1、NEMA Standards PublicationNational Electrical Manufacturers AssociationNEMA ICS 10-2015, Part 4Guide to Application of Low-voltage Automatic Transfer Switch EquipmentA NEMA Industrial Automation Control Products and Systems (01IS) Section Document ICS 10-2015, Part 4 Guide to Application of Low-volt
2、age Automatic Transfer Switch Equipment Published by: National Electrical Manufacturers Association 1300 North 17th Street, Suite 900 Rosslyn, Virginia 22209 www.nema.org 2015 National Electrical Manufacturers Association. All rights, including translation into other languages, reserved under the Un
3、iversal Copyright Convention, the Berne Convention for the Protection of Literary and Artistic Works, and the International and Pan American copyright conventions. NEMA ICS 10-2015, Part 4 Page 2 2015 National Electrical Manufacturers Association Section 110.9 of NFPA 70, the National Electrical Cod
4、e (NEC) requires that equipment intended to interrupt current at varying fault levels shall have an interrupting rating (IR) that is sufficient for nominal circuit voltage and the current that is available at the line terminals of the equipment. NEC Section 110.10 requires that overcurrent protectiv
5、e devices be selected and applied to prevent extensive damage to a circuits electrical components during a fault condition, such as transfer switches. Proper selection of protective devices has always been important; with changes to the NEC to more explicitly require selectivity, product information
6、 and markings have received more scrutiny. In response, the standards committees responsible for transfer switches have revised the labeling requirements for devices listed to the harmonized North American standard known in the US as UL 1008, in Canada as C22.2 No. 178.1, and in Mexico as ANCE NMX-J
7、-672. These new labeling requirements affect all products marked as a “transfer switch,” whether automatic for emergency use, automatic for optional use, or manual. A transfer switch with integral overcurrent protection, whether a circuit breaker or a fuse, states its short-circuit withstand/closing
8、 rating based on the integral protection. Therefore, these devices did not require marking changes. A transfer switch without integral overcurrent protection must, of course, be protected. It might be protected by fuses or by specific circuit breakers, according to its markings, which is current pra
9、ctice. The first new aspect is that the transfer switch may be marked as having a rating at a certain current level and time duration. For example, 42 kA at 600 V for 0.05 seconds. The time duration is in seconds to align with the time-current curves from circuit breaker manufacturers. To properly a
10、pply the transfer switch, the operating time of the protective device must be the same as or faster than the time rating of the transfer switch. In addition to short-circuit current and time rating, a transfer switch will be marked with a short-time rating, or will be marked as not having a short-ti
11、me rating. This change is in response to concerns that low-voltage power circuit breakers or insulated case circuit breakers might have the instantaneous trip disabled in the field and not properly protect a transfer switch that does not have a short-time rating. These new markings first went into e
12、ffect in August 2014. Users and inspectors should expect to see the new markings over the next year. These new markings apply in Canada and Mexico also, because the requirements are in the tri-nationally harmonized standard. The following example markings are copied from the product standard UL 1008
13、/CSA C22.2 No. 178-1/ NMX-J-672 ANCE, Transfer Switch Equipment. It is instructive to compare the different markings, since each one is related to a different kind of qualification. NEMA ICS 10-2015, Part 4 Page 3 2015 National Electrical Manufacturers Association Example for a device with short-cir
14、cuit but not short-time current ratings, with integral overcurrent protection. SHORT-CIRCUIT WITHSTAND AND CLOSING RATINGS THIS TRANSFER SWITCH IS SUITABLE FOR USE IN A CIRCUIT CAPABLE OF DELIVERING THE SHORT-CIRCUIT CURRENT FOR THE MAXIMUM VOLTAGE MARKED BELOW. WHEN PROTECTED BY A CIRCUIT BREAKER,
15、IT SHALL NOT INCLUDE A SHORT-TIME TRIP RESPONSE. SHORT-CIRCUIT CURRENT VOLTAGE (RMS SYMMETRICAL AMPERES X 1000) (VOLTS AC, MAXIMUM) 65 240 50 480 42 600 SHORT-TIME CURRENT RATINGS THIS TRANSFER SWITCH DOES NOT INCLUDE SHORT-TIME CURRENT RATINGS NEMA ICS 10-2015, Part 4 Page 4 2105 National Electrica
16、l Manufacturers Association Example for a device with short-circuit and short-time current ratings, with integral overcurrent protection. SHORT-CIRCUIT WITHSTAND/CLOSING AND SHORT-TIME CURRENT RATINGS THIS TRANSFER SWITCH IS SUITABLE FOR USE IN A CIRCUIT CAPABLE OF DELIVERING THE SHORT-CIRCUIT CURRE
17、NT FOR THE MAXIMUM VOLTAGE MARKED BELOW. WHEN PROTECTED BY A CIRCUIT BREAKER WITH A SHORT-TIME TRIP RESPONSE, THE SHORT-TIME RESPONSE OF THE CIRCUIT BREAKER MUST BE COORDINATED WITH THE SHORT-TIME CURRENT RATING OF THE TRANSFER SWITCH AS MARKED BELOW. SHORT-CIRCUIT CURRENT VOLTAGE (RMS SYMMETRICAL A
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- NEMAICS10PART42015GUIDETOAPPLICATIONOFLOWVOLTAGEAUTOMATICTRANSFERSWITCHEQUIPMENTPDF

链接地址:http://www.mydoc123.com/p-994235.html