1、*USACE / NAVFAC / AFCESA / NASA UFGS-21 13 20.00 20 (November 2009)-Preparing Activity: NAVFAC SupersedingUFGS-21 13 20.00 20 (April 2006UFGS-13956N (September 1999)UNIFIED FACILITIES GUIDE SPECIFICATIONSReferences are in agreement with UMRL dated October 2009*SECTION TABLE OF CONTENTSDIVISION 21 -
2、FIRE SUPPRESSIONSECTION 21 13 20.00 20FOAM FIRE EXTINGUISHING FOR AIRCRAFT HANGARS11/09PART 1 GENERAL1.1 REFERENCES1.2 RELATED REQUIREMENTS1.3 SYSTEM DESCRIPTION1.3.1 Design Requirements1.3.1.1 Shop Drawings1.3.1.2 Calculations1.3.1.3 AFFF Containment and Disposal Plan1.3.1.4 As-Built Drawings for t
3、he Fire Extinguishing System1.3.2 System Operation1.3.2.1 Overhead Systems1.3.2.2 Monitor System1.3.2.3 Hose System1.4 SUBMITTALS1.5 QUALITY ASSURANCE1.5.1 Qualifications of Installer1.6 SPARE PARTSPART 2 PRODUCTS2.1 DESIGN OF FOAM SYSTEMS2.1.1 Sprinkler Heads2.1.2 Cabinet2.1.3 Deluge Pre-Action Val
4、ves2.1.4 AFFF Solution Distribution2.1.5 AFFF Solution Application Density2.1.6 Sprinkler Discharge Area2.1.7 Friction Losses2.1.8 Location of Sprinkler Heads2.1.9 Water Supply2.1.10 Duration of Discharge2.2 ELECTRIC DETECTION DEVICES2.2.1 Control Panel2.2.1.1 Main AnnunciatorSECTION 21 13 20.00 20
5、Page 1Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-2.2.1.2 Initiating Zones2.2.1.3 Remote Annunciator Panel2.2.2 Auxiliary Power Supply2.2.2.1 Storage Batteries2.2.2.2 Battery Charger2.3 PNEUMATIC DETECTION SYSTEM2.3.1 Air Compressor2.3.2 Piping a
6、nd Control Panel2.4 PIPING SUPERVISION2.5 MANUAL RELEASE STATIONS2.6 HEAT DETECTORS2.6.1 Combination Fixed Temperature Rate-of-Rise Detectors2.6.2 Rate Compensating Detector2.7 OPEN-AREA (SPOT-TYPE) SMOKE DETECTORS2.7.1 Ionization Detectors2.7.2 Photoelectric Detectors2.7.3 Detector Spacing and Loca
7、tion2.8 COMBINATION ULTRAVIOLET-INFRARED FLAME DETECTORS2.9 ELECTRICAL WORK2.9.1 Wiring2.9.2 Operating Power2.9.3 Conductor Identification2.10 SYSTEM ACTIVATION2.10.1 Overhead System Activation2.10.2 Monitor System Activation2.10.3 Hose System Activation2.11 ALARMS2.11.1 Water Motor Alarms2.11.2 Loc
8、al Alarm2.11.3 Fire Alarm2.11.3.1 Pressure Switch2.11.4 Trouble Alarm2.12 TANK MOUNTED AIR COMPRESSOR2.13 AFFF CONCENTRATE2.13.1 Concentrate Fill Pump2.14 DIAPHRAGM PRESSURE PROPORTIONING EQUIPMENT2.14.1 Diaphragm Pressure Proportioning Tanks2.14.2 Concentrate Ratio Controller2.15 BALANCED PRESSURE
9、PROPORTIONING SYSTEM2.15.1 Skid-Mounted Balanced Pressure Proportioning System2.15.2 In-Line Balanced Pressure Proportioning System2.15.3 AFFF Concentrate Storage Tanks2.16 OSCILLATING MONITOR NOZZLES2.17 HAND HOSE LINES2.18 WALL FOAM HYDRANTS2.19 ABOVEGROUND PIPING SYSTEMS2.19.1 Pipe, Fittings, and
10、 Mechanical Couplings2.19.2 Jointing Material2.19.3 Duplex Basket Strainers2.19.4 Pipe Hangers and Supports2.19.5 Valves2.19.6 Identification Signs2.19.7 Inspectors Test Connection2.19.8 Main Drains2.19.9 Pipe Sleeves2.19.9.1 Sleeves in Masonry and Concrete Walls, Floors, Roofs2.19.9.2 Sleeves in Pa
11、rtitions2.19.10 Escutcheon Plates2.19.11 Fire Department Inlet ConnectionsSECTION 21 13 20.00 20 Page 2Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-2.19.12 Backflow Preventers2.20 BURIED PIPING SYSTEMS2.20.1 Pipe and Fittings2.20.2 Valves2.20.3 Po
