSIFICATION. Equipment covered by this CID shall be commercially av
3、ailable portable equipment and may be modified to the extent necessary to meet the following description. 3. SALIENT CHARACTERISTICS 3.1 Safety and Environmental. The equipment shall meet all safety and environmental requirements as specified in MIL-PRF-28800 for Class 2 equipment, except as stated
4、herein. 3.2 Electrical Power Sources. All operating power for internal circuits of the suitcase size load bank shall be derived from the output power of the source being tested. 3.3 Operating Temperature. The equipment shall meet its performance and accuracy requirements in an operating environment
5、of -40 degrees F to +125 degrees F. 3.4 Non-operating Temperature. The equipment shall meet its performance and accuracy requirements after being in a non-operating environment (Storage Temperature) of -60 degrees F to +160 degrees F. Beneficial comments, recommendations, additions, deletions, clari
6、fications, etc. and any other data that may improve this document should be sent to: WR-ALC/642 CBSG/GBEA, 460 Richard Ray Blvd, Suite 200, Robins AFB, GA 31098-1813. Since contact information can change, you may want to verify the currency of this address information using the ASSIST Online databas
7、e at http:/assist.daps.dla.mil AMSC N/A FSC 6150 INCH-POUND Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-A-A-59823 2 3.5 Mean Time Between Failures. (MTBF). The equipment Mean Time Between Failures (MTBF) shall be 2,000 hours. The lower test MTBF
8、shall be 2,000 hours and the upper test MTBF shall be 4,000 hours. 3.6 Calibration and Maintenance Adjustments. The design of the system shall provide for readily accessible calibration adjustments and maintenance adjustments. The calibration adjustments, wherever possible, shall be accessible witho
9、ut removal of the instrument case or modules. These adjustments shall be provided by variable value components, which are adjustable, by the use of simple means. The calibration by substitution of selected components or parts is unacceptable unless specifically approved. The calibration interval sha
10、ll be a period of one year or greater based on an operating time of 2,000 hours. 3.7 Resistive Load Testing. 3.7.1 Design. The load bank shall be designed for field service and be completely self contained and air cooled. 3.7.2 Application. The suitcase size load bank shall be capable of resistive l
11、oad testing of ground power supplies, batteries and generator sets producing 28 volt DC (+/-5%), power. 3.7.3 Rating. The load bank shall have a minimum resistive load test rating of 10 kW (+/- 2%) at 350 amps, and 28 volts. 3.7.4 Load adjustment. The load bank shall have the capability for variable
12、 and step loading. Fixed step loading shall be provided at 100 and 200 amps and an adjustable step load from 0 to 100 amps, or similar combinations, shall be available to supply total load continuous values from 0 to 350 amps at 28 VDC. 3.7.5 Operation. The load bank shall be capable of a continuous
13、 run at full load for up to an hour. The load bank shall be capable of cool down within 5 minutes, under no load conditions, and be capable of performing multiple back to back full loads without damage to components. 3.8 Instruments and Controls 3.8.1 Meters and Indicators. The load bank control pan
14、el shall have as a minimum have the following items: DC Voltmeter 0 - 50 volts, DC Ammeter 0 - 400 amps, power-available indicator lamp, load step/adjustment controls and plug style test lead pins (for voltage monitoring and testing). Meter accuracy shall be not less than +/- 3%. 3.8.2 Protection. T
15、he load bank and load elements shall be adequately protected with resettable/replaceable circuit breakers, fuses, thermal switches or other protective devices. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-A-A-59823 3 3.9 Cables 3.9.1 Power cables.
16、 The load bank shall be provided with two each, 10 ft. cables capable of effectively carrying a DC current of 350 amps. The cables shall be clearly and permanently labeled at each end (1) DC Pos (+) and (2) DC Gnd (-). The end of each cable that connects to the power source unit under test (uut) sha
17、ll have 3/8 inch inside diameter closed loop type terminal lug to connect to the uut. The other end of each cable shall be terminated for proper connection to the load bank power input. 3.9.2 Sense cables. The load bank shall be provided with two each, 10 ft. sense cables to connect the load bank to
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
2000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- AIRFORCEAA598232009LOADBANKELECTRICAL28VOLTSDC350AMPS28VDC350A 电气 负荷 PDF

链接地址:http://www.mydoc123.com/p-427182.html