《IEC TR3 61334-1-4-1995 Distribution automation using distribution line carrier systems - Part 1 General considerations - Section 4 Identification of data transmission parameters co.pdf》由会员分享,可在线阅读,更多相关《IEC TR3 61334-1-4-1995 Distribution automation using distribution line carrier systems - Part 1 General considerations - Section 4 Identification of data transmission parameters co.pdf(60页珍藏版)》请在麦多课文档分享上搜索。
1、RAPPORT CE1 TECHNIQUE TECHNICAL REPORT IEC 1334-1 14 Premire dition First edition 1995-1 1 Automatisation de la distribution laide de systmes de communication courants porteurs - Partie 1 : Con si d rat ions gnrales - Section 4: Identification des paramtres de trans- mission de donnes des rseaux de
2、distribution moyenne et basse tension Distribution automation using distribution line carrier systems - Part 1 : General considerations - Section 4: Identification of data transmission parameters concerning medium and low-voltage distribution mains Numro de rfrence Reference number CEVIEC 1334-1 -4:
3、 1995 Copyright International Electrotechnical Commission Provided by IHS under license with IECNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-Numros des publications Depuis le ler janvier 1997, les publications de la CE1 sont numrotes a partir de 60000. Publicati
4、ons consolides Les versions consolides de certaines publications de la CE1 incorporant les amendements sont disponibles. Par exemple, les numros ddition 1.0, 1.1 et 1.2 indiquent respectivement la publication de base, la publication de base incorporant lamendement 1, et la publication de base incorp
5、orant les amendements 1 et 2. Validit de la prsente publication Le contenu technique des publications de la CE1 est constamment revu par la CE1 afin quil reflte ltat actuel de la technique. Des renseignements relatifs la date de reconfirmation de la publication sont disponibles dans le Catalogue de
6、la CEI. Les renseignements relatifs des questions ltude et des travaux en cours entrepris par le comit technique qui a tabli cette publication, ainsi que la liste des publications tablies, se trouvent dans les documents ci- dessous: Site web) de la CEI Catalogue des publications de la CE1 Publi annu
7、ellement et mis jour rgulirement (Catalogue en ligne)* Disponible la fois au ) un comportement trs slectif avec une frquence de rsonance denviron 50 kHz et une impdance correspondante trs basse (environ 0,Ol Q). Cela signifie que limpdance augmente trs rapidement pour des frquences du signal de tran
8、smission sloignant de cette rsonance. La courbe montre le comportement typique de la mme batterie de condensateurs MT mais avec des cbles de raccordement lectriques externes plus longs (environ 1,5 m). On peut noter le dplacement de la rsonance vers 30 kHz, ainsi quune importante variation de limpda
9、nce en fonction de la frquence. Copyright International Electrotechnical Commission Provided by IHS under license with IECNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-1334-1 -4 O IEC:1995 -11 - Available information refers to transmission characteristics of a se
10、ction of distribution network between two coupling points, e.g. the points where transmission signals are transmitted/ received. There are two cases to be considered when two coupling points are, from a transmission point of view, either interconnected or disconnected. The first case happens when th
11、ere is a galvanic continuity between the two coupling points or if transmission continuity is ensured by means of an appropriate devices such as a by-pass. The second case happens when neither galvanic nor transmission continuity exists. With reference to two interconnected coupling points, the para
12、meters assumed to identify the characteristics of the corresponding transmission channel are: - the impedance, as a function of frequency and time, related to each coupling point zc (f, 0 - the transmission transfer function, as a function of frequency and time, between the two considered coupling p
13、oints, Hc ( f, 0 NOTE - The module is the ratio of received signal amplitude to transmitted signal amplitude and the phase is the difference between the received signal phase and the transmitted signal phase. - the noise, as a function of frequency and time, related to each coupling point Nc (f, 0 W
14、ith reference to two disconnected coupling points, the most important transmission parameter is: - the cross-talk transfer function, as a function of frequency and time, between the two considered coupling points cc (f, t) NOTE - The module is the ratio of received signal amplitude to transmitted si
15、gnal amplitude and the phase is the difference between the received signal phase and the transmitted signal phase. The above mentioned parameters allow the evaluation of the expected channel characteristics by the creation of a mathematical model approximating the real channel. 3 Transmission parame
16、ters of the main components of a distribution network 3.1 Capacitors MV capacitor banks, for reactive power compensation, installed in HV/MV or MV/LV substations present (figure 1, curve “a“) a very high selective behaviour with a resonance frequency of about 50 kHz and a very low corresponding impe
17、dance (about 0,Ol Q). This means that the impedance rapidly increases when the frequency of the transmission signal is far from the resonance point. Curve “b“ shows the typical behaviour of the same MV capacitor banks provided with external electrical connections of longer length (about 1,5 m). It c
18、an be noticed that the resonance point falls to about 30 kHz, thus significantly modifying the impedance values as a function of the frequency. Copyright International Electrotechnical Commission Provided by IHS under license with IECNot for ResaleNo reproduction or networking permitted without lice
19、nse from IHS-,-,- 12 - 1334-1-4 O CE1:1995 En pratique, ces cbles ayant gnralement une longueur suprieure 1,5 m, le dcalage de la rsonance vers des frquences en dessous de 30 kHz autorise lemploi de frquences au- dessus de 50 kHz sans que les batteries de condensateurs MT ne provoquent dattnuation t
20、rop importante du signal de transmission. La consquence en est que dans la plage au-del de 50 kHz, les batteries de condensateurs MT nimposent pas lusage de circuits-bouchons des fins de transmission. Pour les condensateurs BT, la situation est similaire et on arrive aux mmes conclusions. La courbe
21、c montre le comportement typique dun condensateur BT avec cbles de connexions externes trs courts. La courbe externes correspond des cbles denviron 13 m pour le mme condensateur BT. En pratique, la longueur des cbles est suprieure cette valeur. Dans tous les cas, ia longueur relle peut tre facilemen
22、t augmente en insrant de simples tores de ferrite afin dobtenir une valeur suffisante de limpdance (de 20 d 30 d) afin de ne pas affecter la transmission de signaux. 3.2 Transformateurs Les transformateurs prsentent de faon typique en extrmit de la ligne MT une valeur dimpdance fonction de la frquen
23、ce. La figure 2a montre cette variation pour un transformateur MT/BT en fonction de la frquence du signal de transmission dans deux configurations diffrentes: enroulement secondaire en circuit ouvert et en court-circuit. Dans la plage de 10 kHz 200 kHz, cette impdance est de type capacitif et dcrot
24、avec la frquence. La rsonnance dun transformateur MT/BT est gnralement infrieure 10 kHz. Bien que dpendant du type et de la classe du transformateur, les valeurs releves constituent une rfrence acceptable. Limpdance de 1 kQ 50 kQ est plus leve que limpdance caractristique de la ligne qui se situe en
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- IECTR361334141995DISTRIBUTIONAUTOMATIONUSINGDISTRIBUTIONLINECARRIERSYSTEMSPART1GENERALCONSIDERATIONSSECTION4IDENTIFICATIONOFDATATRANSMISSIONPARAMETERSCOPDF

链接地址:http://www.mydoc123.com/p-1238199.html