12、st Indicator Valves2.20.4 Valve Boxes2.20.5 Buried Utility Warning and Identification TapePART 3 EXECUTION3.1 EXCAVATION, BACKFILLING, AND COMPACTING3.2 CONNECTIONS TO EXISTING WATER SUPPLY SYSTEMS3.3 AFFF SYSTEM INSTALLATION3.4 DISINFECTION3.5 FIELD PAINTING3.5.1 Foam Systems in Unfinished Areas3.5
13、.2 Foam Systems in All Other Areas3.5.3 Piping Labels3.5.4 Field Touch-Up3.6 ELECTRICAL WORK3.6.1 Wiring3.7 FLUSHING3.8 FIELD QUALITY CONTROL3.8.1 Preliminary Tests3.8.2 Formal Inspection and Tests (Acceptance Tests)3.8.2.1 Systems and Device Testing3.8.2.2 AFFF Discharge and Concentration Testing3.
14、8.2.3 Flushing and Rinsing3.8.3 Environmental Protection3.8.4 Additional Tests3.8.5 AFFF Concentrate Storage Tanks Fill-Up3.8.6 Manufacturers Representative3.9 OPERATING INSTRUCTIONS3.10 TRAINING REQUIREMENTS3.11 SCHEDULE- End of Section Table of Contents -SECTION 21 13 20.00 20 Page 3Provided by IH
15、SNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-*USACE / NAVFAC / AFCESA / NASA UFGS-21 13 20.00 20 (November 2009)-Preparing Activity: NAVFAC SupersedingUFGS-21 13 20.00 20 (April 2006UFGS-13956N (September 1999)UNIFIED FACILITIES GUIDE SPECIFICATIONSReferences a
16、re in agreement with UMRL dated October 2009*SECTION 21 13 20.00 20FOAM FIRE EXTINGUISHING FOR AIRCRAFT HANGARS11/09*NOTE: This guide specification covers the requirements for automatic deluge, and pre-action fire extinguishing foam systems for aircraft hangars.Edit this guide specification for proj
17、ect specific requirements by adding, deleting, or revising text. For bracketed items, choose applicable items(s) or insert appropriate information.Remove information and requirements not required in respective project, whether or not brackets are present.Comments and suggestions on this guide specif
18、ication are welcome and should be directed to the technical proponent of the specification. A listing of technical proponents, including their organization designation and telephone number, is on the Internet.Recommended changes to a UFGS should be submitted as a Criteria Change Request (CCR).*NOTE:
19、 For fuel tank farm protection use Section 21 13 21.00 20 FOAM FIRE EXTINGUISHING FOR FUEL TANK PROTECTION. For hazardous and flammable handling and storage facilities such as truck or rail loading/unloading racks, hazardous/flammable liquid warehouses, fuel pump houses and laboratories, use Section
20、 21 13 22.00 20 FOAM FIRE EXTINGUISHING FOR HAZ/FLAM MATERIAL FACILITY. Choose the type of system most appropriate for the hazard. Deluge systems are primarily intended for fire protection of aircraft hangar facilities. Pre-action systems may be required for Air Force hangars even though NFPA 409 re
21、commends deluge systems for aircraft hangars. Consult the current edition of AFR 88-15, “Criteria and Standards for Air Force Construction“ for Air Force projects. Pre-action systems provide SECTION 21 13 20.00 20 Page 4Provided by IHSNot for ResaleNo reproduction or networking permitted without lic
22、ense from IHS-,-,-added safety against accidental discharge by requiring both actuation of a detector and fusing of a sprinkler head before foam discharge will occur. Deluge systems provide the fastest fire extinguishment. Areas larger than 279 sq meters 3,000 square feet and all deluge systems must
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- NAVYUFGS21132000202009FOAMFIREEXTINGUISHINGFORAIRCRAFTHANGARS 飞机库 泡沫 消防设施 PDF

链接地址:http://www.mydoc123.com/p-984786.html